4.4 Heating circuit connection
Please note the following: After the heating tracks have been laid, the connecting cables can be connected to the
secondary side of the device. For this purpose, connect the output terminals 36 V (Figure 1, Letter B) to the connec-
tion lines of the heating tracks.
Notice
Per connection (output terminal pair 36 V) max. 400 W may be connected.
The connected total power must not exceed the rated power of the power supply unit.
Variant 3: Connection of a potential-free switching contact
When using a potential-free switching contact, the supply terminal room thermostat L (230 V) is connected to the
switching contact SK via the potential-free contact. In addition, the supply terminal room thermostat N must be
connected to the switching contact N.
L
N
PE
L
N
N
SK
36V
36V
36V
36V
36V
0V
0V
0V
0V
0V
L
N
PE
Heizkreis/Output
S1
Heizfolie/Heat
film
Anschlussschema / Connection scheme
Basic TT 36-400W/800W/1200W AP/UP
DC
Filter(
optional
)
Netzanschluss/
Mains
Supply
230V/50Hz
Heizkreis/Output
S2
Heizkreis/Output
S3
Heizkreis/Output
S4
Heizkreis/Output
S5
Thermostat
L
N
230V/50Hz
Last/
Load
Max.400W*
N
*Max. 400 W pro Heizkreis. Die angeschlossene Gesamtleistung der Heizkreise darf die Nennlast des Trafos nicht
überschreiten.
*Max. 400 W per output. The connected total power of the outputs must not exceed the nominal load of the
transformer
L
L
N
N
N
PE
SK
Relay with
potential-free
contact
Heating foil
Heating circuit/Output S1
Heating circuit/Output S2
Heating circuit/Output S3
Heating circuit/Output S4
Heating circuit/Output S5
Network connection/ L
Main supply N
230V/50Hz PE