72

 

Modbus Register

Alarms

Modbus 

Function 

Type

Comp.

 

#1

Comp.

 

#2

Comp.

 

#3

Comp.

 

#4

Comp.

 

#5

Comp.

 

#6

Comp.

 

#7

Comp.

 

#8

Comp.

 

#9

Comp.

 

#10

Comp.

 

#11

Comp.

 

#12

Comp.

 

#13

Comp.

 

#14

Comp.

 

#15

Comp.

 

#16

Comp.

 

#17

Comp.

 

#18

Comp.

 

#19

Comp.

 

#20

COMPRESSOR_SPEED_F

AUL

T

04:input Register

31235

31286

31337

31388

31439

31490

31541

31592

31643

31694

31745

31796

31847

31898

31949

32000

32051

32102

32153

32204

LOW_T

ANDEM_SUPERHEA

T

04:input Register

31236

31287

31338

31389

31440

31491

31542

31593

31644

31695

31746

31797

31848

31899

31950

32001

32052

32103

32154

32205

HIGH_T

ANDEM_SUPERHEA

T

04:input Register

31237

31288

31339

31390

31441

31492

31543

31594

31645

31696

31747

31798

31849

31900

31951

32002

32053

32104

32155

32206

EXCESS_SURGES

04:input Register

31238

31289

31340

31391

31442

31493

31544

31595

31646

31697

31748

31799

31850

31901

31952

32003

32054

32105

32156

32207

HIGH_SUPERHEA

T

04:input Register

31239

31290

31341

31392

31443

31494

31545

31596

31647

31698

31749

31800

31851

31902

31953

32004

32055

32106

32157

32208

Suction 

Temperature Sensor Fault

04:input Register

31240

31291

31342

31393

31444

31495

31546

31597

31648

31699

31750

31801

31852

31903

31954

32005

32056

32107

32158

32209

Discharge 

Temperature Sensor Fault

04:input Register

31241

31292

31343

31394

31445

31496

31547

31598

31649

31700

31751

31802

31853

31904

31955

32006

32057

32108

32159

32210

Suction Pressure Sensor Fault

04:input Register

31242

31293

31344

31395

31446

31497

31548

31599

31650

31701

31752

31803

31854

31905

31956

32007

32058

32109

32160

3221

1

Discharge Pressure Sensor Fault

04:input Register

31243

31294

31345

31396

31447

31498

31549

31600

31651

31702

31753

31804

31855

31906

31957

32008

32059

321

10

32161

32212

Oil Pressure Sensor Sensor Fault

04:input Register

31244

31295

31346

31397

31448

31499

31550

31601

31652

31703

31754

31805

31856

31907

31958

32009

32060

32

111

32162

32213

Oil 

Temperature Sensor Fault

04:input Register

31245

31296

31347

31398

31449

31500

31551

31602

31653

31704

31755

31806

31857

31908

31959

32010

32061

321

12

32163

32214

Motor 

Temperature Sensor Fault

04:input Register

31246

31297

31348

31399

31450

31501

31552

31603

31654

31705

31756

31807

31858

31909

31960

3201

1

32062

321

13

32164

32215

Evap Refrigerant 

Temp.  Sensor Fault

04:input Register

31247

31298

31349

31400

31451

31502

31553

31604

31655

31706

31757

31808

31859

31910

31961

32012

32063

321

14

32165

32216

Evap Refrigerant Level Sensor Fault

04:input Register

31248

31299

31350

31401

31452

31503

31554

31605

31656

31707

31758

31809

31860

3191

1

31962

32013

32064

321

15

32166

32217

Oil Seal 

Temperature Sensor Fault

04:input Register

31249

31300

31351

31402

31453

31504

31555

31606

31657

31708

31759

31810

31861

31912

31963

32014

32065

321

16

32167

32218

Pre-Oil Filter Presssure Sensor Fault

04:input Register

31250

31301

31352

31403

31454

31505

31556

31607

31658

31709

31760

3181

1

31862

31913

31964

32015

32066

321

17

32168

32219

Circuit Leaving W

ater Sensor Fault

04:input Register

31251

31302

31353

31404

31455

31506

31557

31608

31659

31710

31761

31812

31863

31914

31965

32016

32067

321

18

32169

32220

Содержание MCS-BMS-GATEWAY-N54-see

Страница 1: ...ols MCS Modbus RTU Modbus IP Ethernet BACnet IP BACnet MS TP N2 LonWorks Manual supports the following MCS BMS GATEWAY see Chapter 4 5 for installation MCS BMS GATEWAY NL see Chapter 4 5 for installat...

Страница 2: ...rovisions shall be provided to ensure that this information remains proprietary by your employees agents and other personnel that may have access to this document Copyright 2022 Date Author Descriptio...

Страница 3: ...MCS BMS GATEWAY 17 4 3 BMS Network Settings 18 4 3 1 BACnet MS TP N2 and Modbus IP to RTU 18 Figure 5 Protocol Selection Switch Tables 18 4 3 2 BACnet MS TP Setting the MAC Address for BMS Network 18...

Страница 4: ...ssor Control State Chart 67 Chapter 9 ALARMS UNIT COMPRESSOR MODBUS 68 9 1 Unit Alarms 68 9 2 Compressor Alarms 69 9 3 MODBUS Alarms 71 Chapter 10 CREATING CSV FILES USING MCS CONFIG 76 9 4 How to Cre...

Страница 5: ...eing configured by Network Management Tools such as LonMaker For binding implicit mode a Net work Management Tool is necessary to create the bindings It is possible to place a MCS BMS GATEWAY into a N...

Страница 6: ...LCD The following steps will display the BACnet IP Network address and the the TCP IP port Press the Menu key select Serv Tools and then press the Enter key Use arrow to BACnet Setting then press Ente...

Страница 7: ...et Mask and Default Gateway Press the Menu key select Serv Tools and then press the Enter key Select Ethernet Network then press Enter Set DYNAMIC IP to NO Set the IP Address Set the Subnet Mask Set D...

Страница 8: ...HNSON N2 MCS Network Protocol Support Magnum MicroMag BACnet MCS BACnet RouterR2 Modbus IP In Development MCS IP MCS Ethernet Modbus RTU MCS 485 BACnet MS IP MCS BMS Gateway Johnson N2 MCS BMS Gateway...

Страница 9: ...9 2 4 MCS MAGNUM USING RS 485 Using the RS485 the MCS Magnum can be connected to the BMS Modbus RTU or MCS 485 RS485 MCS MAGNUM MCS MAGNUM MCS MAGNUM Building Management System...

Страница 10: ...ring Multiple MCS Controllers Using the RS485 the network must be wired controller to controller Star configurations not allowed Up to 30 controllers can be wired togetherMCS MAGNUM USING ETHERNET 04...

Страница 11: ...onnect Internet access through router which allows connection via MCS Connect from anywhere 2 6 EXAMPLE NETWORK 2 6 1 Standalone MCS Magnum MCS Touch BMS Johnson N2 or BACnet MS TP Internet Access Eth...

Страница 12: ...12 2 6 2 MULTIPLE MCS MAGNUM ENCLOSURES Internet Access BMS BACnet IP or Modbus IP...

Страница 13: ...13 2 7 MULTIPLE MCS MAGNUM BMS RS485 WIRING DIAGRAM 04 14 2022 C...

Страница 14: ...evice is found or not CONNECTIVITY The light shows the level of connectivity for the device Green is full connectivity Yellow is limited connectivity Blue is limited IP connectivity And red is connect...

Страница 15: ...emplate or it can be a specific template specified by the OEM customer Setup Select File Transfer to upload files to the FieldServer gateway including configuration files firmware upgrades and more Se...

Страница 16: ...e Map Descriptors detail page Again tabs across the top of the page provide quick access to settings status info stats and error stats User Messages Allows access to error messages info messages and d...

Страница 17: ...t Device ID Set MCS MAGNUM BacNet port to 47808 in MCS CONFIG For Windows XP Customer ProtoCarrier Startup Guide Page 23 of 38 6 LONWORKS FPC C35 COMMISSIONING PROTOCARRIER ON A LONWORKS NETWORK Commi...

Страница 18: ...less of how many devices are connected to MCS BMS GATEWAY Set the BACnet MS TP MAC addresses of the MCS BMS GATEWAY to a value between 1 to 127 MAC Master Addresses this is so that the BMS Front End c...

Страница 19: ...P switches When more than one device is connected to the MCS BMS GATEWAY the subsequent BACnet Device In stance values will be sequential from the first previous device For example Given that Device I...

Страница 20: ...Off 110 On Off Off Off 300 Off On Off Off 600 On On Off Off 1200 Off Off On Off 2400 On Off On Off 4800 Off On On Off 9600 On On On Off 19200 Off Off Off On 20833 On Off Off On 28800 Off On Off On 38...

Страница 21: ...21 Chapter 5 Interfacing MCS BMS GATEWAY to Devices 5 1 MCS BMS GATEWAY Connection Ports Figure 7 MCS BMS GATEWAY...

