9.1 Inspection 
 

Periodically carry out the following work on the U100HL-024KA-4: 
 

Time point 

Check 

Method 

Annually during standstill 

General condition 

Visual inspection 

Annually during operation 

Noise bearing condition 

Acoustic test 

 

Vibrations 

Visual inspection 

 

9.2 Lubrication 

 
The bearings of the U100HL-024KA-4 are lubricated for life. 
 

9.3 Troubleshooting 
 
Fault 

Cause 

Action 

Flow rate and/or 
pressure is too low 
 

Speed is too low 

Check voltages 

Fan or system is leaking 

Check torques and seals on the 
connection lines  

Flow rate is too low 

Line is clogged/impeller is dirty 

Clean line/impeller 

Speed is too low 

Check voltages 

Pressure is too low 

Density is lower than indicated 

Check layout 

Power consumption is 
too high 
 

Flow rate is greater than indicated 

Check layout 

Pressure is lower than indicated 

Check layout 

Density is higher than indicated 

Check layout 

Speed is too high 

Check voltages 

Abnormal noises 
and/or vibrations 
 

Bearing damage (motor) 

Replace bearings or motor 

Impeller scrapes or is unbalanced 

Turn off fan 

Loose mounting screw 

Retighten the screw. Secure against 
loosening 

Vibrations 

Turbulence in the system 

Check air routing in the system 

 

 

Содержание U100HL-024KA-4

Страница 1: ...a can be subject to change without advanced notice Version December 6 2018 Micronel AG Original Operating Manual German OPERATING MANUAL U100HL 024KA 4 Micronel AG Z rcherstrasse 51 CH 8317 Tagelswang...

Страница 2: ...formance Fields 6 5 2 Mechanical Nominal and Threshold Values of the Blower 7 5 3 1 Dimensions 7 5 3 2 Nominal and Threshold Values of the Blower 8 5 4 1 Materials 8 5 5 1 Mounting 9 5 5 2 Sound and V...

Страница 3: ...k is the observance of all safety instructions in this manual Illustrations in this manual are provided for basic understanding and may differ from the actual design Please check to see if the manual...

Страница 4: ...e to people Danger from ejected parts Do not insert any objects through the opening in the U100HL 024KA 4 Danger from rotating and pressurized parts Before starting work on the U100HL 024KA 4 Disconne...

Страница 5: ...rate the U100HL 024KA 4 only with gases as described in Chapter 4 Intended Use with the values as specified in Chapter 5 Technical Specifications Transport assembly and disassembly may only be carried...

Страница 6: ...ecifications NOTE Overheating of the U100HL 024KA 4 during operation outside the permitted range for continuous operation Only operate the blower within the limits specified in the pQ chart and not wi...

Страница 7: ...change without advanced notice Version December 6 2018 Micronel AG 5 2 Mechanical Nominal and Threshold Values of the Blower 5 3 1 Dimensions Figure 1 Dimensions of the U100HL 024KA 4 in mm Pipe thre...

Страница 8: ...7 Thermal Ambient temperature C 20 25 45 Storage ambient temperature C 20 25 65 Measuring range integrated temperature sensor C 20 85 Motor Rotational speed RPM 22 000 43 000 Start up time 2 s 6 Envir...

Страница 9: ...re tension Do not exceed the maximum tightening torque of 8 Nm This is to avoid damaging the housing Maintain a minimum distance of 60 mm on each side for heat dissipation NOTE Risk of overheating thr...

Страница 10: ...ace maximum 75 C of the U100HL 024KA 4 High surface temperatures of over 75 C may occur on the surface of the U100HL 024KA 4 during operation No temperature sensitive parts such as electrical lines or...

Страница 11: ...e Plug type Binder miniature circular connector plug series 423 M16 DIN 8 pin male Plug recommendations Self assembled Female M16 Binder circular connector plug series 423 DIN 8 pin Pre assembled 2 m...

Страница 12: ...erator rpm speed min 1 6 1 3 3 NTC Temperature Monitoring NTC NTCG164KF104F TDK 6 2 Pipe and Hose Connections The conveying direction is labeled with IN at the intake and OUT at the outlet The gases v...

Страница 13: ...ection of at least 12 cm in length must also be connected during operation with opened suction nozzles suction from or discharge into the surrounding area to prevent fingers from coming into contact w...

Страница 14: ...e of 4 mm and 80 l min is specified for static operation Risk of overheating through the prevention of natural convection The U100HL 024KA 4 is passively cooled Observe the permissible housing tempera...

Страница 15: ...A 4 Disconnect from the power supply Secure against restarting Determine the absence of voltage Vent pipes and pump depressurization Before re commissioning Check that all fastening elements have been...

Страница 16: ...w Check voltages Fan or system is leaking Check torques and seals on the connection lines Flow rate is too low Line is clogged impeller is dirty Clean line impeller Speed is too low Check voltages Pre...

Страница 17: ...s Measures after de commissioning or before storage Attach caps to the suction and pressure discharge nozzles Ensure proper storage conditions see below Storage conditions Ambient temperature 20 C to...

Отзывы: