Technical Bulletin—TC-9100 Universal Controller
75
Item Type MEM R/W Tag Description
Hex Dec
Summer/Winter Compensation
Module
9F 159 Connection D WP
OT@ Outdoor Temperature
A0
160 Number
D
W
SPW
Winter Set Point
A1
161 Number
D
W
SPS
Summer Set Point
A2
162 Number
D
W
WA
Winter Authority Slope
A3
163 Number
D
W
SA
Summer Authority Slope
Low Limit Module
A4 164 Connection D
WP FT@
Low Limit (Anti-freeze) Temperature
Connection
A5
165 Number
D
W
FSP
Low Limit (Anti-freeze) Set Point
A6
166 Number
D
WP FDIF
Low Limit (Anti-freeze) Differential
A7
167 2 Bytes
VR
R
LOO
Local Output Override Status
X2
X1 FANS
3-Speed
Fan
Status
=00
OFF
=01
Speed
1
(Low)
=10
Speed
2
(Medium)
=11
Speed
3
(High)
X3
not
used
X4=1
FOS
Fan Override by Hardware Input
X6 X5
FANT
TM-9180 Fan Override Status
=00
OFF
=01
Speed
1
(Low)
=10
Speed
2
(Medium)
=11
Speed
3
(High)
X7
internal
use
X8=1 FOR Fan
Override
by
TM-9180
X9=1 AI01 AI1
Override
by
TM-9180
X10=1 AI02 AI2
Override
by
TM-9180
X11=1 AI03 AI3
Override
by
TM-9180
X12=1 AI04 AI4
Override
by
TM-9180
X16...X13
not
used