Страница 22: ...22 5 2 Wiring diagram for connecting the MCS Magnum Wire to 12 volt power supply 04 14 2022 C BMS Communication Rev 04 14 2022...

Страница 23: ...enable successful communications between the MCS BMS GATEWAY and the MCS MAGNUM The MCS MAGNUM BACNET DEVICE ID must be set to the address specified on the MCS BMS GATEWAY s label The MCS MAGNUM BACNE...

Страница 24: ...he magnum for the change to take effect The MCS MAGNUM IP must be set to the address specified on the MCS BMS GATEWAY s label Example 192 168 18 101 Range of default settings 101 150 The MCS MAGNUM IP...

Страница 25: ...485 Device Network An RS 485 network with more than one device needs to have biasing to ensure proper communi cation The biasing only needs to be done on one device The MCS BMS GATEWAY has 510 Ohm res...

Страница 26: ...GATEWAYas show below in Figure 13 Ensure that the power supply used complies with the specifications provided in chapter 9 6 MCS BMS GATEWAY accepts either 9 30VDC or 12 24 VAC on pins 4 and 5 7 Frame...

Страница 27: ...27 0 Start up Guide MCS BMS GATEWAY N54 Chapter 6 MCS BMS GATEWAY N54 START UP GUIDE...

Страница 28: ...lation between serial Ethernet devices and networks NOTE For troubleshooting assistance refer to Section 9 or any of the troubleshooting appendices in the related driver supplements Check the MSA Safe...

Страница 29: ...quipment Setup ProtoNode Start up Guide 7 2 Equipment Setup 2 1 Mounting The ProtoNode can be mounted using the DIN rail mounting bracket on the back of the unit Figure 1 DIN Rail Bracket Din Rail Bra...

Страница 30: ...30 Equipment Setup ProtoNode Start up Guide 8 2 2 Physical Dimensions R1 Serial Port Power Port R2 Serial Port Figure 2 ProtoNode FPC N54 Dimensions...

Страница 31: ...t of the logic The bias resistor is 510 ohms which is in line with the BACnet spec It should only be enabled at one point on the bus for example on the field port were there are very weak bias resisto...

Страница 32: ...n Figure 4 Termination resistor is also used to reduce noise It pulls the two lines of an idle bus together However the resistor would override the effect of any bias resistors if connected NOTE The R...

Страница 33: ...ollowing baud rates are supported on the R1 and R2 Ports 9600 19200 38400 57600 76800 115000 NOTE Not all baud rates listed are supported by all protocols Check the specific protocol driver manual for...

Страница 34: ...be added to the power supply of the host system A safety margin of 25 is recommended Figure 6 Required Current Draw for the Gateway Apply power to the ProtoNode as shown below in Figure 7 Ensure that...

Страница 35: ...ontrol Panel click Network and Internet and then click Network and Sharing Center Click Change adapter settings on the left side of the window Right click on Local Area Connection and select Propertie...

Страница 36: ...ar as untrusted This will cause the following pop up windows to appear When the Web Server Security Unconfigured window appears read the text and choose whether to move forward with HTTPS or HTTP When...

Страница 37: ...the Username default is admin and the Password found on the label of the FieldServer NOTE There is also a QR code in the top right corner of the FieldServer label that shows the default unique passwor...

Страница 38: ...reen will appear that allows the user to select which mode the FieldServer should use NOTE Cookies are used for authentication NOTE To change the web server security mode after initial setup go to Sec...

Страница 39: ...reen will appear that allows the user to select which mode the FieldServer should use NOTE Cookies are used for authentication NOTE To change the web server security mode after initial setup go to Sec...

Страница 40: ...hrase fields will appear under the mode selection Copy and paste the Certificate and Private Key text into their respective fields If the Private Key is encrypted type in the associated Passphrase Cli...

Страница 41: ...ge to the Network Settings page follow the below instructions Find the Navigation tree across the left side of the screen Click the orange arrow next to the ProtoNode CN number and title to expand the...

Страница 42: ...or the FieldServer s internet and network connections Click the Add Rule button to add a new row and set a new Destination Network Netmask and Gateway IP Address as needed Set the Priority for each co...

Страница 43: ...ult Gateway and Domain Name Server1 2 NOTE If the FieldServer is connected to a router the IP Gateway of the FieldServer should be set to the same IP Address of the router Click Save to record and act...

Страница 44: ...relevant device registers in the Config csv file for the initial start up If not the product is shipped with a sample config csv that shows an example of the drivers ordered In the main menu of the F...

Страница 45: ...Setup then File Transfer and finally Update Browse and select the csv file open then click Submit Once download is complete a message bar will appear confirming that the configuration was updated suc...

