When the encoder rotates slower than 1 period per millisecond, the speed can only be
updated whenever one period has elapsed. At high speeds the measurement is a combination
of number of counts and the exact time these counts occurred during the past millisecond.
Output Format: The output is in RPM x 100 (12012 -> 120.12RPM)
Range:
Lowest RPM is 0.33 and highest is 60,000
Accuracy:
1% (quartz crystal controlled)
Resolution:
0.01 RPM regardless of scale
MODBUS commands:
Voltage Mode (Register 0x200)
Register Address: 0x200
The setting of the mode determines how the speed in rpm or position count will be output as
analog voltage to the voltage output.
Default: Mode 0
SPEED Modes
Description
0
Output corresponds to actual RPM where CCW rotation is
negative voltage.
The voltage output range is 0V to +10V when the encoder
rotates CW. Overrange extends ~ 0.4V beyond 10V
The voltage output range is 0V to -10V when the encoder
rotates CCW. Overrange extends ~ 0.4V beyond 10V.
1
Output corresponds to the absolute value of the RPM,
regardless of the direction.
The output is always from 0V to +10V regardless of
direction of rotation. Over range extends ~04V beyond 10V
Address Register Description
Access
0x003
2
Encoder Speed
Read - Only