micronel U100HL-024KA-4 Скачать руководство пользователя страница 14

14 of 17 

All data can be subject to change without advanced notice. Version: December 6, 2018. © Micronel AG

 

CAUTION 

 

 

Risk of injury from interfering with the rotating fan impeller. 
Only operate the U100HL-024KA-4 with hose lines connected to suction or pressure discharge 
nozzles! A pipe or hose section of at least 12 cm in length must also be connected during 
operation with opened suction nozzles (suction from or discharge into the surrounding area) to 
prevent fingers from coming into contact with the impeller! Dismantle connections to the 
suction and pressure discharge nozzles only after safe disconnection from the power supply! 
Pay attention to the stopping time of the impeller. 

 

Potential risk of burn injuries from touching the hot surface of the U100HL-024KA-4! 
Do not touch during operation! A protective guard should be provided to prevent accidental 
contact. 

 

 

 

NOTE 
HINWEIS

 

 

The U100HL-024KA-4 can move during operation! 
The U100HL-024KA-4 may only be operated when fully assembled or secured against 
movement. 

 

Internal and external vibrations can loosen the fixation of the U100HL-024KA-4 
Use components that cannot come loose. Observe the permitted tightening torque? 

 

Overheating of the U100HL-024KA-4 during operation outside the permitted range for 
continuous operation! Only operate the blower within the range specified in the pQ chart and 
do not operate with closed suction or pressure discharge nozzles. A minimum measuring 
aperture of 

ᴓ4 mm and 80 l/min is specified for static operation. 

 

Risk of overheating through the prevention of natural convection 
The U100HL-024KA-4 is passively cooled. Observe the permissible housing temperature. 
Maintain a minimum distance of 60 mm on each side for heat dissipation and cooling air intake. 

 

Transport, assembly and disassembly should only be carried out by trained and responsible 
personnel! 

 

Damage to the electronics through shorting of the connections 
Any electrical connections that are not used must be sufficiently distanced from each other. 
 

 

Proceed as follows: 
 

Make sure that: 
- the suction and pressure lines are properly connected; 
- a pipe or hose of at least 12 cm in length is attached to both nozzles during operation with 
- opened suction or pressure discharge nozzles (suction from or discharge into the 
- surrounding area) to prevent fingers from coming into contact with the impeller; 
- suction and pressure lines are not blocked; 
- all fastening elements are secured against loosening; 
- the correct voltage and type of current is provided. 

Set the control voltage for the speed setpoint setting (Set Speed) initially to 0 VDC. 

Switch the specified operating voltage on. 
Now, increase the control voltage for the speed setpoint setting using Set Speed (0 to 5 VDC) 
to the desired value or the value specified in the data sheet. 
The working point of the U100HL-024KA-4 is adapted to the operating point of the plant using 
this speed control.  

Check the leak-tightness of the connections (make sure that no media leaks out). 
 

 

8

 

Operation  

 

WARNING 

 

 

Risk of injury from ejected parts!  
Do not insert any objects through the opening in the U100HL-024KA-4. 
 

Содержание U100HL-024KA-4

Страница 1: ...a can be subject to change without advanced notice Version December 6 2018 Micronel AG Original Operating Manual German OPERATING MANUAL U100HL 024KA 4 Micronel AG Z rcherstrasse 51 CH 8317 Tagelswang...

Страница 2: ...formance Fields 6 5 2 Mechanical Nominal and Threshold Values of the Blower 7 5 3 1 Dimensions 7 5 3 2 Nominal and Threshold Values of the Blower 8 5 4 1 Materials 8 5 5 1 Mounting 9 5 5 2 Sound and V...

Страница 3: ...k is the observance of all safety instructions in this manual Illustrations in this manual are provided for basic understanding and may differ from the actual design Please check to see if the manual...

Страница 4: ...e to people Danger from ejected parts Do not insert any objects through the opening in the U100HL 024KA 4 Danger from rotating and pressurized parts Before starting work on the U100HL 024KA 4 Disconne...

Страница 5: ...rate the U100HL 024KA 4 only with gases as described in Chapter 4 Intended Use with the values as specified in Chapter 5 Technical Specifications Transport assembly and disassembly may only be carried...

Страница 6: ...ecifications NOTE Overheating of the U100HL 024KA 4 during operation outside the permitted range for continuous operation Only operate the blower within the limits specified in the pQ chart and not wi...

Страница 7: ...change without advanced notice Version December 6 2018 Micronel AG 5 2 Mechanical Nominal and Threshold Values of the Blower 5 3 1 Dimensions Figure 1 Dimensions of the U100HL 024KA 4 in mm Pipe thre...

Страница 8: ...7 Thermal Ambient temperature C 20 25 45 Storage ambient temperature C 20 25 65 Measuring range integrated temperature sensor C 20 85 Motor Rotational speed RPM 22 000 43 000 Start up time 2 s 6 Envir...

Страница 9: ...re tension Do not exceed the maximum tightening torque of 8 Nm This is to avoid damaging the housing Maintain a minimum distance of 60 mm on each side for heat dissipation NOTE Risk of overheating thr...

Страница 10: ...ace maximum 75 C of the U100HL 024KA 4 High surface temperatures of over 75 C may occur on the surface of the U100HL 024KA 4 during operation No temperature sensitive parts such as electrical lines or...

Страница 11: ...e Plug type Binder miniature circular connector plug series 423 M16 DIN 8 pin male Plug recommendations Self assembled Female M16 Binder circular connector plug series 423 DIN 8 pin Pre assembled 2 m...

Страница 12: ...erator rpm speed min 1 6 1 3 3 NTC Temperature Monitoring NTC NTCG164KF104F TDK 6 2 Pipe and Hose Connections The conveying direction is labeled with IN at the intake and OUT at the outlet The gases v...

Страница 13: ...ection of at least 12 cm in length must also be connected during operation with opened suction nozzles suction from or discharge into the surrounding area to prevent fingers from coming into contact w...

Страница 14: ...e of 4 mm and 80 l min is specified for static operation Risk of overheating through the prevention of natural convection The U100HL 024KA 4 is passively cooled Observe the permissible housing tempera...

Страница 15: ...A 4 Disconnect from the power supply Secure against restarting Determine the absence of voltage Vent pipes and pump depressurization Before re commissioning Check that all fastening elements have been...

Страница 16: ...w Check voltages Fan or system is leaking Check torques and seals on the connection lines Flow rate is too low Line is clogged impeller is dirty Clean line impeller Speed is too low Check voltages Pre...

Страница 17: ...s Measures after de commissioning or before storage Attach caps to the suction and pressure discharge nozzles Ensure proper storage conditions see below Storage conditions Ambient temperature 20 C to...