24
NDX VALVE CONTROLLER
3. The distance between the magnet and the device
bottom shall be 4.5 mm with +/ 3 mm tolerance
(1.5 7.5 mm).
4. Check that following magnet alignment require
ments are not exceeded.
Figure 24 shows the exclusion zone. There is no material
limitation outside the exclusion zone, but to guarantee the
optimal performance do not use any magnetic material
inside the zone. Inside the exclusion zone but close to the
”walls” AISI 304 and any austenitic steel can be used.
Fig. 25
4.5 +/ 3 [mm]
Fig. 23
Max 6 deg
Max 1 mm
Max 3 mm
Max 4 deg
Max 3 deg
Max 2 mm
Fig. 24
7
LINEAR MOUNTING