![METREL EurotestXC Скачать руководство пользователя страница 160](http://html1.mh-extra.com/html/metrel/eurotestxc/eurotestxc_instruction-manual_1779026160.webp)
MI 3152(H)
Eurotest
XC (2,5 kV)
Appendix A
– Fuse table – IPSC
160
Fuse type C
Rated
current
(A)
Disconnection time [s]
35m
0.1
0.2
0.4
5
Min. prospective short- circuit current (A)
0.5
5
5
5
5
2.7
1
10
10
10
10
5.4
1.6
16
16
16
16
8.6
2
20
20
20
20
10.8
4
40
40
40
40
21.6
6
60
60
60
60
32.4
10
100
100
100
100
54
13
130
130
130
130
70.2
15
150
150
150
150
83
16
160
160
160
160
86.4
20
200
200
200
200
108
25
250
250
250
250
135
32
320
320
320
320
172.8
40
400
400
400
400
216
50
500
500
500
500
270
63
630
630
630
630
340.2
Fuse type D
Rated
current
(A)
Disconnection time [s]
35m
0.1
0.2
0.4
5
Min. prospective short- circuit current (A)
0.5
10
10
10
10
2.7
1
20
20
20
20
5.4
1.6
32
32
32
32
8.6
2
40
40
40
40
10.8
4
80
80
80
80
21.6
6
120
120
120
120
32.4
10
200
200
200
200
54
13
260
260
260
260
70.2
15
300
300
300
300
81
16
320
320
320
320
86.4
20
400
400
400
400
108
25
500
500
500
500
135
32
640
640
640
640
172.8