![Midea KJRM-120H2/BMWKO-E Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/midea/kjrm-120h2-bmwko-e/kjrm-120h2-bmwko-e_owners-manual_1790916051.webp)
47
Addresses below can be used as 03(Read Holding Registers), 06(Write
Single Register)
Data Content
Address of
Register
Notes
FORCED HEAT2 ON 202+(Unit
Address) *100
Enable/Disable
1/0 (Available for multiple pump)
Set as 1 is invalid before HEAT2
ENABLE is set as YES.
DHW SWITCH
206+(Unit
Address) *100
Enable/Disable
1/0 (Available for multiple
pump
)
DHW MODE ON/
OFF
207+(Unit
Address) *100
Enable/Disable
Set as 1 is invalid before DHW
SWITCH is set as YES.
1/0 (Available for multiple
pump
)
Water Set
Temperature of the
selected unit
217+(Unit
Address) *100
(30°C~60°C)
(Available for multiple pump)
Note: 1. 06 Write register, if the value is written beyond the scope of the note,
the exception code is returned.
2. Unit Address stands for machine address 0-15, 0 stands for host 0.
Содержание KJRM-120H2/BMWKO-E
Страница 55: ...WP MD20U 034B EN 16127100001177...
Страница 56: ......