40 N2 Dialer Module—N2 Dialer Module (NDM)
-No phone number
-Configure phone numbers
Remote fails
to answer
-Remote modem not powered up
-Activate power
-Remote modem not configured
for auto answer
-Configure the modem for auto answer
-Phone line not connected
-Connect phone line
-Incorrect phone number
-Correct phone number
Remote fails to dial
on alarm
-Remote configured as local
-Reconfigure as remote
-No phone number
-Enter phone number
-Remote NDM modem string not
correct
-Correct remote modem string
-Remote modem not powered up
-Connect power to remote modem
-Dial-In control is disabled
-Enable Dial-In control
-N2 not connected to other
controllers
-Alarm points not defined in
controller or facility management
system
-Connect N2 to other controllers
-Reconfigure controller with proper alarm
points, and set up as critical alarm
points in facility management system
-N2 Device set to
Address 0
-Change N2 Address
-DX Controller not configured to
report alarm
-Configure DX Controller to report alarm
Continued on next page . . .