46
© 2009 Merten by Schneider Electric
Push-button, 4-gang plus with room temperature control unit and IR receiver
Multifunction with RTCU and FanCoil 1817/1.0
Display external temperature in display
You can cyclically read an external temperature value
(2-byte value) via the bus and display it. The external
temperature can be the outdoor temperature transmit-
ted from a weather station, for example.
|
The external temperature is only shown in the dis-
play, this temperature has no effect on the control
behaviour of the push-button.
Communication objects
You can select the following communication objects:
You can use this setting in combination with the Fan Coil
actuator, for example. If you combine it with the "Linear
regulator" push-button function, you can easily control
fan speeds with one push-button.
The display can be used to show whether the fan of the
fan coil actuator is working in automatic or manual
mode and which fan speed is currently activated. The
status feedback object can be used to send the status
to the LED.
In the parameters, you can set the percentage values at
which the individual levels are displayed.
Communication objects
You can select the following communication objects:
Control
Cooling status (basic
level)
1 byte Low CRT
Transmit/
read out
Control
Correcting variable
heating (basic level)
1 bit
Low CRT
Transmit/
read out
Control
Correcting variable
heating (basic level)
1 byte Low CRT
Transmit/
read out
Control
Correcting variable
heating (additional
level)
1 bit
Low CRT
Transmit/
read out
Control
Correcting variable
heating (additional
level)
1 byte Low CRT
Transmit/
read out
Control
Correcting variable
cooling (basic level)
1 bit
Low CRT
Transmit/
read out
Control
Correcting variable
cooling (basic level)
1 byte Low CRT
Transmit/
read out
Control
Correcting variable
cooling (additional
level)
1 bit
Low CRT
Transmit/
read out
Control
Correcting variable
cooling (additional
level)
1 byte Low CRT
Transmit/
read out
Control
Dewpoint alarm
1 bit
Low WC
Receive
Display external temperature in display
Display external temperature
Parameter
Settings
Read external temperature cyclically Yes
No
Cycle time = base * factor
Base
1 s
1 min
1 h
1 day
Factor (3-255)
3-255,
3
Function
Object name
Type
Prio Flags Behaviour
Display exter-
nal tempera-
ture
External tempera-
ture
2 byte Low WCT Transmit/
receive
Function Object name
Type
Prio Flags Behaviour
Controlling and displaying the fan speed
Fan speed
Parameter
Setting
Number of fan speeds
1 - 7,
3
Value range for speed display:
1-100 %
Display fan speed 1 up to ... %
1 - 100%,
34%
Display fan speed 2 up to ... %
1 - 100%,
67%
Display fan speed 3 up to ... %
1 - 100%,
100%
Display "Auto" in display
If fan status automatic is "0"
If fan status automatic is "1"
Function
Object name
Type Prio Flags Behaviour
Display of
fan speed
Fan 0 -100 %
1 byte Low WC
Receive
Display auto-
matic
Fan status auto-
matic
1 bit
Low WC
Receive