DL7, DL7L
73
Cyclic report
tab
The cyclic report contains the values and units of the selected totalizers at the time of
sending the message.
Mode: Disabled
(Disabled, Daily, Weekly, Monthly)
[1]
Hour: 0
(0, .., 23)
[2]
[1]: E-mail messages can be sent in the mode:
Daily
– select
Hour
,
Weekly
– select
Hour
and
Day of the week
or
Monthly
– select
Hour
and
Day of the month
of sending the
message. The e-mail will be sent at the indicated time and will contain the values and
units of the totalizers at the time of sending the message (data sent in the form of
a table).
[2]: The e-mail is sent at the indicated full hour or each time after starting the device within
the indicated hour.
12.3.3 Modbus TCP (Client)
Device enables reading out up to 100 values from 20 devices via Ethernet connection
(Modbus TCP protocol). To ensure proper communication, all parameters in
Servers
tab
and in
Register
tab need to be configured.
Read values can be assigned to channels (channel type:
Modbus TCP
, more information
Servers
tab
Up to 20 servers can be configured.
Mode: Disabled
(Disabled, Enabled)
[1]
Address:
[2]
IP address:
[value]
[3]
Port:
[value]
[4]
Timeout:
[value] ms (1000, .., 60000)
[5]
Frequency:
[value] s (1, .., 3600)
[6]
[1]: Turns on/off servers. If sensor or device (
slave
) connected with servers will be
disconnected, it is recommended to set mode for server as
Disabled
(changed in
Channels
window and in
Register
tab is not necessary); after plugged on sensor set
mode for server as
Enabled
.
[2]: Column
Address
enabling easy identification of the added server. Entered data are
displayed in the format
IP addres
:
Port
, for example 192.168.2.15:502.
[3]: Parameters should correspond to the network where the recorder is intended to
operate.
[4]: It is recommended to use the 502 port dedicated to Modbus TCP, port 80 is not allowed
(reserved
for the device’s www server).
[5]: Timeout between Query and Response.
[6]: Frequency of Query sending. If several sensors are connected to one server, the value
entered in the Frequency field determines the time between sending Query for
consecutive sensors.
Register
tab
#: 1
(1, .., 100)
[1]
Server:
[value] (Disabled, selection from the list of added servers)
[2]