background image

30

© 2009 Merten by Schneider Electric

Push-button, 4-gang plus with room temperature control unit and IR receiver

Multifunction with RTCU and FanCoil 1817/1.0

Getting to know and parameterising the room temperature control unit

Setpoint adjustment affects all operation modes

In this setting, you not only change the setpoint temper-

ature for the current operation mode, you change all the 

setpoint temperatures in the same way and at the same 

time. The only setpoint temperatures that are not affect-

ed are those for the frost/heat protection. These opera-

tion modes also specify the limits of the setpoint 

adjustment. It is therefore not possible to set setpoint 

temperatures lower than the frost protection or higher 

than the heat protection.
You can specify the setpoint adjustment directly via the 

"Setpoint adjustment input" object and the control 

menu. By comparison, you use the "Current setpoint 

temperature input" object to specify a new setpoint tem-

perature. Setpoint adjustment is determined here by 

the difference between the current setpoint tempera-

ture and the "reference setpoint for calculating the set-

point adjustment". 

The active operating state of the controller is deter-

mined by the states of the communication objects: 

"Comfort", "Night reduction", "Frost/heat protection" 

and "Dewpoint alarm".
The highest priority when calculating the setpoints is 

the dewpoint alarm. If it occurs, heating continues to be 

possible but cooling is deactivated ("0" to the controller 

output). The dewpoint alarm is terminated when its 

communication object is set to "0".
After a reset, the operation mode you preconfigured is 

active. The corresponding setpoints then also apply. If 

the setpoint that was set is changed via the control 

menu and the value is higher or lower than the set limit, 

an acoustic signal can inform you of this (you can set 

this on the "Signal function" tab).
When a setpoint adjustment is received via the bus, the 

controller checks whether it lies within the parameter-

ised limits, and if necessary, adjusts it to the corre-

sponding limits.

Example 1

Cooling/heating
Limits of setpoint adjustment = +3 K/-3 K
Setpoint adjustment: "Setpoint adjustment input" object = +5 °C

Initial status

Result

Cooling:

Heating protection = 35 °C

Night = 28 °C

Standby = 26 °C

Comfort = 24 °C

Heating:

Comfort = 21 °C 

Standby = 19 °C 

Night = 17 °C 

Frost protection = 7 °C

Cooling:

Heat protection = 35 °C

Night = 

31 °C

Standby = 

29 °C

Comfort = 

27 °C

Heating

Comfort = 

24 °C 

Standby = 

22 °C

 

Night = 

20 °C

 

Frost protection = 7 °C

Example 2

Cooling/heating
Limits of setpoint adjustment = +10 K/-10 K
Setpoint adjustment: "Setpoint adjustment input" object = +20 °C

Initial status

Result

Cooling:

Heating protection = 35 °C

Night = 28 °C

Standby = 26 °C

Comfort = 24 °C

Heating:

Comfort = 21 °C 

Standby = 19 °C 

Night = 17 °C 

Frost protection = 7 °C

Cooling:

Heat protection = 35 °C

Night = 

35 °C

Standby = 

33 °C

Comfort = 

31 °C

Heating

Comfort = 

28 °C 

Standby = 

26 °C

 

Night = 

24 °C

 

Frost protection = 7 °C

Example 3

Cooling/heating
Limits of setpoint adjustment = +3 K/-3 K
New set value: object "Current setpoint temperature input" = 24 °C
Reference setpoint for calculating the setpoint adjustment = 21 °C
Calculated setpoint adjustment = +3 °C

Initial status

Result

Cooling:

Heating protection = 35 °C

Night = 28 °C

Standby = 26 °C

Comfort = 24 °C

Heating:

Comfort = 21 °C 

Standby = 19 °C 

Night = 17 °C 

Frost protection = 7 °C

Cooling:

Heat protection = 35 °C

Night = 

31 °C

Standby = 

29 °C

Comfort = 

27 °C

Heating

Comfort = 

24 °C 

Standby = 

22 °C

 

Night = 

20 °C

 

Frost protection = 7 °C

Содержание MEG6212-03 Series

Страница 1: ...operating instructions of your printer to find out which type of foil strips you can print Only use the coloured foil strips enclosed as the base since this ensures that the push button LEDs under the...

Страница 2: ...button and hold he hour dis play for the selected time switching time starts to flash 4 Press the left or right push button on the display Set the hours as desired 5 Press the central push button brie...

Страница 3: ...th RTCU and FanCoil 1817 1 0 Media type Twisted Pair Product name Push button 4 gang plus room temp control IR Order number MEG6214 40xx MEG6214 41xx Manufacturer Merten Product family 2 3 Push Button...

Страница 4: ...and factor parameters The actual time is giv en by the multiplication of the two values Exam ple Base 1 second factor 3 gives 3 seconds The bold values in a table are the values set dur ing factory co...

Страница 5: ...can be changed using the menu buttons on the push button see operating instruc tions If you use room temperature control Control general tab additional possible settings appear You can specify whether...

Страница 6: ...d via the feedback object Display Parameter Settings User menu enabled Yes No Adjust operation mode during frost heat protection Yes No Set display mode multiple names appear during the change Actual...

Страница 7: ...ton Two objects 1 bit 1 byte can also be transmitted in any combination when the push button is pressed Status indication The status LED can Be switched on or off continuously Light up when pressed fo...

Страница 8: ...B not equal to 0 Flashes when switch value object A equals 0 Flashes when switch value object B equals 0 Flashes when status feedback object equals 1 Flashes when status feedback object equals 0 Opera...

Страница 9: ...iod can be parameterised When switching takes place an ON OFF telegram is sent via the switch object When dimming dimming up or dimming down is carried out via the 4 bit dimming object the parameters...

Страница 10: ...rised You can specify whether a stop telegram is to be trans mitted when the push button is released If you have enabled the transmission of a stop telegram a stop tel egram will be transmitted via th...

Страница 11: ...the next time the push button is activated for a long period the exact period can be pa rameterised When a stop step telegram has been transmitted to ad just the slats a stop step telegram for the sam...

Страница 12: ...long operation of the push button Status indication The status LED can Be switched on or off continuously Light up when pressed for a long period and go out when released Flash Display the status of o...

Страница 13: ...are 1 bit 2 bit priority con trol 4 bit 1 byte in steps or infinitely Push button X Parameter Setting Edge function Normal operate release Number of objects One Two Push button X edges object A B Para...

Страница 14: ...ject values you may need to set the Read flags manually The following activation sequence chart shows the phases into which the pulse edge function is divided Example 1 Object A 1 bit Sends 1 None Non...

Страница 15: ...ends cyclically Toggles and is not sent Toggles cyclically sends immediately then cyclically Toggles cyclically only sends cyclical ly Toggles cyclically and is not sent Sends its value Sends its valu...

Страница 16: ...the toggled value is transmitted and a new cycle time is started Subsequently it is always toggled cyclically and the new value is transmitted Toggles cyclically only sends cyclically If no cycle time...

Страница 17: ...sed cy cle time e g 3 minutes it switches it back off again With a long press of the push button the same function is carried out but with a longer cycle time e g 6 min utes Number of objects 2 object...

Страница 18: ...of the switch ac tuator Number of objects 1 object A Object A 1 bit Object A Action on release before the long operating time has elapsed Sends 1 immediately and then cyclically Action on achieving t...

Страница 19: ...transmits the value which it currently has Therefore you can for example transmit a value with the sending group address which was previously re ceived via another group address No action Available va...

Страница 20: ...and value B is transmitted after one cycle time regardless of wheth er a cycle time is already running or not staircase lighting timer function None stops cyclical sending No action is carried out and...

Страница 21: ...step value Reduce current object value once Reduce the current object value once by the parame terised step value Any active cycle time is terminated Reverse slide direction and send cyclically If no...

Страница 22: ...gain after the last possible step Example Value 1 0 value 2 255 step size 100 the following values are sent 39 78 0 39 78 0 etc Decrease stepwise within limits The value is reduced by one step value a...

Страница 23: ...t different actions for short and long presses of a push button both for when the push button is pressed and for when it is released You can also set a cycle time which can be parameterised for each o...

Страница 24: ...ong operating time has elapsed Sends value 2 Action on achieving the long operating time Toggles Action on release after achiev ing the long operating time Toggles cyclically sends immedi ately then c...

Страница 25: ...on mode Parameter Settings Number of operation modes between which you want to toggle One Two Three Four Operation mode 1 Comfort extension operation Comfort operation Standby operation Night operatio...

