![METREL EurotestXC Скачать руководство пользователя страница 153](http://html1.mh-extra.com/html/metrel/eurotestxc/eurotestxc_instruction-manual_1779026153.webp)
MI 3152(H)
Eurotest
XC (2,5 kV)
Technical specifications
153
12.15
Currents
Instrument
Maximum voltage on C1 measuring input ........ 3 V
Nominal frequency ................................... ........ 0 Hz, 40 Hz ... 500 Hz
Ch1 clamp type: A1018
Range: 20 A
I1
– Current
Measuring range (A)
Resolution (A)
Accuracy*
0.0 m ... 99.9 m
0.1 m
(5 % of r 5 digits)
100 m ... 999 m
1 m
(3 % of r 3 digits)
1.00 ... 19.99
0.01
(3 % of reading)
Ch1 clamp type: A1019
Range: 20 A
I1
– Current
Measuring range (A)
Resolution (A)
Accuracy*
0.0 m ... 99.9 m
0.1 m
indicative
100 m ... 999 m
1 m
(5 % of reading )
1.00 ... 19.99
0.01
(3 % of reading)
Ch1 clamp type: A1391
Range: 40 A
I1
– Current
Measuring range (A)
Resolution (A)
Accuracy*
0.00 ... 1.99
0.01
(3 % of r 3 digits)
2.00 ... 19.99
0.01
(3 % of reading)
20.0 ... 39.9
0.1
(3 % of reading)
Ch1 clamp type: A1391
Range: 300 A
I1
– Current
Measuring range (A)
Resolution (A)
Accuracy*
0.00 ... 19.99
0.01
indicative
20.0 ... 39.9
0.1
40.0 ... 299.9
0.1
(3 % of r 5 digits)
* Accuracy at operating conditions for instrument and current clamp is given.