8.4.2 Cooling Mode
8.4.2.1 Compressor running rules
The maximum operation frequency of compressor after starting submits to following rule.
45
43
40
38
31.5
29.5
22
20
Fmax=F4
Fmax=F7
Fmax=F8
Fmax=F6
Fmax=F3
If users switch on AC by remote controller, the compressor will run at the Fmax frequency for 7
minutes according to the outdoor ambient temp. During the 7 minutes, the frequency limitation is active.
7 minutes later, the compressor running frequency will be controlled as below:
3.5
3.0
2.5
2.0
1.5
1.0
0.5
-0.5
-1.0
A
B
C
D
E
F
G
H
While the zones of A,B,C... are corresponding to different compressor running frequency.
Note:
When T1-Ts keeps in the same temp. zone for 3 minutes, the compressor will run as the below rules:
A~E: Increase the frequency to the higher level until to F8.
Содержание 11DSNA-A-1301
Страница 1: ...NEOLA INVERTER SERIES Service Manual 2013 11DSNA A 1301...
Страница 18: ...16 MS11D 22CRDN1 MN10W MS11D 22HRDN1 MN10W...
Страница 20: ...18 MOC 18CDN1 MN10W MOC 18HDN1 MN5W...
Страница 21: ...19 MOF 22CDN1 MN5W MOF 22HDN1 MN5W...
Страница 32: ...30 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 52: ...50 9 2 2 Indoor outdoor unit s communication error diagnosis and solution E1...
Страница 55: ...53 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3...
Страница 56: ...54 9 2 5 IPM malfunction or IGBT over strong current diagnosis and solution P0...
Страница 57: ...55 9 2 6 Over voltage or too low voltage protection diagnosis and solution P1...
Страница 58: ...56 9 2 7 High temperature protection of compressor top diagnosis and solution P2...
Страница 59: ...57 9 2 8 Inverter compressor drive error diagnosis and solution P4...