Страница 26: ...push button s internal scene module and must be identical to the scene addresses in the module The scene addresses entered with this function are not transmitted to the bus Communication objects You...

Страница 27: ...Actuator group 7 is a special group which allows you to transmit values with 16 bits Specifying scene addresses and values For each scene you specify the scene address via which the scene on the exte...

Страница 28: ...2 Time control tab Set the Request time synchro nisation via the bus parameter to Yes 3 Time control tab For the Behaviour when syn chronisation fails parameter select whether the switching commands a...

Страница 29: ...Switching time 3 18 00 Switching time 4 22 00 The switching times are not carried out until the time has been set once via the control menu or via the time object When a change is made from a holiday...

Страница 30: ...re sensor integrated into the push button However you can also measure the temperature via an external sensor and transfer it to the controller via the bus which then takes it fully or partially into...

Страница 31: ...peration mode only or All operation modes Setpoint adjustment affects current operation mode only In this setting the setpoint temperature of the current operation mode is changed You can select wheth...

Страница 32: ...econfigured is active The corresponding setpoints then also apply If the setpoint that was set is changed via the control menu and the value is higher or lower than the set limit an acoustic signal ca...

Страница 33: ...button operation mode push button function comfort extension operation or The bus object Comfort extension The parameterised time for the comfort extension runs to an end and can then be restarted by...

Страница 34: ...ht operation mode This operation mode enables you to reduce or increase the room tem perature to a greater extent during the night or over the weekend In this operation mode you use a 1 tele gram to s...

Страница 35: ...mode has the highest priority A 0 telegram terminates the dewpoint alarm and the new operation mode is set The operation mode is the result of current informa tion from the objects Comfort input and N...

Страница 36: ...ing frost heat protec tion No Frost heat protection object or Temperature jump detection Disable object Dewpoint alarm object Dewpoint alarm 1 Cooling Yes 0 No Correcting variable cooling 0 1 0 1 Fros...

Страница 37: ...uator Electric convector Night storage heating Ceiling heating Cooling In the cooling control mode the current actual temper ature is compared with the current setpoint tempera ture If the actual temp...

Страница 38: ...ed to con tinue to heat the room above the setpoint temperature If you have configured the heating and cooling setpoint temperatures to be the same the insensitive zone is set to 0 K The air condition...

Страница 39: ...n not adjust the values for standby or night operation Two stage heating or cooling In order to shorten the heat up phase with slow heating systems e g underfloor heating a second more re sponsive hea...

Страница 40: ...its ad vantage is that the room temperature is not constant but changes continuously reducing comfort particularly when heating and cooling systems are slow to react To counteract this effect you can...

Страница 41: ...he controller Warm water heating Underfloor heating Electric heating Fan convector Split unit Cooling ceiling You can also set the control parameters for the propor tional range and the reset time man...

Страница 42: ...ceiling with motorised valve drives Switching electric radiator heating Air conditioning with 4 duct 2 circuit air convector sys tem e g switching valve drives Temperature limitation using shading fa...

Страница 43: ...t status object here If you want to display the system s status using visuali sation software there is one 1 byte status object and one 2 byte status object available for this purpose Structure of the...

Страница 44: ...e The following formula applies Actual temperature measured temperature correc tion value If you also use an external temperature sensor you can set the percentage proportion at which the external ac...

Страница 45: ...system types for which the recommended parameters have already been preconfigured Howev er if you have sufficient specialised knowledge you can also set the control parameters as required For 2 step...

Страница 46: ...water when the heating is switched off for a longer period of time e g over the summer When the valve protection is switched on the valves are opened for a preset dura tion 100 on the controller outpu...

Страница 47: ...variables Parameter Setting Function Object name Type Prio Flags Behaviour Control Current actual tem perature output 2 byte Low CRT Transmit read out Control Current actual tem perature input 2 byte...

Страница 48: ...ow CRT Transmit read out Control Correcting variable heating basic level 1 byte Low CRT Transmit read out Control Correcting variable heating additional level 1 bit Low CRT Transmit read out Control C...

Страница 49: ...iour when bus voltage fails The operation LEDs status LEDs are switched off to gether with the display including the background light ing Merten GmbH Solutions for intelligent buildings Serv ice Cente...

Отзывы: