DL7, DL7L
70
OUT6RL
Mode: Disabled
(Disabled, Normally open, Normally closed, Pulsation)
[1]
[1]: In the
Normally open
mode the relay circuit is closed when an event is reported (e.g.
exceeded alarm-control threshold). In the
Normally closed
mode, the relay circuit is
normally closed when idle, and is opened when an event is reported.
Pulsation
- when
an event is reported, the relay circuit is closed and opened at approx. 1 Hz frequency
(e.g. a light indicator blinks - alarm notification). After the acknowledge, the relay output
remains active if the threshold is still exceeded (the indicator is lit). If the exceeding
returns to normal
– the relay output will be inactive.
Notes:
Regardless of the
Mode
selected, after switching off the device and during
starting the device, the relay outputs remain open.
OUT3
Mode: Disabled
(Disabled, 0-20mA, 4-20mA, 0-24mA, 0-5V, 0-10V)
[1]
Source: Channel 1
(Channel 1, .., 100)
[2]
Failure value: Constant
(Disabled, Constant)
[3]
[1]: Setting the operating mode of a given output to generate standard loop current signals:
0-20 mA, 4-20 mA, 0-24 mA or standard voltage signals: 0-5 V, 0-10 V, (
Disabled
sets
the output to 0-5 V mode and value 0 V).
[2]: Selection of the channel which value is to be retransmitted. The output span may be
set as a sub-range of retransmitted channel span by entering the process values for
minimum and maximum span value respectively.
[3]: The failure from the source channel
may be retransmitted as the constant “special”
value on the output. If
Disabled
mode is selected, the value is set to 0, except for to
mode 4-20mA when it is set to 3.6 mA.
PSBATT
In the I/O settings window additional module configuration is not required. The module
operating parameters are automatically assigned to subsequent virtual measuring inputs:
1.
Battery charge status {1; 2; 3}:
1
– low battery level
2
– medium battery level
3
– high battery level
Notes:
The approximate battery charge indicator depends on the load.
2.
Operating mode: charging / discharging {0; 1; 2; 3}:
0
– battery operating (external power supply switched off)
1
– pre-charging
2
– main charging
3
– recharging
3.
Voltage (BATT1+BATT2) [V] (approximate
value, accuracy ± 5%)
4.
Charging current [A]
5.
BATT1 battery temperature
[⁰C]
6.
BATT2 battery temperature
[⁰C]