60
Technical Bulletin—TC-9100 Universal Controller
Outputs
(Cont.)
Model 1: TC-9100-x000
Two analog outputs: jumper selectable for either:
0 to 10 VDC (10 mA maximum),
or: PWM signal for Solenoid Valve Power Driver
(not used).
Five digital (triac) outputs: rated at 24 VAC (0.5 A maximum). Leakage
current 1 mA maximum.
Configurable as:
PAT (Position Adjust Type – Incremental Control),
DAT (Duration Adjust Type),
2-stage on/off,
3-speed fan control, or
On/off output types.
Model 2: TC-9100-x001
Seven digital (triac) outputs: rated at 24 VAC (0.5 A maximum). Leakage
current 1 mA maximum.
Configurable as:
PAT (Position Adjust Type – Incremental Control),
DAT (Duration Adjust Type),
2-stage on/off,
3-speed fan control, or
On/off output types.
Models 1 and 2:
Signal for Mode LED on TM-9180 or
RS-1150/RS-1160
room module.
(Refer
to
Software Configuration
section for output type configuration
details.)
Mounting
DIN rail or surface (two brackets supplied with controller).
Housing
Material:
ABS + polycarbonate, self-extinguishing VO UL94.
Protection: IP30 (IEC529)
Dimensions (H x W x D)
118 mm* x 108 mm x 31 mm
* 140 mm with separable terminals
Shipping Weight
0.3 kg
CE Compliance
(Directive 89/336/EEC)
EN61000-6-3
(EN 50081-1),
EN61000-6-1
(EN 50082-1)
Table 26: TC-9100 Universal Controller Ordering Codes
Description Model
Code
TC-9100 Universal Controller with Analog Outputs
TC-9100-
x
000*
TC-9100 Universal Controller without Analog Outputs
TC-9100-
x
001*
* For controller with standard terminals,
x
= 0; with separable terminals,
x
= 1.
Table 27: TC-9100 Controller Accessories Ordering Codes
Description Model
Code
Service Module
SM-9100-8101
Ordering
Codes