Indoor fan speed can be set as high, medium, low or auto fan and the anti-cold-wind function is
preferential.
Auto fan action in heating mode:
2.5
2
High
Low
1
Medium
1.5
8.4.3.4 Defrosting mode
Condition of defrosting:
----T4
>
0
℃
,
When the units are running, if the following two items are satisfied, the units start defrosting:
The units run with T3
<
3
℃
for 40 minutes and T3 keeps lower than TCDI
℃
for more than 3 minutes.
The units run with T3
<
3
℃
for 80 minutes and T3 keeps lower than TCDI+2
℃
for more than 3
minutes.
----T4
<
0
℃
,
If the 1
st
condition and 2
nd
condition items are satisfied, then the program judges if T2 has decreased
more than 5
℃
.When T2 has decreased more than 5
℃
, enter the defrosting mode.
----No matter what value T4 is, if the machine runs with T3
<
3
℃
for more than 120 minutes and T3
keeps lower than TCDI+4
℃
for more than 3 minutes, the machine will enter defrosting mode no
matter if T2 drops more than 5
℃
or not.
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will finish and the machine will turn to
normal heating mode.
----T3 rises to be higher than TCDE1
℃
.
----T3 keeps to be higher than TCDE2
℃
for 80 seconds.
----The machine has run for 10 minutes in defrosting mode.
Содержание 11DSNA-A-1301
Страница 1: ...NEOLA INVERTER SERIES Service Manual 2013 11DSNA A 1301...
Страница 18: ...16 MS11D 22CRDN1 MN10W MS11D 22HRDN1 MN10W...
Страница 20: ...18 MOC 18CDN1 MN10W MOC 18HDN1 MN5W...
Страница 21: ...19 MOF 22CDN1 MN5W MOF 22HDN1 MN5W...
Страница 32: ...30 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 52: ...50 9 2 2 Indoor outdoor unit s communication error diagnosis and solution E1...
Страница 55: ...53 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3...
Страница 56: ...54 9 2 5 IPM malfunction or IGBT over strong current diagnosis and solution P0...
Страница 57: ...55 9 2 6 Over voltage or too low voltage protection diagnosis and solution P1...
Страница 58: ...56 9 2 7 High temperature protection of compressor top diagnosis and solution P2...
Страница 59: ...57 9 2 8 Inverter compressor drive error diagnosis and solution P4...