34
NDX VALVE CONTROLLER
420 mA
OUT
(Optional)
+
420 mA
IN
+
2 pc. 1/2” NPT Standard
M20X1.5 available with adapter
PH2 3 mm 10 mm
Fig. 37 Wiring of NDX1510_
Connector
Function
Power Source
Min. Power
Impedance
Other
IN
Setpoint / HART
420 mA
Loop Power
3.8 mA,
9.7 VDC
485 Ω at 20 mA
OUT
Position Transmitter
External
12 ... 30 VDC
780 Ω max,
690 Ω for I.S.
Fail safe output is
3.5 mA or 22,5 mA
420 mA OUT
or
NAMUR DO
(Optional)
+
420 mA
IN
+
Namur
DO
(Optional)
+
PH2 5 mm 10 mm
2 pc. 1/2” NPT Standard
M20X1.5 available with adapter
Fig. 38 Wiring of NDX_511_ and NDX_512_
NOTE
Remove temporary cable gland plugs with 10
mm hexagon wrench.