![METREL EurotestXC Скачать руководство пользователя страница 149](http://html1.mh-extra.com/html/metrel/eurotestxc/eurotestxc_instruction-manual_1779026149.webp)
MI 3152(H)
Eurotest
XC (2,5 kV)
Technical specifications
149
12.10
Rpe – PE conductor resistance
RCD: No
R
–
PE conductor resistance
Measuring range (
)
Resolution (
)
Accuracy
0.00 ... 19.99
0.01
(5 % of r 5 digits)
20.0 ... 99.9
0.1
100.0 ... 199.9
0.1
10 % of reading
200 ... 1999
1
Measuring current .................................... min. 200 mA into PE resistance of 2
RCD: Yes,
no trip out of RCD
R
– PE conductor resistance
Measuring range (
)
Resolution (
)
Accuracy
0.00 ... 19.99
0.01
(5 % of r 10 digits)
20.0 ... 99.9
0.1
100.0 ... 199.9
0.1
10 % of reading
200 ... 1999
1
Accuracy may be impaired in case of heavy noise on mains voltage.
Measuring current .................................... < 15 mA
Nominal voltage range ............................. 93 V ... 134 V (45 Hz ... 65 Hz)
185 V ... 266 V (45 Hz ... 65 Hz)