39
+5.0
+4.5
+3.5
+3.0
+2.5
+2.0
+1.5
+1.0
H
G
F
E
D
C
B
A
+0.5
While the zones of A,B,C... are corresponding to different compressor running frequency.
ΔT=0
℃
as default.
Note:
When T1-Ts keeps in the same temp. zone for 3 minutes, the compressor will run as the below rules:
A~E: Increase the frequency to the higher level until to F10.
F: Keep the current frequency.
G: Decrease the frequency to the lower level until to F1.
H: Run at F1 for 1h.(if T1-Ts-ΔT >6
℃
, the compressor will stop)
Meanwhile, the compressor running frequency is limited by the current.
I3HEAT
I2HEAT
I1HEAT
Off
Decrease
Hold
Resume
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower level.
Содержание 11DSNA-A-1301
Страница 1: ...NEOLA INVERTER SERIES Service Manual 2013 11DSNA A 1301...
Страница 18: ...16 MS11D 22CRDN1 MN10W MS11D 22HRDN1 MN10W...
Страница 20: ...18 MOC 18CDN1 MN10W MOC 18HDN1 MN5W...
Страница 21: ...19 MOF 22CDN1 MN5W MOF 22HDN1 MN5W...
Страница 32: ...30 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 52: ...50 9 2 2 Indoor outdoor unit s communication error diagnosis and solution E1...
Страница 55: ...53 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3...
Страница 56: ...54 9 2 5 IPM malfunction or IGBT over strong current diagnosis and solution P0...
Страница 57: ...55 9 2 6 Over voltage or too low voltage protection diagnosis and solution P1...
Страница 58: ...56 9 2 7 High temperature protection of compressor top diagnosis and solution P2...
Страница 59: ...57 9 2 8 Inverter compressor drive error diagnosis and solution P4...