MICRONOR AG
MR340-1 DIN Rail Module Controller
Page 28 of 74
Linear Encoder With Film Without HOMING Region
Hardware Example: MR343 Linear Encoder, MR340-1 Controller and TD5334 series Film Strip
without HOMING region. The diagram below illustrates an application employing a Film Strip
without any HOMING region.
In this section, the MR343 linear encoder uses an Encoder Film Strip without a HOMING
region. That is, the Encoder Film Strip is a sequence of lines only. A typical application will
use the Modbus interface to track position and speed. The quadrature outputs can also be
used independently.
The following tables describe how to initially configure and operate the MR343 system in this
scenario.
Initial Configuration Sequence
Non-HOMING Linear Encoder
Step
Command Name Register Address Notes
1
Reset Mode
FC10 0x208
Set to 1 to reset Position Counter only. For the
Position Counter to function properly, user’s
actuator must be at the reference position
when ZERO Input is pulsed.
2
Preset Value
FC10 0x20A
This will be the Position Counter value when
the actuator is at the reference position.
Typically, the user will set this value to 0 unless
another initial setting is required.
3
Quadrature
Multiplier
FC10 0x211
Set to 0 for 2 counts per line
Set to 1 for 4 counts per line
4
Direction
FC10 0x20B
With this command, the user can set the
preferred direction of the Position Counter. Set
to 0=CW or 1=CCW.
5
Speed Filter
FC10 0x216
For applications monitoring Speed via Modbus,
the user may want to select a value (0-8) to filter
speed results.
6
Save To EEPROM FC05 0x002
Send this command to save all current
parameters to internal EEPROM
7
Optical
Calibration
Perform an Optical Signal Calibration by
simultaneously moving the Encoder Film Strip
back and forth while holding down the on-
board Calibration pushbutton for at least 10
seconds. The POWER LED will blink while
calibration is performed. After 10 seconds,the
STATUS LED will blink shortly indicating that
calibration is complete and the user can then
release the button.
Sensor