Technical Bulletin—TC-9100 Universal Controller
59
Specifications & Technical
Data
Supply Voltage
24 VAC, ±15%, 50-60 Hz.
Power Consumption
5 VA for controller only (not including power consumption of connected
actuator devices).
Ambient Operating
Conditions
0° to 50°C
10 to 90% RH noncondensing
Ambient Storage
Conditions
-40° to 70°C
10 to 90% RH
Terminations
Screw terminal blocks for 1 x 1.5 mm
2
/14 AWG (maximum) cable.
Separable terminal blocks are available as an option.
Communication
Interfaces
Optically isolated RS-485 interface for N2 Bus connection at 9600 baud.
Service Module (SM-9100) interface at 600 baud: non-isolated synchronous
bus.
Room Command Module (TM-9180) interface at 600 baud: non-isolated
synchronous bus.
Controller Addressing
0-255 selectable on DIP switches (8).
Inputs
Four analog inputs (AI1-AI4):
0 to 10 VDC
(controller input impedance > 100 KOhm).
Supply for sensors:
15 VDC, 20 mA.
Two digital inputs (DI1, DI2):
Volt-free contacts
(closed contact resistance < 1 KOhm).
Alternative (DI1 only):
Condensation Sensor, Type HX-9100-8001.
Occupancy button
Volt-free momentary contact
(Alternate mode):
(use TM-9180 or
RS-1150/RS-1160
room
module).
Continued on next page...