8.1
AUTO TT – Auto test sequence for TT earthing system
Tests / measurements implemented in AUTO TT sequence
Voltage
Z line
Voltage Drop
Zs rcd
RCD Uc
Figure 8.3: AUTO TT menu
Measurement parameters / limits
I dN
Rated RCD residual current sensitivity
[10 mA, 30 mA, 100 mA, 300 mA,
500 mA, 1000 mA]
Type
RCD type
[AC, A, F, B*, B+*]
Selectivity
Characteristic
[G, S]
Fuse type
Selection of fuse type
[gG, NV, B, C, D, K]
Fuse I
Rated current of selected fuse
Fuse t
Maximum breaking time of selected fuse
Limit(dU)
Maximum voltage drop
[3.0 % ... 9.0 %]
Limit Uc(Uc)
Conventional touch voltage limit
[25 V, 50 V]
Ia(Ipsc (LN),
Ipsc (LPE))
Minimum short circuit current for selected fuse
See Appendix A for reference fuse data.
* Model MI 3152 only.
Connection diagram
Figure 8.4: AUTO TT measurement