WALL SWITCH, REMOTE CONTROL OR THERMOSTAT OPERATION
The Insert comes with an "ON-OFF" Rocker Switch located in the lower right hand corner of the
surround. An optional Wall Switch, remote control or thermostat may be purchased to substitute for
the Rocker Switch. A thermostat should be placed in the same room as the fireplace, approx. 4-5 ft.
off the floor. Do Not place thermostat near the fireplace. Thermostat must be 460 to 750 Millivolt
rated. An on-off wall switch or remote control may be used if Insert is not used primarily as a
supplementary heat source.
WHEN INSTALLED IN A SLEEPING AREA, A THERMOSTAT
IS REQUIRED.
NOTE:
If thermostat is located over 25 ft. from the fireplace the pilot flame may need to be
increased.
CAUTION: BURNER SHOULD LIGHT IMMEDIATELY AFTER TURNING WALL SWITCH OR
THERMOSTAT "ON". IF BURNER DOES NOT COME ON IMMEDIATELY TURN THE
THERMOSTAT/WALL SWITCH OFF AND WAIT 60 SECONDS BEFORE TURNING ON AGAIN. IF BURNER
DOES NOT COME ON IMMEDIATELY AFTER SECOND TRY RECHECK COMPLETE INSTALLATION OF
LOGS, PILOT, ETC. TO INSURE PROPER PILOT FLAME IMPINGEMENT ON THE THERMOPILE AND
PROMPT BURNER IGNITION
.
NEVER TURN BURNER ON & OFF "QUICKLY" - ALWAYS WAIT 60 SECONDS!
When using remote control be sure to hold in button firmly until Insert lights. DO NOT push button
and release quickly before Insert lights. Insert should light IMMEDIATELY and then button can be
released. If Insert does not light immediately release button, wait 60 seconds and repeat lighting
procedure.
Use two-wire, copper lead wire per chart and install as follows:
FIGURE 12
NOTE: Thermostat Must Be 325-750 Millivolt Rated
CAUTION:
THIS CONTROL IS A MILLIVOLT SYSTEM. NO ADDITIONAL POWER SUPPLY CAN OR
SHOULD BE USED.
RECOMMENDED MAXIMUM
LEAD LENGTH (TWO-WIRE)
WHEN USING WALL THERMOSTAT
(CP-2 SYSTEM)
WIRE SIZE MAX.
LENGTH
14 GA.
100 FT.
16 GA.
64 FT.
18 GA.
40 FT.
20 GA.
25 FT.
22 GA.
18 FT.