POSITION Modes
Description
2
The output ranges from 0V to +10V (ove0.4V) for
CW motion with +10V corresponding to the Voltage Scale
setting (Register 24).
The output ranges from 0V to -10V (overrange -0.4V) for
CCW motion with -10V corresponding to the Voltage Scale
setting (Register 24).
Voltage Scale (Register 0x201)
Register Address: 0x201
The voltage scale can be set by the user to track SPEED or POSITIOIN.
Example: With Voltage Mode set to 0, a Voltage Scale setting of 1000 will provide a full scale
+10V output for 1000RPM (CW) or -10000V output for 1000RPM (CCW). Faster speeds will
linearly extend from ±10V until peaking at approx. 10.4V.
Range
Description
10-100,000
(SPEED)
In SPEED mode a Voltage Scale setting of X establishes
±
10V “full
scale” value to correspond to X RPM.
1-28,388,607
(POSITION)
In POSITION mode, a Voltage Scale setting of X establishes
±
10V
“full scale” output to correspond to X Counter value.