N2 Dialer Module—N2 Dialer Module (NDM) 23
Table 5: Local Dialer Communication Parameters
Item
Range
Description
Remote site phone
numbers (50 possible)
31 characters
Phone numbers of remote
dialers to call.
Number of retries
0-100
Number of retries before dial
operation ceases.
0 = until connection is made.
Dial delay
1 to 30 minutes
Number of minutes to delay
before redialing a remote facility;
i.e., a dial delay of 4 means that
the dialer attempts a call every
4 minutes.
Disconnect delay
1 to 255 minutes
Number of minutes to wait after
call connects before dialer
disconnects automatically.
Modem connect time
30-255 seconds
Amount of time waited for a
connection to be established
before hanging up and redialing.
Default = 60 seconds
Modem setup string
31 characters per line
Before dialing; i.e., AT&F
Disconnect delay
control
0-2
0=use disconnect delay
1=4-hour delay
2=never hang up
Dial command
-1 to 50
-1=remote site dialed in
0=hang up
1-50 =remote site number to dial
Connection status
0-4
0=idle
1=dialing
2=connected
3=retry
4=fail
Содержание N2
Страница 4: ...4 N2 Dialer Module N2 Dialer Module NDM ...
Страница 8: ...8 N2 Dialer Module N2 Dialer Module NDM ...
Страница 26: ...26 N2 Dialer Module N2 Dialer Module NDM ...
Страница 44: ...44 N2 Dialer Module N2 Dialer Module NDM ...
Страница 46: ...46 N2 Dialer Module N2 Dialer Module NDM ...
Страница 66: ...66 N2 Dialer Module N2 Dialer Module NDM Notes ...