N2 Dialer Module—N2 Dialer Module (NDM) 17
The dial command point initiates a dial-out sequence that causes the local NDM to dial
out to remote facilities. Overriding this point to a value from 1-50 causes the local NDM
to dial out to the site corresponding to the number that was configured in HVAC PRO for
Windows. Overriding this point to a value of zero causes the NDM to hang up a phone
connection. When a remote site initiates a call to the local NDM, the dial command
displays a value of -1.
Table 1: Dial Command
Value
Description
-1
A remote site dialed into the local NDM
0
Disconnect or hang up command
1-50
Remote site index as configured in HVAC PRO for Windows
The connection status is a read-only parameter, which provides information about the
connection between the local NDM and the remote NDM.
Table 2: Connection Status (read only)
Value
Description
0
Idle
1
Dialing
2
Connected
3
Retry
4
Failed
Table 3: Disconnect Delay
Value
Description
1-255 minutes
Default 10 minutes
Default number of
minutes to wait before
automatically
disconnecting a call--
user defined in
HVAC PRO for
Windows.