8.4.3.5 Evaporator coil temperature protection
----T2> TEH2
℃
, the compressor running frequency decreases to the lower level and runs for 20s.
When the frequency decreases to F2 and the T2 is still over TEH2
℃
for 3 minutes, the compressor
will stop.
----T2<48
℃
or T2 stays in 48
℃
~ TEH2
℃
for 6 minutes, the frequency will not be limited by T2.
----T2>60
℃
, the compressor will stop and restart when T2<48
℃
.
8.4.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30
℃
.
In auto mode, the machine will choose cooling, heating or fan-only mode according to ΔT (ΔT =T1-Ts).
ΔT=T1-Ts
Running mode
ΔT
>
1
℃
Cooling
-1<ΔT≤1
℃
Fan-only
ΔT≤-1
℃
Heating
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
8.4.5 Drying mode
8.4.5.1 Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as
in cooling mode.
8.4.5.2 Compressor running rules
Содержание 11DSNA-A-1301
Страница 1: ...NEOLA INVERTER SERIES Service Manual 2013 11DSNA A 1301...
Страница 18: ...16 MS11D 22CRDN1 MN10W MS11D 22HRDN1 MN10W...
Страница 20: ...18 MOC 18CDN1 MN10W MOC 18HDN1 MN5W...
Страница 21: ...19 MOF 22CDN1 MN5W MOF 22HDN1 MN5W...
Страница 32: ...30 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 52: ...50 9 2 2 Indoor outdoor unit s communication error diagnosis and solution E1...
Страница 55: ...53 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3...
Страница 56: ...54 9 2 5 IPM malfunction or IGBT over strong current diagnosis and solution P0...
Страница 57: ...55 9 2 6 Over voltage or too low voltage protection diagnosis and solution P1...
Страница 58: ...56 9 2 7 High temperature protection of compressor top diagnosis and solution P2...
Страница 59: ...57 9 2 8 Inverter compressor drive error diagnosis and solution P4...