62
8.3. ANALOG Output Points
Analog Output Points are read-only. Output numbering is based upon SI16-AO4 (SI-Base and SI-EXT) hardware type
board. Notable BACnet properties available: Units
Magnum
BACnet ID
BACnet Name
Modbus Register
N2
Analog Out M-1
AO:1
Refer to Config
*30201
*AO: 1
Analog Out M-2
AO:2
Refer to Config
*30202
*AO: 2
Analog Out M-3
AO:3
Refer to Config
*30203
*AO: 3
Analog Out M-4
AO:4
Refer to Config
*30204
*AO: 4
Analog Out 1-1
AO:5
Refer to Config
*30205
*AO: 5
Analog Out 1-2
AO:6
Refer to Config
*30206
*AO: 6
Analog Out 1-3
AO:7
Refer to Config
*30207
*AO: 7
Analog Out 1-4
AO:7
Refer to Config
*30208
*AO: 8
Analog Out 2-1
AO:8
Refer to Config
*30209
*AO: 9
Analog Out 2-2
AO:10
Refer to Config
*30210
*AO: 10
Analog Out 2-3
AO:11
Refer to Config
*30211
*AO: 11
Analog Out 2-4
AO:12
Refer to Config
*30212
*AO: 12
Analog Out 3-1
AO:13
Refer to Config
*30213
*AO: 13
Analog Out 3-2
AO:14
Refer to Config
*30214
*AO: 14
Analog Out 3-3
AO:15
Refer to Config
*30215
*AO: 15
Analog Out 3-4
AO:16
Refer to Config
*30216
*AO: 16
Analog Out 4-1
AO:17
Refer to Config
*30217
*AO: 17
Analog Out 4-2
AO:18
Refer to Config
*30218
*AO: 18
Analog Out 4-3
AO:19
Refer to Config
*30219
*AO: 19
Analog Out 4-4
AO:20
Refer to Config
*30220
*AO: 20
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates actual value 50.0)
8.4. Setpoints
Setpoints are read-only. Notable BACnet properties available: Units
Magnum
BACnet ID
BACnet Name
Modbus
N2
Setpoint #1
AV:0
STP# 1-<Setpoint name>
40301
ADF:1
Setpoint #21
AV:88
STP# 21-<Setpoint name>
40321
ADF:89
Setpoint #163
AV:230
STP# 163-<Setpoint
name>
40463
ADF:231
8.5. Chiller/Compressor States
State values are read-only. Notable BACnet properties available: Number of States, State-Text (Contains character text
of current state)
Magnum
BACnet ID
BACnet Name
Modbus Register
N2
Chiller Unit State
MV:0
CHILLER STATE
30306
BYT:1
Compressor #1 State
MV:1
COMPRESSOR #1 STATE
30307
BYT:2
Compressor #2 State
MV:2
COMPRESSOR #2 STATE
30308
BYT:3