Installation and User Manual

3.4

Operating Modes

3.4.1

Normal (Double Conversion) Mode

Figure 3-4:  Normal (Double Conversion) Mode.

OFF

ON

OFF

ON

15

15

16

LOAD LEVEL
4kW / 5 kVA

REMAINING TIME

10 minutes

21

22

Operation

3 — 7

86-86000-00 B01

This is the standard operating mode, set by the
factory. 

Two possible cases.

1.

If Normal AC source available:

LED is ON.

The load is protected by the UPS.

Scroll down 

or scroll up 

function buttons

allow you to read the UPS measurements (Normal
AC source voltage, Bypass AC source voltage,
operating mode, battery capacity and UPS Serial
Number).

2.

If Normal AC source not available:

CAUTION: Do 

not operate the Manual 

Bypass switch when the UPS is 
in Normal mode.

LED flashes.

LED is ON.

The audible alarm sounds intermittently.

The load is now powered by the UPS battery.

This display shows remaining back-up time.

16

15

22

21

15

Содержание 11+

Страница 1: ...w w w m g e o p s c o m EX 5 7 11 RT Systems Installation and User Manual ...

Страница 2: ......

Страница 3: ...ECN 003984 07 2004 A02 ECN 004086 11 2004 A03 ECN 004284 05 2005 B00 ECN 004379 03 2006 B01 ECN 005020 10 2006 Copyright 2007 MGE Office Protection Systems All rights reserved Printed in U S A MGE Office Protection Systems 13 Whatney Suite 101 Irvine CA 92618 949 268 2800 For Technical Support Customer Care Center or Customer FAQ please visit our website www mgeops com or call 800 279 7776 ...

Страница 4: ... This page left blank intentionally EX 5 7 11 RT Systems iv 86 86000 00 B01 ...

Страница 5: ...Configuration 1 4 1 2 2 Rack Configuration 1 5 1 3 Rear Panel Components 1 6 1 3 1 Power Module EX 5 7 11 RT 1 6 1 3 2 Battery Module EXB 5 7 11RT With Remote Emergency Power Off REPO Function 1 6 1 3 3 EX RT Transformer Module 1 7 1 4 Power Module Display and Control Panel 1 7 1 5 Optional Accessories 1 8 1 5 1 Power Module Rail Kit 1 8 1 5 2 Battery Transformer CLA Module Rail Kit 1 8 1 5 3 Mult...

Страница 6: ...EPO Communication Port 2 12 2 7 System Connections 2 13 2 7 1 Connections with Common Normal and Bypass AC Sources Single Mains 2 13 2 7 2 Connecting EX RT Transformer Module 2 15 2 7 3 Connections with Separate Normal and Bypass AC Sources 2 Mains 2 16 2 7 4 System Connections as Frequency Converter without Bypass AC Source 2 17 2 8 Connection of Battery Module EXB 2 18 2 9 Connection of Optional...

Страница 7: ...lectrical Specifications 5 1 5 1 System Input Output Power Ratings 5 1 5 2 System Overload Characteristics 5 1 5 3 System Back up Characteristics 5 2 5 4 System Short Circuit Protection 5 2 5 5 Accessories Electrical Characteristics 5 2 5 6 Heat Rejection 5 4 5 7 Environmental Characteristics 5 4 Customer Care Center Single Phase Products Technical Support and Product Services Who to Contact Sched...

Страница 8: ...of the Logo and Control Panel Power Module Shown 2 6 2 5 Accessing Battery Pack 2 6 2 6 Rack Mounting of the Power Module Onto the Rails 2 7 2 7 Input Output Box Bracket System 2 8 2 8 RS232 Communication Cable Connection 2 9 2 9 Relay Pin Connections for Communication Port 2 10 2 10 Communication Card Slot with Network Management Card Installed 2 10 2 10a Activation of Remote Emergency Power Off ...

Страница 9: ... System Ratings 1 3 1 4 Transformer Module Characteristics Ratings 1 3 1 5 Battery Module Ratings 1 4 1 6 System Dimensions and Weights 1 5 1 7 Battery Back up Time Chart 1 12 3 1 Local Settings 3 3 3 2 Output Features 3 3 3 3 ON OFF Features 3 4 3 4 Battery Features 3 4 3 5 System Operation in I T and Industrial Modes 3 5 4 1 Troubleshooting Not Requiring MGE Office Protection Systems After Sales...

