Chapter 13 Troubleshooting and repair
Chapter 13 Troubleshooting and repair
13.1 General problems
Problem
Cause/solution
Device does not
respond (status LED
always off)
l
Fully discharged rechargeable battery and battery packs.
Communication
problems
l
Evaluate the status LED blink code (see "Status LED" on page 58).
l
Load the device log from the myDatalog4 or the myDatanet server and
use DeviceConfig for the evaluation (see "Evaluating the device log"
on page 137).
l
The rechargeable battery or battery pack capacity is virtually depleted.
Not all or no data is
available on the
server.
l
The connection was interrupted during transmission, which is indicated
by a time-out entry in the connection list (see "myDatanet Server
Manual " 805002). Solution: Initiate a ALOHA transmission or wait for
the next cyclical transfer.
l
The assignment of the device and site is not correct (see "Site" on page
59).
The data at the
universal input is
not plausible.
l
Check the cable connections (see "Connecting the sensors" on page
38).
l
Check whether the universal input configuration matches the sensor
output signal (see "Measurement channels" on page 59).
Alarm state of a
measurement value
was not detected.
Increase the record interval (attention: This will increase the required data
volume).
Alarm state was not
transferred
although the data is
present.
l
Check the alarm settings of the measurement channel.
l
The connection was interrupted during transmission, which is indicated
by a time-out entry in the connection list (see "myDatanet Server
Manual " 805002). Solution: Initiate a ALOHA transmission or wait for
the next cyclical transfer.
Alarm message was
not sent although
the alarm was
signalled.
l
Check the settings of the alarm schedule (see "myDatanet Server
Manual " 805002).
l
Check the address data of the alarm schedule (see "myDatanet Server
Manual " 805002).
Rev. 01
129
Содержание myDatalog4
Страница 2: ......
Страница 9: ...Chapter 2 Declaration of conformity Chapter 2 Declaration of conformity Rev 01 9 ...
Страница 10: ......
Страница 52: ......
Страница 56: ......
Страница 110: ......
Страница 126: ......
Страница 128: ......
Страница 141: ...Chapter 15 Document history Chapter 15 Document history Rev Date Changes 01 08 07 2014 First version Rev 01 141 ...
Страница 142: ......
Страница 144: ......