18
• For Windows XP and Windows 7, select: Use the following IP Address
4.3. BMS Network Settings:
• Selecting Stored Configurations, Setting the MAC Address, Device Instance, and Baud Rate
•
Selecting Configuration Files for Devices: “S” Bank DIP Switches S0 – S3
The S bank of DIP switches (S0 - S3) are used to select and load a configuration file from a group of
pretested/preloaded configuration files which are stored in the MCS-BMS-GATEWAY FPC-ED4.
NOTE: S0 - S3 DIP Switches sets the Protocol: BACnet MS/TP, OR JOHNSON N2
NOTE: When setting DIP Switches, please ensure that power to the board is OFF.
4.3.1
BACnet MS/TP, N2 and Modbus IP to RTU
The following chart describes S0 - S3 DIP Switch configuration settings for MCS-BMS-GATEWAY to sup
-
port BACnet® MS/TP, Metasys® N2 by JCI and Modbus IP to RTU.
Figure 5 Protocol Selection Switch Tables
4.3.2
BACnet MS/TP: Setting the MAC Address for BMS Network
Only 1 MAC address is set for MCS-BMS-GATEWAY regardless of how many devices are connected to MCS-
BMS-GATEWAY.
Set the BACnet MS/TP MAC addresses of the MCS-BMS-GATEWAY to a value between 1 to 127 (MAC Master
Addresses); this is so that the BMS Front End can find the MCS-BMS-GATEWAY via BACnet auto discovery.
192 . 168 . 18 . 201
255 . 255 . 255 . 0
192 . 168 . 18 . 1
*Customer ProtoCarrier Startup Guide
Page 24 of 38
x
For Windows XP and Windows 7, select: Use the following IP Address
x
Click
twice
x
Open a web browser and go to the following address: [IP Address of ProtoCarrier]/fserver.xif
o
Example: 192.168.1.24/fserver.xif
x
If the web browser prompts to save the file, save the file onto the PC. If the web browser displays
the xif file as a web page, save the file onto the local PC as fserver.xif
Figure 18: Sample of Fserver.XIF File Being Generated
S0
–
S3 DIP
Switches
S Bank DIP Switch Location
S0
S1
S2
S3
Off
On
Figure 3: S Bank DIP Switches
Fig 3
Shows setting for
BACNet MS/TP
Dip switch
S0 ‘ON’
as per the Figure 5
chart below
MCS-BMS-GATEWAY
MCS-BMS-GATEWAY Bank DIP Switches
Profile – MCS-BMS-GATEWAY RER
S0
S1
S2
S3
Bacnet MS/TP
On
Off
Off
Off
N2
Off
On
Off
Off
Modbus IP to RTU
On
On
Off
Off