NDX VALVE CONTROLLER
All parameters
This view lists all configurable device parameters. In offline
mode, All parameters view is the view, which is opened
from the frame application “Offline parameterize” menu
option for parameterizing the device beforehand before
going to online mode or before the device is available.
All parameters view provides a central place to parame
terize the whole device in one place.This allows seasoned
service personnel to quickly configure the device from the
ground up. This view also allows separate configuration
phase and commissioning phase in places, where DTM
instances are configures before there is the physical device
network available. To send offline parameterization to
the device, open the DTM GUI in online mode and send
modifications by clicking Apply button.
Fig. 61
Device Information
Parameter name
Description
Default value
Limits/options
HART Tag
8 characters
NDX
Device Date
Enter a date, e.g. the date when you installed the device.
31.03.2016
Description
Enter a description of the device (max. 16 characters)
NDX
Message
Enter any other relevant information (max. 32 characters)
NDX
HART Long Tag
32 characters, case sensitive, allows consistent implementation
in Host Applications for the longer tag names demanded by
industry users
NDX
HART protocol (restart required)
Restart required after changing the HART protocol.
HART 6
HART 6
HART 7
Assembly Related
Parameter name
Description
Default value
Limits/options
Positioner Fail Action
Set Positioner Fail Action according to actuator spring
direction.
If you change the value of this parameter, calibrate the device.
When there is linear actuator without mechanical limit in open/
closed end, it is recommended to use Manual calibration.
Close
Close
Open
Position Transmitter Direction
Set position transmitter signal direction.
Normal direction: Output rises when valve angle rises
Normal direction
Normal direction
Reverse
Position Transmitter Fail Value
Position transmitter output when the NDX has a fatal error or is
powered off.
3.5 mA
3.5 mA
22.5 mA
Actuator Type
Select actuator type
Select single acting or double acting parameter, depends on
actuator type.
If you change the value of this
parameter, calibrate the device.
Single Acting
Single Acting Actuator
Double Acting Actu
ator
Valve Type
Select valve type.
Defines if device is mounted top of the linear valve or rotary
valve. Dead angle and Beacon position menu are visible if
Rotary is selected as valve type.
If you change the value of this parameter, calibrate the device.
Linear
Rotary
Linear
Dead Angle
This setting is made mainly for segment and ball valves. The
entire signal range is then used for effective valve opening
90° α0.
Refer to device user guide for proper dead angle value for your
valve type.
0 %
0100 %