Страница 10: ...quipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Certification Standards IEEE 587 ...

Страница 11: ...ear liquids or in an excessively damp environment Never let a foreign body penetrate inside the system Never block the ventilation grates of the system Never expose the system to direct sunlight or source of heat If the system must be stored prior to installation storage must be in a dry place The admissible storage temperature range is 25ºC to 55ºC Special Precautions All handling operations will...

Страница 12: ...MBER ________________________________________________ CLA Module SERIAL NUMBER ______________________________________________________ ADDITIONAL MODULES SERIAL NUMBERS ____________________________ ______________________________ ____________________________ ______________________________ ____________________________ ______________________________ ____________________________ _______________________...

Страница 13: ...t information on MGE Office Protection Systems products that will enhance the performance of the EX 5 7 11 RT Please contact your MGE Office Protection Systems representative for detailed information on these options 2 Setup and Installation Setup and Installation guides the user through tools and equipment required for connecting the EX 5 7 11 RT and battery installation or replacement Included a...

Страница 14: ... This page left blank intentionally EX 5 7 11 RT Systems c x 86 86000 00 B01 ...

Страница 15: ...nce of the EX 5 7 11 RT Please contact your MGE Office Protection Systems representative for detailed information on these options Table 1 1 EX RT Model Descriptions and Contents Also All units include rail kits for rack mounting and stabilizing feet for tower configuration NOTE The Power Module is factory configured for single Mains input at 208VAC 60Hz Other input output voltage settings are ava...

Страница 16: ... 86008 Empty Battery Chassis EXB RT W EPO 86009 I O Box 5 7kVA UL US 86010 I O Box 11kVA UL US 86012 I O Box Bracket System 86013 Rear Bracket Supports 86207 Battery Module EXB 5 7RT 86209 Battery Module EXB 11RT 86211 EX RT Transformer Module 11kVA 86213 CLA Charger Module 86215 5kVA Power Module EX 5RT 86216 7kVA Power Module EX 7RT 86217 11kVA Power Module EX 11RT 86311 EX RT Transformer Module...

Страница 17: ...r 200 208VAC Isolated 120 208 240VAC are available with EX RT Transformer Module Introduction 1 3 86 86000 00 B01 UPS Characteristics MAIN 1 Normal AC Source default Power Rating Input Voltage VAC Input Current A Input Breaker A Output Voltage VAC Output Current A Inrush Current Min Max Online Bypass 5 kVA 208 18 32 21 6 19 40 208 19 25 200A 1ms 7 kVA 25 45 30 3 26 65 50 23 5 11 kVA 38 64 44 42 70...

Страница 18: ...Configuration Figure 1 1 Tower Configuration with Power Module Battery Module and optional Transformer Module OFF ON BATTERY MODULE POWER MODULE EX 11 RT EXB RT EX RT Transformer TRANSFORMER MODULE EX 5 7 11 RT Systems Introduction 1 4 86 86000 00 B01 Part Number 86207 86209 Battery Type 12VDC 7Ah 12VDC 9Ah Battery Output Voltage 240VDC 240VDC ...

Страница 19: ... 16 x 17 49 x 25 131 x 444 x 635mm 142 lbs 64 5 kg EXB 11RT Battery Module 3U 5 16 x 17 49 x 25 131 x 444 x 635mm 151 lbs 68 5 kg EX RT Transformer Module 11kVA 3U 5 16 x 17 49 x 25 131 x 444 x 635mm 173 lbs 78 5 kg CLA Charger Module 3U 5 16 x 17 5 x 25 26 5 lbs 12 kg EX RT Transformer Module 7kVA 3U 5 16 x 17 49 x 25 131 x 444 x 635mm 173 lbs 78 5 kg POWER MODULE EX 5 7 11 RT BATTERY MODULE EXB ...

Страница 20: ...attery power connectors to the UPS or to other Battery Modules Battery Circuit Breaker with shunt trip 14 13 12 1 2 4 5 3 6 7 9 10 11 8 Slot for optional communication cards Dry relay contacts Communication Port Remote Emergency Power Off REPO function See Section 2 6 Connector for automatic detection of Battery Module s RS232 communication port Battery CLA Module power connector Manual Bypass swi...

Страница 21: ...ker Load 1 1 NEMA L6 30R 208Vac Load 1 Circuit Breaker Transformer Protect Breaker Load 4 4 NEMA 5 15 20R 120Vac Load 4 Circuit Breaker Transformer I O Box AC Input AC Output Load 3 1 NEMA L6 30R 208Vac Introduction 1 7 86 86000 00 B01 OFF ON E X 1 1 R T 15 16 19 17 18 20 21 22 23 Load protected On line Operation LED Operation on battery LED Operation on bypass LED Fault LED LCD display UPS OFF bu...

Страница 22: ... installation of Power Module Figure 1 7 Power Module Rail Kit Front mounting brackets Rear support brackets part number 86013 This can be ordered separately Telescopic rails 25 16 to 39 61 length 639 mm to 1005 mm Input Output Box bracket system part number 86012 1 5 2 Battery Transformer CLA Module Rail Kit Part number 86002 This kit is for rack mounting of the Battery Transformer CLA Module in ...

Страница 23: ...ppendix for additional Back up time information 1 5 4 Battery Extension Cable Kit 6 ft 1 8 m Part number 86006 This extended battery cable kit will be used instead of the standard battery cable when Battery Modules EXBs are distant from each other located in two different enclosures for instance The battery extension cable kit includes a 6 ft long straight connector battery power cable and a 6 ft ...

Страница 24: ...heels with brakes leveling feet seismic floor mount panels plates to lock modules and hardware included Modules not included Figure 1 10 Typical Battery Integration kit with casters setup 1 5 6 Input Output Box I O Box 5 7kVA Part number 86009 I O Box 11kVA Part number 86010 OFF O TRANSFORMER MODULE optional POWER MODULE BATTERY MODULES up to 6 Modules Not Included In Kit Introduction ...

Страница 25: ... 120 208 240VAC outputs Figure 1 11 Typical Transformer Module Contents and Connections Introduction Warranty and Product Registration EX RT Transformer Quick Start Manual EX RT Transformer Module Box Contents Tower Stand Extenders Stabilizer Bracket 4 screws included 41 Transformer Rail Kit Transformer Cable w w w m g e o p s c o m EX 5 7 11RT Systems Quick Start ...

Страница 26: ...tery capacity must be set within the UPS 5 Ah increment See UPS Personalization Section 3 2 Battery Back up Time Recommended Batteries EX 5RT EX 7RT EX 11RT 2 hours 50 Ah 65 Ah 100 Ah 4 hours 100 Ah 130 Ah 200 Ah 8 hours 200 Ah 260 Ah 400 Ah EX 5 7 11RT 50A cable w battery not included Optional High Power Battery Cabinet not included 15A Utility AC Source cable not included see section 2 9 for cab...

Страница 27: ...on as close to the final installation location as possible See Figures 2 1 on Page 2 2 All Modules are shipped in separate boxes Prior to any installation the following items should be observed upon receipt of the EX 5 7 11 RT 1 Inspect shipment for any damage prior to receipt Damage claims should be filed directly with the courier Replacements for damaged components should be ordered through MGE ...

Страница 28: ... EX 5 7 11 RT Power Module E X 1 1 R T 31 32 33 35 36 see 1 5 1 30 34 OFF O I O Box 5 7kVA Part number 86009 I O Box 11kVA Part number 86010 Installation Contents of EX 5 7 11 RT Power Module PN 86215 86216 86217 EX 5 7 11 RT Power Module Two sets of tower stands RS232 communication cable Product documentation Input Output Box PN 86009 for EX 5 7RT 86010 for EX 11RT Solution Pac 2 CD Power Module ...

Страница 29: ...dule Part number 86207 EXB 11RT Battery Module Part number 86209 38 29 Installation 2 3 86 86000 00 B01 Contents of EXB 5 7 11RT Battery Module PN 86207 86209 Stabilizer Bracket and hardware EXB 5 7 11RT Tower stand expanders Battery Power cable Battery EX RT Transformer CLA Module rail kit PN 86002 Battery detection cable EXB Documentation Bezel hex drive 44 43 42 41 40 39 38 29 ...

Страница 30: ...er Module E X B R T E X 1 1 R T OFF ON Tower Configuration with Optional Transformer Module Tower Configuration with Standard System Use the same procedure for tower mounting multiple battery modules if applicable E X B R T E X 1 1 R T OFF ON Transformer Module Battery Module Power Module Battery Module 1 1 2 2 4 4 4 4 3 3 5 1 1 2 2 4 4 4 4 3 3 5 Power Module EX 5 7 11 RT Systems Installation 2 4 ...

Страница 31: ...or optimum stability To prepare the front panel logo and LCD display for rack orientation of all modules including Transformer or CLA Module if equipped Proceed as follows 1 Unclip logo plate and pull the LCD display from front panel 2 Rotate them 90 degree counter clockwise as shown 3 Place items back onto the panel Figure 2 4 Typical Orientation of the Logo and Control Panel Power Module Shown E...

Страница 32: ...Unscrew the brackets securing the battery connectors 3 Disconnect Battery plugs 4 Unscrew the brackets securing the battery pack Remove battery bracket pack covers 5 Pull the left and right battery packs out and set aside for reinstalling after the Battery Module cabinet has been rack mounted 6 Mount Battery Module cabinet on rack 7 Re install the battery pack in reverse order Figure 2 5 Accessing...

Страница 33: ... 2 Attach rear support brackets to module These brackets prevent the module from sliding out of the rack 3 Attach rails together secure with wing nuts and finger tighten both sides 4 Attach both rails to rear and front of rack with supplied flathead screws as shown 5 Use caution when sliding unit into rack Temporarily secure unit to rack with thumb screws on front mounting brackets 6 Secure rear s...

Страница 34: ...e replacement module into the connectors of the I O Box 1 2 Secure small brackets to larger bracket from the underside 3 Secure small attached brackets to the I O Box with four screws 4 Secure large bracket to rails at the rear of module with four nuts Figure 2 7 Input Output Box Bracket System OFF 1 2 4 4 3 Install input output cables per section 2 7 prior to this step 27 27 EX 5 7 11 RT Systems ...

Страница 35: ... MGE Office Protection Systems Transverse communication card See Section 2 5 3 or check www mgeops com for the complete list of compatible cards 2 5 1 Connecting the RS232 Communication Port 1 Connect the RS232 communications cable to the serial port on the computer 2 Connect the other end of the communications cable to the RS232 communications port on the EX 5 7 11 RT The EX 5 7 11 RT systems can...

Страница 36: ...lot cover secured by two screws 2 Insert the Transverse card into the slot 3 Secure the card with both screws 4 Refer to user manual of the Network Management Card for set up Figure 2 10 Communication Card Slot with Network Management Card installed 1 1 2 EX 5 7 11 RT Systems Installation 2 10 86 86000 00 B01 1 2 3 4 5 6 7 8 9 NO NO NO NO common NC When the status is active the contact between the...

Страница 37: ...protocol Used with the UPS Control LCD display USB Card PN 66067 For direct communications via USB with the customer s server and automatic UPS recognition by the power management software of Windows 2000 XP or 2003 Server or Macintosh OS 9 and 10 Dual port AS 400 Relay PN 66068 CAN NOT BE USED WITH THIS UPS Status Card 6 Alarm Relay Card PN 66069 Provides status in the form of 6 Alarm relays 250V...

Страница 38: ...ngle device To simplify the last two steps the Power Module provides an RJ 11 six contact connector on the back panel called Remote Emergency Power Off REPO port Upon applying a voltage source 5 27VDC 10mA max to pins 2 4 of this port the Power Module will send a signal to trip off the shunt trip on each circuit breaker of all Battery Modules via the battery detection cable simultaneously Refer to...

Страница 39: ...er Module is factory configured for single input whereas both Normal AC and Bypass AC sources are identical by means of jumper between L1 and L3 Jumper must be removed for separate Normal AC and Bypass AC sources 2 Mains or with Frequency Converter application Keep Manual Bypass Switch at Normal position 7 L6 L5 L2 L1 L1 L4 L3 Jumper see note Output 200 208 220 230 240Vac Normal AC source 200 208 ...

Страница 40: ...Output Cables Installation Card Settings RS232 Download 66074 UPS data Reset 100 10 1 2 ON ETHERNET IP MAC 00E0D8FF855E 1 2 OFF O OFF O Output to Load or Transformer Module if applicable AC INPUT UPSTREAM CIRCUIT BREAKER NOT SUPPLIED To Load or Transformer Module if applicable Normal AC Simplified Connection Diagram Normal AC Input Output L6 L5 L2 L1 L1 L4 L3 Jumper Output 200 208 220 230 240Vac N...

Страница 41: ...x L3 L2 L1 Lb Ld N Lc La 208VAC 240VAC AC Input 120VAC 208VAC AC Output 120VAC 240VAC Terminal Block capability AWG 4 solid or stranded wire BATTERY MODULE EXB 5 7 11 RT AC INPUT UPSTREAM CIRCUIT BREAKER NOT SUPPLIED Transformer Module Bypass AC Normal AC Simplified Connection Diagram To Load WARNING To avoid overloading 120VAC output windings distribute loads evenly between Load 2 and Load 4 on r...

Страница 42: ...d Settings RS232 Download 66074 UPS data Reset 100 10 1 2 ON ETHERNET IP MAC 00E0D 8FF855E 1 3 Output Bypass Normal OFF O OFF O OFF O To Load or Transformer Module if applicable 2 L3 L1 MAINS 2 BYPASS AC NORMAL AC MAINS 1 LOAD With separate Normal and Bypass AC inputs supplied by separate sources Isolation Transformer PN 86211 EX 5 7 11 RT Systems Installation 2 16 86 86000 00 B01 Proceed as follo...

Страница 43: ... source 200 208 220 230 240Vac OUTPUT To Load 208VAC INPUT From Utility 208 VAC Power Module I O Box 1 OFF O Installation 2 17 86 86000 00 B01 CAUTION Always connect the earth ground wire first 1 Remove the cover plate under the I O Box Remove the jumper connecting L3 and L1 CAUTION Removing the jumper will disable the Bypass AC source Do not connect anything to the Bypass AC terminal block 2 Refe...

Страница 44: ...tery power cable to the connectors and of the Power and Battery Modules 3 Connect the battery detection cable between connectors and of the Power and Battery Modules Figure 2 16 Rear view of Battery Module cable connections 4 42 40 13 14 6 12 12 4 42 13 6 40 14 EX 5 7 11 RT Systems Installation 2 18 86 86000 00 B01 ...

Страница 45: ...ut cable cross section not provided maximum 16 AWG solid or stranded wires Field wiring connections to terminal block shall be made using the following No 14 AWG 60ºC copper wires for AC inputs No 10 AWG 75º C copper wires for DC inputs Figure 2 17 Rear view of CLA Module cable battery and AC input connections DC Input to High Power Battery Cabinet Separate 15A Utility AC Source 208 or 240 Use 15A...

Страница 46: ... This page left blank intentionally EX 5 7 11 RT Systems 2 20 86 86000 00 B01 ...

Страница 47: ...nt for normal startup of EX 5 7 11 RT systems If the system is configured for cold start the AC and DC sources are required for initial startup only 1 Check that the manual bypass switch is on Normal position 2 Set the Normal AC source circuit breaker to the ON position 3 Set the battery circuit breaker to the ON position The load is powered via the Bypass AC source but not protected by the UPS Ba...

Страница 48: ...luded in the MGE Office Protection Systems Solution Pac 2 CD ROM 3 2 1 Accessing personalization with front panel buttons Press scroll down and scroll up function buttons together for more than 3 seconds Press the function button placed under the ENT word to enter the set up mode and follow the LCD messages using the buttons now defined as select keys See Tables 3 1 3 2 3 3 and 3 4 for settings Fi...

Страница 49: ...n bypass NOK When bypass OK See Table 3 5 Transfer Interrupt time 10 ms 10 to 200 ms Interrupt time calibration during by steps of 10 ms during load transfer when Bypass AC source is out of tolerances Overload level 102 50 70 Select IT Network for computer loads Select Industrial for other applications or when there exists and absolute need for service continuity with potential 10msec interrupt wh...

Страница 50: ...utput load level 10 Remote Command Enabled Disabled Enables shutdown or restart orders from software Table 3 4 Battery Features Display Factory setting Options Comments Battery test Every week No test daily monthly Pre Alarm 20 0 to 100 Low battery signal 1 increment Runtime choice UPS reads and type From 50 to 400 Ah Requires CLA Module if using of Battery Modules options See Section 1 5 8 connec...

Страница 51: ...ransferred to Bypass AC source AC source with 10 milli seconds output break The UPS does not return to normal mode if overload is removed Output short circuit and Bypass The load remains powered by the UPS Load is transferred to Bypass AC source in tolerance The UPS shuts down after 3 minutes AC source The UPS does not if the short circuit remains return to normal mode if the short circuit is remo...

Страница 52: ...startup exe Then go to Advanced settings and UPS settings Please note that the Linux Unix MacOS versions of Personal Solution Pac do not include this feature 3 3 2 Final Startup sequence Press the ON button more than 3 seconds After UPS internal test sequence the green LED goes on CAUTION During the startup if the Bypass AC source is out of tolerance there will be a 10msec output interrupt 15 EX 5...

Страница 53: ... source available LED is ON The load is protected by the UPS Scroll down or scroll up function buttons allow you to read the UPS measurements Normal AC source voltage Bypass AC source voltage operating mode battery capacity and UPS Serial Number 2 If Normal AC source not available CAUTION Do not operate the Manual Bypass switch when the UPS is in Normal mode LED flashes LED is ON The audible alarm...

Страница 54: ...es 1 If Normal AC source Mains 1 and Bypass AC Source Mains 2 are available and LED are ON The load is supplied with AC power but not protected in ECO mode 2 If Normal AC source Mains 1 is available but Bypass AC source Mains 2 is not available LED is ON The audio alarm sounds intermittently The load is automatically supplied in Normal mode via the Normal AC input 3 Both Normal and Bypass AC sourc...

Страница 55: ... The audio alarm beeps every 10 seconds This indicate the load is supplied by the battery The LCD display indicates the battery remaining back up time Second Case Low battery warning LED is ON LED flashes The audio alarm beeps every 3 seconds Low battery warning on LCD display There is very little remaining battery back up time Close all applications because UPS automatic shutdown is pending Third...

Страница 56: ... UPS It is powered via the Bypass AC source If the UPS is set in frequency converter mode the load will not be powered If the Bypass AC source is out of tolerance the UPS will generate a calibrated 10msec output interrupt 2 Set the battery circuit breaker s to the OFF position 3 Set the Normal AC source circuit breaker to the OFF position LED is now OFF CAUTION Performing this step will disconnect...

Страница 57: ...s on Load supplied by Bypass AC source Push the ON button for more than the LCD display shows 3 seconds LOAD LEVEL XX kW XX KVA LED is on and Bypass UPS overload Check if any device is shorted or AC source is present failed the LCD display shows THERMAL OVERLOAD 1XX LED is on the LCD Short circuit conditions on output Check if any load has shorted or display shows devices failed CURRENT OVERLOAD L...

Страница 58: ...ery replacement audible alarm is on procedure in Section 4 4 the LCD display shows BATTERY FAULT LED is on Static switch failure Please visit www mgeops com the LCD display shows or call 800 279 7776 for technical SHUTDOWN support STATIC SW FAILED Audible alarm is on Batteries may have exceeded Follow the battery replacement the LCD display shows their rated life period Battery procedure in Sectio...

Страница 59: ...rn the manual bypass switch to the BYPASS position 3 Switch the battery circuit breaker s to the OFF position CAUTION Do not switch the Normal AC source circuit breaker to the OFF position Doing so will disconnect power to the load 4 Loosen three screws to remove the Input Output box 5 Disconnect the battery cables and from the Power Module The Power Module can be replaced The connected equipment ...

Страница 60: ...le 3 Switch the battery circuit breaker s to the ON position 4 Check if Normal AC source circuit breaker is on the ON position 5 Check that the LED is ON 6 Turn the manual bypass switch from the BYPASS to the NORMAL position 7 Follow initial start up sequence See Section 3 1 in order to personalize the UPS 8 Push the ON button for more than 3 seconds The green LED is ON and the connected equipment...

Страница 61: ... battery circuit breaker s to the OFF position 2 Disconnect the cables and from the Power Module The Battery Module can be replaced The connected equipment is powered by the UPS but not protected It is also possible to replace the battery packs instead of Battery Module CAUTION Always replace both battery packs with new ones To remove battery pack 1 First switch the battery circuit breaker s to th...

Страница 62: ... This page left blank intentionally EX 5 7 11 RT Systems 4 6 86 86000 00 B01 ...

Страница 63: ...8 220 230 240 250VAC 50 60 Hz autoranging 120 208 240Vac or frequency converter are possible with transformer module depends on output voltage setting can be modified by software set to 4 by default 1 2 4 8 are possible values can be modified by software 5 2 System Overload Characteristics Figure 5 1 Power Supplied as a Function of Input Voltage Left and Permissible UPS Overloads as a Function of ...

Страница 64: ...VA US Model Only with 7Ah Battery Modules 10 20 30 40 50 60 70 80 90 100 Standard 170 91 49 33 25 21 16 13 11 9 Std 1 EXB 358 170 110 84 60 46 39 31 27 25 Std 2 EXB 540 260 170 120 100 75 64 57 52 45 Std 3 EXB 740 355 240 170 122 110 95 84 68 60 Std 4 EXB 892 505 290 235 170 135 119 105 92 84 Std 5 EXB 1220 540 355 260 225 170 140 120 110 100 5 4 System Short Circuit Protection Short circuit curre...

Страница 65: ...0 208 250 Volts 7kVA 4 9kWatts 87 87 89 88 89 89 88 88 Output 220 230 240 Volts Output 200 208 250 Volts 11kVA 8kWatts 89 88 90 90 89 89 87 88 Output 220 230 240 Volts Output 200 208 250 Volts kVA kW 25 50 75 100 Output load percentage 5kVA 4kWatts 90 89 91 91 91 91 92 91 Output 220 230 240 Volts Output 200 208 250 Volts 7kVA 4 9kWatts 90 89 91 91 91 91 92 91 Output 220 230 240 Volts Output 200 20...

Страница 66: ...time is adversely affected by high and low temperatures It is significantly reduced at temper atures under 10 C Above 25 C battery service life is cut in half every 10 C Above 40 C battery manufacturers no longer guarantee operation due to the risk of thermal runaway Air enters through the front air vent grills and exits through the back Always keep air vent grills unobstructed kVA kW 25 50 75 100...

Страница 67: ...sit our website www mgeops com Scheduling Field Service Engineer Support Scheduling of the MGE Office Protection Systems Field Service Engineers typically should be done 7 to 10 days before they are required on site If the startup of the UPS is critical to maintaining your schedule please contact MGE Office Protection Systems to insure a safe installation and start up that will maintain the MGE Of...

Страница 68: ......

Страница 69: ...rd Institute AWG American Wire Gauge Breaker Electrical circuit interrupter BTU or Btu British thermal unit Defined as the amount of heat required to raise the tempera ture of one pound of water by 1 F Carrier The company or individual responsible for delivering goods from one location to another C Common CB Circuit breaker cm Centimeter Conduit A flexible or rigid tube enclosing electrical conduc...

Страница 70: ...f Electrical and Electronic Engineers IGBT Insulated gate bipolar transistors Input branch circuit The input circuit from the building power panel to the equipment Inverter An electrical circuit that generates an AC voltage source from a DC voltage source Inverter mode See on line mode I O Input Output I T or IT Information Technology kVA KiloVolt Ampere is equal to 1000 Volt Ampere L Line LCD Liq...

Страница 71: ...ctifier Shipping damage Any damage done to an article while it is in transit SPDT Single Pole Double Throw Static Transfer An solid state switching mechanism electronically controlled to pass AC power directly from the utility to an output load Technician Refers to an electronic technician qualified to maintain and repair electronic equipment Not necessarily qualified to install electrical wiring ...

Страница 72: ...EX 5 7 11 RT Systems G 4 86 86000 00 B01 This page left blank intentionally ...

Страница 73: ...stance NAME _____________________________________________________________________________________ COMPANY ___________________________________________________________________________________ STREET ADDRESS ____________________________________________________________________________ CITY ________________________________________ STATE __________________ ZIP ___________________ I would like to order__...

Страница 74: ......

Страница 75: ......

Страница 76: ...te 101 Irvine California 92618 www mgeops com w w w m g e o p s c o m Contact MGE Office Protection Systems United States MGE Office Protection Systems 13 Whatney Suite 101 Irvine CA 92618 949 268 2800 www mgeops com ...

Отзывы: