3.2.3 Installation methods

 

There are three different types of installation: 

(A)   Embedding the film between inorganic layers with dispersion fillers or dispersion plaster systems such as  
        Schönox FS, Brillux PM1881 or Maxit K+B.
(B)   Bonding of the film between inorganic and organic layers with all types of flexible adhesives as  
        described under (A).
(C)   Floating installation on floor and ceiling as top layer under the top layer. 

In cases (A) - (B), the foil is to be worked in the thin-bed method in a moist adhesive bed without air bubbles. To 
do this, apply the adhesive bed 1-2 mm thick to the substrate, then carefully press the foil into the still damp bed 
with a plastic trowel. The copper contact strips always face the wall. After the heating foil has been glued in, a 
complete covering layer (filler, plaster system, tile, etc.) of at least 2 mm must be applied. If several heating foils 
are to be laid next to each other, it must be ensured that a minimum distance of 20 mm is maintained between the 
individual foils.

It must be ensured that the foil is not laid over expansion joints.

If several heating strips are to be laid floating next to each other according to installation method (C), it must be 
ensured that the heating strips are secured against slipping with adhesive tape and that a minimum distance of 
20 mm is maintained between the individual foils. The heating tracks and copper contact strips must not touch 
or cross each other when laid in multiple tracks. The ends/joints of the foil must always be taped with insulating 
adhesive tape (even with uncut strips). For the installation of the controller and sensor, see section 

Electrical 

connection.

  

 
 

3.2.4. Installation under tiles

Before the tiles are bonded, the heating foil must be completely laid with flexible tile adhesive using a thin-bed 
method and a 1-2 mm thick top layer. The surface must be dried according to the instructions of the adhesive 
manufacturer. When laying several strips, ensure that the surface is level.

09

Notice

Further information can be found in the QR code on the back

Sealings in wet areas are applied above the heating foil.

Für eine schwimmende Verlegung ohne Verklebung, z.B. zwischen 
Estrich und Laminat, empfehlen wir, eine ca. 2 mm ausgleichende Kork-
schicht oder Glasfaservlies unter der Heizfolie zu verlegen.

3.2.2  Wärmedämmung

Eine Wärmedämmung im Boden und Wandbereich ist zu empfehlen, 
um die Wärmeabgabe ins Mauerwerk und den Boden zu reduzieren. 
Um den Wärmefluss nach unten zu begrenzen, ist folgendes Mindest-
verhältnis der Wärmedurchgangskoeffizienten des Fußbodenaufbaues 
oberhalb der Dämmschicht und des Wärmedurchgangskoeffizienten 
für alle Schichten unterhalb der Lastverteilschicht einzuhalten (nach EN 
50559:2013-12):

•  Zwischengeschossdecke, über beheizten Räumen:  
 

U max: 1,25 W/(m

2

*K)

•  Zwischengeschossdecken über teilweise beheizten Räumen:  
 

U max: 0,75 W/(m

2

*K)

•  Kellerdecken, Wände und Decken gegen unbeheizte Räume sowie  
 

Decken und Wände, die an das Erdreich grenzen: 

 

U max: 0,35 W/(m

2

*K)

Die Dämmschichten unter der Fußbodenkonstruktion sind nach fol-
gender Tabelle zu wählen. Mindest-Wärmedurchgangskoeffizienten 
sind einzuhalten. Es dürfen nur genormte, für Fußbodenheizung geeig-
nete Dämmstoffe verwendet werden. Die Zusammendrückbarkeit der 
Dämmschicht darf nicht mehr als 5 mm betragen. Bei mehreren Lagen 
ist die Zusammendrückbarkeit der einzelnen Lagen zu addieren.

U

max

 

W/(m

2

*L)

R

min

m

2

*K/W

Zwischengeschossdecken über beheizten 

Räumen

1,25

0,75

Zwischengeschossdecken über teilweise 

beheizten Räumen

0,75

1,25

Heizflächen zwischen Außenluft oder Erdreich

0,35

2,86

Kellerdecken, Wände oder Decken gegen 

unbeheizte Räume

0,35

2,86

Mindest-Wärmedurchgangskoeffizient und Mindest-Wärmeleitwider- 
stand der Bauteile.

If the heating film is being installed without adhesive, e.g. between screed 
and laminate, we recommend the inclusion of roughly 2 mm of a cork layer 
or fibreglass matting underneath the heating film to compensate for this.

3.2.2  Heat insulation

Heat insulation in the floor and walls is recommended, in order to re-
duce the loss of heat to the walls and floor. To limit heat radiation down-
wards, the following minimum ratio of the heat transfer coefficient of 
the floor structure above the insulation layer and the heat transfer coef-
ficient of all layers underneath the load distribution layer must be obser-
ved (according to EN 50559:2013-12):

•  Intermediate ceilings, above heated rooms: 
 

U max: 1.25 W/(m

2

*K)

•  Intermediate ceilings, above rooms that are heated to some extent:
 

U max: 0.75 W/(m

2

*K)

•  Cellar ceilings, walls and ceilings next to unheated rooms as well as  
 

ceilings and walls adjacent to earth:

 

U max: 0.35 W/(m

2

*K)

The insulation layers below the floor structure must be chosen in ac-
cordance with the following table. Minimum heat transfer coefficients 
must be observed. Standardised insulation materials that are suitable 
for underfloor heating must be used. The insulation layer must not be 
compressible by more than 5 mm. If there are several layers, the com-
pressibility of the individual layers is added together.

U

max

 

W/(m

2

*L)

R

min

m

2

*K/W

Intermediate ceilings above heated rooms

1.25

0.75

Intermediate ceilings above rooms that are 

heated to some extent

0.75

1.25

Heating areas between outside air or earth

0.35

2.86

Cellar ceilings, walls or ceilings next to unhea- 

ted rooms

0.35

2.86

Minimum heat transfer coefficient and minimum heat conductivity of 
the components.

Wärmedämmung und Verlegung als Direktheizung im Dünnbettkleber

Heat insulation and installation as direct heating in thin bed adhesive

Thermal insulation and laying as 
direct heating in thin-bed adhesive.

Floor covering
Heating foil
Thin bed adhesive
Screed
Cover

Insulation layer

load-bearing floor

Содержание E-NERGY CARBON BASIC TT 1200

Страница 1: ...E NERGY CARBON Electric surface heating system Installation instructions operating manual Power supply unit BASIC TT mfh systems modern floor heating mfh systems modern floor heating...

Страница 2: ...02 INSTALLATION SKETCH Heating foil Control unit Thermo sensor Transformer Please keep this document in a safe place...

Страница 3: ...etreatment of the substrate 08 3 2 2 Thermal insulation 08 3 2 3 Installation methods 09 3 2 4 Installation under tiles 09 3 2 5 Ceiling installation 10 3 2 6 Use in humid wet rooms 10 4 Electrical co...

Страница 4: ...stribution box In case of change of ownership the Please inform the subsequent owner about the installation In humid wet rooms DIN VDE 0100 part 701 be taken into account If the E NERGY CARBON heating...

Страница 5: ...or safety When working on the heating system the operating instructions must be handed over to the installer for information The E NERGY CARBON system can be installed inconspicuously in ceilings wall...

Страница 6: ...strip on the heating track must not be damaged or cut 2 4 Operation The E NERGY CARBON system impresses with its easy installation and operation To achieve the comfortable temperature the controller...

Страница 7: ...hnitte immer nur von der unkontaktierten Seite der Heizfolie vornehmen Jede andere unsachgem e Besch digung der Folie wie z B Einrisse durch scharfe Gegenst nde oder Knicke sind zu vermeiden Bewahren...

Страница 8: ...ceilings drywall panels and wood based panels must be installed to bridge cracks in the joint area When installing on the floor dry screeds and wood based panels must always be laid in two layers and...

Страница 9: ...ccording to installation method C it must be ensured that the heating strips are secured against slipping with adhesive tape and that a minimum distance of 20 mm is maintained between the individual f...

Страница 10: ...mmissioning must be carried out by a qualified electrician Attention If the measured resistance values deviate by more than 15 from the output value damage to the contacts or the heating foil must be...

Страница 11: ...on room thermostat 230 V L N SK N D heating circuit fuses 15 A each E Connection protective conductor for housing cover Figure 1 Example power supply unit BASIC TT 800 W AP UP C D E B A Network connec...

Страница 12: ...oltage variations Select the installation site taking into account the safety instructions and the following points of view carefully The maximum cable length between the heating track and the device...

Страница 13: ...s of the BASIC TT power supply unit are designed for the connection of a room thermostat with 230 V AC The room thermostat is connected to the room thermostat L supply terminal and room thermostat N s...

Страница 14: ...ilm Anschlussschema Connection scheme Basic TT 36 400W 800W 1200W AP UP DC Filter optional Netzanschluss Mains Supply 230V 50Hz Heizkreis Output S2 Heizkreis Output S3 Heizkreis Output S4 Heizkreis Ou...

Страница 15: ...Filter optional Netzanschluss Mains Supply 230V 50Hz Heizkreis Output S2 Heizkreis Output S3 Heizkreis Output S4 Heizkreis Output S5 Thermostat L N 230V 50Hz Last Load Max 400W N Max 400 W pro Heizkr...

Страница 16: ...erminal room thermostat N must be connected to the switching contact N L N PE L N N SK 36V 36V 36V 36V 36V 0V 0V 0V 0V 0V L N PE Heizkreis Output S1 Heizfolie Heat film Anschlussschema Connection sche...

Страница 17: ...in the immediate vicinity of the heating foil so that it is clearly visible and place the operating instructions in the distribution box or a suitable location Possible cause Remedy Heating mode not...

Страница 18: ...Internal safety temperature switch 130 C automatic resetting Insulation material class B Housing protection class IP20 Dimensions L x W x H 400 W 250x173x75 mm 800 W 300 x 220 x 85 mm 1200 W 300 x 22...

Страница 19: ...mum lengths hicoTHER hicoTHER hicoTHER Max heat transfer resistance R forfloor Explanation of symbols a Waste disposal instructions the product may n general household waste It must be recycled v wast...

Страница 20: ...199 06 99 53 516 00 262 80 188 30 0 2 m 182 92 99 53 49 77 258 00 131 40 94 15 0 3 m 121 95 66 35 33 18 172 00 87 60 62 77 0 4 m 91 46 49 77 24 88 129 00 65 70 47 08 0 5 m 73 17 39 81 19 91 103 20 52...

Страница 21: ...6 3 9 m 9 38 5 10 13 23 6 74 4 83 4 0 m 9 15 4 98 12 90 6 57 4 71 4 1 m 8 92 4 86 12 59 6 41 4 59 4 2 m 8 71 4 74 12 29 6 26 4 48 4 3 m 8 51 4 63 12 00 6 11 4 38 4 4 m 8 31 4 52 11 73 5 97 4 28 4 5 m...

Страница 22: ...7 3 m 5 01 7 07 3 60 7 4 m 4 94 6 97 3 55 7 5 m 4 88 6 88 3 50 7 6 m 4 81 6 79 3 46 7 7 m 4 75 6 70 3 41 7 8 m 4 69 6 62 3 37 7 9 m 4 63 6 53 3 33 8 0 m 4 57 6 45 3 29 8 1 m 4 52 6 37 8 2 m 4 46 6 29...

Страница 23: ...7 m 3 42 4 82 10 8 m 3 39 4 78 10 9 m 3 36 4 73 11 0 m 3 33 4 69 11 1 m 4 65 11 2 m 4 61 11 3 m 4 57 11 4 m 4 53 11 5 m 4 49 11 6 m 4 45 11 7 m 4 41 11 8 m 4 37 11 9 m 4 34 12 0 m 4 30 12 1 m 4 26 12...

Страница 24: ...FLEECE 66 W lfm 110 W m FLEECE 132 W lfm 220 W m FLEECE S 25W lfm 145W m FLEECE S 50W lfm 290W m PET 69 W lfm 115 W m 13 2 m 3 91 13 3 m 3 88 13 4 m 3 85 13 5 m 3 82 13 6 m 3 79 13 7 m 3 77 13 8 m 3...

Страница 25: ...r to have them repaired by a third party and to bear the costs incurred Furthermore mfh systems is entitled to de liver a comparable system from mfh systems or from a third party supplier as a replace...

Страница 26: ...___________________________ Elektroinstallateur Electrician _______________________________ Verlegedatum Fitting date _______________________________ Installationsdatum Installation date _____________...

Страница 27: ...nce after mounting 1 cm W m2 2 cm W m2 3 cm W m2 4 cm W m2 5 cm W m2 6 cm W m2 7 cm W m2 8 cm W m2 9 cm W m2 10 cm W m2 11 cm W m2 12 cm W m2 13 cm W m2 14 cm W m2 15 cm W m2 16 cm W m2 Resistance val...

Страница 28: ...RGY CARBON PET 69 W lfm 115 W m It is hereby confirmed that the above mentioned products comply with the essential requirements laid down in the Council Directive on the approximation of the laws of t...

Страница 29: ...29 heating foil assembled E NERGY CARBON room thermostats including temperature sensor and E NERGY CARBON power supply BASIC TT...

Страница 30: ...30 Notes...

Страница 31: ...31...

Страница 32: ...ystems GmbH Hager Feld 8 49191 Belm Vehrte Germany Fon 49 0 5406 699 95 10 Fax 49 0 5406 699 95 90 mail mfh systems com www mfh systems com Social Media Online download area LEAD FREE Im Einklang mit...

Отзывы: