Chapter 13 Troubleshooting and repair
Log entry
Parameter
Description
Code
Plain text
Code
Plain text
1600
(1/2)
STATE
(1/2)
1
OK
Last connection OK
2
TRANSMISSION
ERROR
Last transmission faulty
Try again later
3
MEASUREMENT
ERROR
Last measurement faulty
l
Check the configuration.
l
Check the connection between the
device and sensor.
4
HOLD
Standby (GPRS ON, measurement OFF)
If the ALOHA transmission mode is initiated,
the myDatalog4 switches back into "RUN"
mode (GPRS ON, measurement ON).
5
TRANSPORT
Transport lock (GPRS OFF, measurement
OFF)
see "Standby"
6
OFFLINE
Offline (GPRS OFF, measurement ON)
see "Standby"
1600
(2/2)
STATE
(2/2)
7
NO NET (NET LOCK) Netlock/no matching provider
l
Try to improve the position of the
antenna.
l
Check whether the device is in the
coverage area
(www.microtronics.at/footprint).
l
Lift the network block (see
"myDatanetDeviceConfig Manual "
805004)
8
NO NET
No GSM network
l
Improve the position of the antenna
l
Try again later
10
GPRS ERROR
No GPRS connection
Try to improve the position of the antenna.
11
IP ERROR
No myDatanet server available
l
Check whether port 51241 is enabled
on the myDatanet server.
l
Try again later
12
SIM CARD ERROR
Faulty SIM chip
Contact support.
Rev. 01
133
Содержание myDatalog4
Страница 2: ......
Страница 9: ...Chapter 2 Declaration of conformity Chapter 2 Declaration of conformity Rev 01 9 ...
Страница 10: ......
Страница 52: ......
Страница 56: ......
Страница 110: ......
Страница 126: ......
Страница 128: ......
Страница 141: ...Chapter 15 Document history Chapter 15 Document history Rev Date Changes 01 08 07 2014 First version Rev 01 141 ...
Страница 142: ......
Страница 144: ......