Страница 46: ...he main menu of the FS GUI screen click Setup then File Transfer Click the config csv link under the Retrieve heading in the middle section of the screen o The file will automatically download to the...

Страница 47: ...ted driver supplements and configuration manual MSA Safety also offers a technical support on the MSA Safety website which contains a significant number of resources and documentation that may be of a...

Страница 48: ...nload the FieldServer Toolbox zip via the MSA Safety website Extract the executable file and complete the installation Connect a standard Cat 5 Ethernet cable between the user s PC and ProtoNode Doubl...

Страница 49: ...Node into the web browser or use the FieldServer Toolbox to connect to the ProtoNode Click on Diagnostics and Debugging Button then click on view and then on connections If there are any errors showin...

Страница 50: ...ate parity data bits stop bits Check Serial device address Verify wiring Verify device is connected to the same subnet as the ProtoNode No COMS on the Ethernet protocol To fix this check the following...

Страница 51: ...nostics page via one of the following methods o Open the FieldServer FS GUI page and click on Diagnostics in the Navigation panel o Open the FieldServer Toolbox software and click the diagnose icon of...

Страница 52: ...is is the power light and should always be steady green when the unit is powered RX The RX LED will flash when a message is received on the serial port on the 3 pin connector If the serial port is not...

Страница 53: ...r Next Gen Recovery 9 7 Internet Browser Software Support The following web browsers are supported Chrome Rev 57 and higher Firefox Rev 35 and higher Microsoft Edge Rev 41 and higher Safari Rev 3 and...

Страница 54: ...Off On Off Off Off On 17 Off Off Off On Off Off On Off 18 Off Off Off On Off Off On On 19 Off Off Off On Off On Off Off 20 Off Off Off On Off On Off On 21 Off Off Off On Off On On Off 22 Off Off Off O...

Страница 55: ...On On On Off 62 Off Off On On On On On On 63 Off On Off Off Off Off Off Off 64 Off On Off Off Off Off Off On 65 Off On Off Off Off Off On Off 66 Off On Off Off Off Off On On 67 Off On Off Off Off On O...

Страница 56: ...f On On Off On 109 Off On On Off On On On Off 110 Off On On Off On On On On 111 Off On On On Off Off Off Off 112 Off On On On Off Off Off On 113 Off On On On Off Off On Off 114 Off On On On Off Off On...

Страница 57: ...Off Off On On Off On On 155 On Off Off On On On Off Off 156 On Off Off On On On Off On 157 On Off Off On On On On Off 158 On Off Off On On On On On 159 On Off On Off Off Off Off Off 160 On Off On Off...

Страница 58: ...Off Off On Off Off On 201 On On Off Off On Off On Off 202 On On Off Off On Off On On 203 On On Off Off On On Off Off 204 On On Off Off On On Off On 205 On On Off Off On On On Off 206 On On Off Off On...

Страница 59: ...37 On On On Off On On On Off 238 On On On Off On On On On 239 On On On On Off Off Off Off 240 On On On On Off Off Off On 241 On On On On Off Off On Off 242 On On On On Off Off On On 243 On On On On Of...

Страница 60: ...37 Sensor 2 6 AI 38 Refer to Config 30038 AI 38 Sensor 2 7 AI 39 Refer to Config 30039 AI 39 Sensor 2 8 AI 40 Refer to Config 30040 AI 40 Magnum BACnet ID BACnet Name Modbus Register N2 Sensor 2 9 AI...

Страница 61: ...Config 00038 BO 38 Relay 3 9 BO 39 Refer to Config 00039 BO 39 Relay 3 10 BO 40 Refer to Config 00040 BO 40 Magnum BACnet ID BACnet Name Modbus N2 Relay 4 1 BO 41 Refer to Config 00041 BO 41 Relay 4...

Страница 62: ...er to Config 30214 AO 14 Analog Out 3 3 AO 15 Refer to Config 30215 AO 15 Analog Out 3 4 AO 16 Refer to Config 30216 AO 16 Analog Out 4 1 AO 17 Refer to Config 30217 AO 17 Analog Out 4 2 AO 18 Refer t...

Страница 63: ...ints are read only Magnum BACnet ID BACnet Name Modbus N2 Wanted FLA AV 3 Wanted FLA 30318 ADF 4 Steps Wanted AV 4 Steps Wanted On 30315 ADF 5 Steps On AV 5 Steps On 30316 ADF 6 Step Delay AV 6 Step D...

Страница 64: ...Sat Disch 30357 ADF 61 Compressor 8 Disch SH AV 61 C8_Disch SH 30358 ADF 62 Compressor 8 Suct SH AV 62 C8_Suct SH 30356 ADF 63 Compressor 8 Oil Pres Diff AV 70 C8_Oil Pres Diff 30382 ADF 71 Compresso...

Страница 65: ...mpressor 16 Oil Pres Diff AV 531 C16_Oil Pres Diff 30663 ADF 532 Compressor 17 FLA AV 496 C17_FLA 30580 ADF 497 Compressor 17 Sat Suction AV 499 C17_Sat Suct 30616 ADF 500 Compressor 17 Sat Disch AV 5...

Страница 66: ...etwork Demand FLA and Network Demand Steps sensors Magnum BACnet ID BACnet Name Modbus N2 Network Run Stop AV 246 Net_R S 40201 BO 247 Network Target Reset AV 247 Net_Tar Res 40202 AO 248 Network Dema...

Страница 67: ...N 34 HI TEMP UNLOAD 35 HI TEMP HOLD 36 SCROLL STEP1 37 SCROLL STEP2 38 SCROLL STEP3 39 SCROLL STEP4 12 RESERVED 13 AMBIENT OFF 14 PROCESS HEAT OFF 15 UNIT IS UNLOADED 16 UNIT IS LOADED 17 OFF TMP ICE...

Страница 68: ...input Register 31027 AV Ananlog Value 1312 HVAC HVAC HVAC BOILER_STAGE_FAULT 04 input Register 31028 AV Ananlog Value 1313 HVAC HVAC HVAC HIGH_WATER_TEMP 04 input Register 31029 AV Ananlog Value 1314...

Страница 69: ...HVAC RTU HVAC RTU LUBE_OIL_TIME HVAC RTU HVAC RTU HVAC RTU REFRIGERATION_LEAK HVAC RTU HVAC RTU HVAC RTU LOW_REFRIGERATION_TEMP HVAC RTU HVAC RTU HVAC RTU TOO_MANY_PURGES HVAC RTU HVAC RTU HVAC RTU E...

Страница 70: ...ure Sensor Fault HVAC RTU HVAC RTU HVAC RTU Oil Temperature Sensor Fault HVAC RTU HVAC RTU HVAC RTU Motor Temperature Sensor Fault HVAC RTU HVAC RTU HVAC RTU Evap Refrigerant Temperature Sensor Fault...

Страница 71: ...083 32134 32185 LOW_DISCHARGE_PSI 04 input Register 31217 31268 31319 31370 31421 31472 31523 31574 31625 31676 31727 31778 31829 31880 31931 31982 32033 32084 32135 32186 LUBE_OIL_TEMP 04 input Regis...

Страница 72: ...99 31650 31701 31752 31803 31854 31905 31956 32007 32058 32109 32160 32211 Discharge Pressure Sensor Fault 04 input Register 31243 31294 31345 31396 31447 31498 31549 31600 31651 31702 31753 31804 318...

Страница 73: ...70 1921 1972 2023 2074 2125 2176 2227 2278 2329 2380 LOW_DISCHARGE_PSI Analog Value 1412 1463 1514 1565 1616 1667 1718 1769 1820 1871 1922 1973 2024 2075 2126 2177 2228 2279 2330 2381 LUBE_OIL_TEMP An...

Страница 74: ...70 1921 1972 2023 2074 2125 2176 2227 2278 2329 2380 LOW_DISCHARGE_PSI Analog Value 1412 1463 1514 1565 1616 1667 1718 1769 1820 1871 1922 1973 2024 2075 2126 2177 2228 2279 2330 2381 LUBE_OIL_TEMP An...

Страница 75: ...1539 1590 1641 1692 1743 1794 1845 1896 1947 1998 2049 2100 2151 2202 2253 2304 2355 2406 Discharge Pressure Sensor Fault Analog Value 1438 1489 1540 1591 1642 1693 1744 1795 1846 1897 1948 1999 2050...

Страница 76: ...Click on Setup 3 Be sure to set IP Address Subnet Mask Default Gateway MCS IP Port and Bacnet Device ID then save config file DO NOT CHANGE BACNET DEVICE ID ONCE CSV FILES ARE CREATED 4 Click on BMS...

Страница 77: ...es This would be the time to name the CSV files there is a 15 character maximum not including the file extension If you do not name the file it will default to the first 15 characters of the config na...

Страница 78: ...78 Providing HVAC R Control Solutions Worldwide 5580 Enterprise Pkwy Fort Myers FL 33905 Office 239 694 0089 Fax 239 694 0031 www mcscontrols com...

Отзывы: