7.6
Testing RCDs
Various test and measurements are required for verification of RCD(s) in RCD protected
installations. Measurements are based on the EN 61557-6 standard.
The following measurements and tests (sub-functions) can be performed:
Contact voltage,
Trip-out time,
Trip-out current and
RCD Auto test.
Figure 7.22: RCD menus
Test parameters / limits
I dN
Rated RCD residual current sensitivity
[10 mA, 30 mA, 100 mA, 300 mA, 500
mA, 1000 mA]
Type
RCD type
[AC, A, F, B*, B+*]
Use
RCD / PRCD selection
[fixed, PRCD, PRCD-S, PRCD-K]
Selectivity Characteristic
[G, S]
X IdN
Multiplication factor for test current
[0.5, 1, 2, 5]
Phase
Starting polarity
[+, -]
Limit Uc
Conventional touch voltage limit
[25 V, 50 V]
* Model MI 3152 only.
Connection diagram