Installation and User Manual
Table 3-1: Local Settings.
Display
Factory setting
Options
Language
English
French, Spanish, German, Italian
Date/time format
International
US
Date/time change
(DD-MM-YYYY/HH:MM)
MM-DD-YYYY/HH:MM adjustable
Audible alarm
Quick beeps
Slow beeps
Table 3-2: Output Features.
Display
Factory setting
Options
Comments
Output voltage
208 Volts AC (***)
200/208/220/230/240/250
Input voltage must be equal to
output voltage
Frequency converter
Disabled
Enabled
Bypass AC source disabled
Output frequency
Auto ranging
50/60 Hz
User selectable under
frequency converter mode
ECO mode
Disabled
Enabled
See Section 3.4.2.
Hot standby
Disabled
Enabled
Cascade (See Figure 3-3)
Operating mode
Industrial
IT Network
(*) See Table 3-5.
Bypass
When bypass NOK
When bypass OK (**)
(*) See Table 3-5.
Transfer
Interrupt time
10 ms
10 to 200 ms
Interrupt time calibration during
(by steps of 10 ms)
during load transfer when
Bypass AC source
is out of tolerances
Overload level
102%
50/70%
(*) : - Select "IT Network" for computer loads. Select “Industrial” for other applications or when there exists and absolute need
for service continuity (with potential 10msec. interrupt) when Bypass AC source is not within set tolerances.
See Table 3-5 for more details.
(**) UPS will switch to Bypass AC Source if it is within the set tolerances.
(***) Input voltage must be equal to output voltage.
Figure 3-3: Configuration used to provide cascade redundancy to critical loads.
Utility
AC Source
NORMAL AC
LOAD
BYPASS AC
NORMAL AC
Protective Device
Protective Device
Cascade redundancy configuration
offers better protection to critical
load, whereas the first UPS acts as
the Bypass AC Source for the
second UPS.
Operation
3 — 3
86-86000-00 B01
Содержание 11+
Страница 1: ...w w w m g e o p s c o m EX 5 7 11 RT Systems Installation and User Manual ...
Страница 2: ......
Страница 4: ... This page left blank intentionally EX 5 7 11 RT Systems iv 86 86000 00 B01 ...
Страница 14: ... This page left blank intentionally EX 5 7 11 RT Systems c x 86 86000 00 B01 ...
Страница 46: ... This page left blank intentionally EX 5 7 11 RT Systems 2 20 86 86000 00 B01 ...
Страница 62: ... This page left blank intentionally EX 5 7 11 RT Systems 4 6 86 86000 00 B01 ...
Страница 68: ......
Страница 72: ...EX 5 7 11 RT Systems G 4 86 86000 00 B01 This page left blank intentionally ...
Страница 74: ......
Страница 75: ......