Mendota MEDALLION Скачать руководство пользователя страница 13

 

A-2.  ELEVATED RISE THROUGH-THE-WALL VENTING 

The maximum vertical rise is 15 ft. when used with a maximum horizontal run of 15 ft.  For other venting 
configurations within these maximum limits (see Figure 5, page 10).  
NOTE:  The horizontal run of vent pipe must be level or have a ¼" rise for every 1' of run toward the  
               termination.  Never allow the vent to run downward.  This will cause high temperatures and the 
               possibility of a fire. 
USING OFFSETS AND RETURNS:  A single 90

º

 vertical-to-horizontal elbow is already calculated into 

the allowable maximum 12' horizontal run.  Each additional 90

º

 elbow reduces the maximum horizontal 

distance by 3'.  Example:  by using three total 90

º

 elbows the maximum horizontal distance has been 

reduced to 6 ft. (3 - 1 = 2 elbows x 3' = 6'; 12’ Max. - 6' of elbows = 6' of horizontal run).  Note:  45

º

 

elbows reduce the maximum horizontal distance by 1½ '.

  

Always maintain the proper rise (6' for each 

elbow used after the initial elbow) for the calculated total run when using elbows. 
SUPPORT:  Horizontal runs of pipe will require one vent support for every 3 ft. of pipe. 
CAUTION:  If a vertical-to-horizontal elbow is enclosed within a wall, floor or ceiling, a top air space  
 clearance of 3" must be maintained. 
Be sure to maintain 1 1/2" air space clearances to any combustibles. 
 

IMPORTANT:  REFER TO DRAWINGS ON PAGES 9 & 10 WHILE FOLLOWING THESE INSTRUCTIONS. 

 

The Medallion Stove must be installed by a qualified Mendota service person. 

 

1.  Position stove in desired location.  See page 7 for guidelines on proper vent cap placement on exterior 

of home.  Check to determine if wall studs are in the way when vent system is attached.  If this is the 
case you may want to adjust the stove location. 

 

2.  Locate position where vent pipe will pass through any ceilings and will penetrate the outside wall.  

Since vent pipe sections "overlap" we suggest preassembling and measuring the total vent pipe run so 
you can more accurately locate the point where the vent pipe will penetrate the outside wall. Be sure 
components are properly twist locked and leak proof.  (See Pg. 8 "

TWIST LOCK PROCEDURE

").  Be 

sure all vent components are properly twist lock-proof.  Be sure Millpak 2000° sealant (#65-06-00909) 
is used in the inner joints of all adjustable pipe sections. 

 
 
3.  Cut and frame a 10" x 10" opening in the outside wall and in any ceiling openings.  The outside wall 

hole must be positioned so the vent system will run level or have a ¼ " on rise AND be perpendicular to 
the wall.  The height of the opening must be located to meet all local and national building codes and 
not allow the termination to be easily blocked or obstructed.  A ceiling firestop spacer is required at any 
floor (ceiling) opening. 

*NOTE:  DO NOT SEPARATE TELESCOPING SECTIONS USE AS COMPLETE ASSEMBLIES. 

4.  Connect vent pipe to the stove adapter on top of stove vent outlet. 

5.  The horizontal pipe must end flush with the exterior wall of the home.  Horizontal pipe will require a 

proper support every 3 ft. of vent pipe.  THERE MUST BE A MINIMUM OF 1 1/2" CLEARANCE 
TO COMBUSTIBLES FROM ALL VENT PIECES.  Use decorative wall thimble kit on inside of wall 
before connecting horizontal run to vent termination. 

6.  From the exterior of the home, slide the horizontal vent cap over the end of the horizontal pipe and 

tightly secure the vent cap to the wall with screws.  Seal with high quality caulking. 
NOTE:  Do not recess vent termination cap into the wall or siding. 

 
 

 

 

1

Содержание MEDALLION

Страница 1: ...TINGUISH ANY OPEN FLAME 5 IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR S PHONE 6 FOLLOW THE GAS SUPPLIERS INSTRUCTIONS 7 IF GAS SUPPLIER IS UNAVAILABLE CALL YOUR FIRE DEPARTMENT DO NOT STORE OR...

Страница 2: ...AL TOTAL WEIGHT 225 LB SAFETY AGA CERTIFIED PILOT GENERATOR MILLIVOLT THERMOCOUPLE SYSTEM ACTIVATED WITH SWITCH OR THERMOSTAT GAS REQUIREMENTS SUPPLY PRESSURE NAT GAS 7 W C 5 W C MIN 11 W C MAX L P GA...

Страница 3: ...on repair and any adjustments to logs or burner must be done by a qualified service person The Stove should be inspected before use and at least annually by a professional service person More frequent...

Страница 4: ...ant Si aucun code n existe suivez la norme ANSI Z223 1 ou la norme CAN CGA ACNOR B149 _______________________________________________ MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTION Unit to sidewall...

Страница 5: ...urce of supplemental heat Air movement options for maximizing heat circulation which can be considered are through the wall grills or floor grills or the continuous operation of central heating blower...

Страница 6: ...MENDOTA MEDALLION MENDOTA DIRECT VENT FREESTANDING GAS STOVE SPECIFICATIONS CLEARANCES Figure 2 Specifications Clearances 5...

Страница 7: ...ss window door by releasing the 4 turn latches behind side doors rotate latches counterclock wise and pull outward and carefully sliding glass door forward 4 You are now ready to hook up the gas suppl...

Страница 8: ...Vertical clearance to ventilated soffit located above the terminal from the center line of the terminal 18 inches 46 cm minimum K Clearance to a mechanical air supply inlet 6 feet 1 8 m minimum E Cle...

Страница 9: ...rate vent system Common vent systems are prohibited Do not recess vent termination into a wall or siding WE STRONGLY RECOMMEND THAT FIXED LENGTH PIPE SECTIONS BE USED IN PLACE OF TELESCOPING SECTIONS...

Страница 10: ...Galvanized 36 RIGID VENT STACK PIPE Black 48 RIGID VENT STACK PIPE Galvanized 48 RIGID VENT STACK PIPE Black 11 14 5 8 ADJUSTABLE VENT PIPE Black Only 2 90 ELBOW Galvanized 90 ELBOW Black 3 45 ELBOW G...

Страница 11: ...ypes of venting system installations A HORIZONTAL THROUGH THE WALL TERMINATION 1 Minimum rise 2 Elevated rise B VERTICAL THROUGH THE ROOF TERMINATION 1 Through typical roof 2 Through existing chimney...

Страница 12: ...pendicular to the wall The height of the opening must be located to meet all local and national building codes and not allow the termination to be easily blocked or obstructed If wall being penetrated...

Страница 13: ...system is attached If this is the case you may want to adjust the stove location 2 Locate position where vent pipe will pass through any ceilings and will penetrate the outside wall Since vent pipe s...

Страница 14: ...rilled hole placed in the roof in No 1 The opening should be a sufficient size to meet all clearance requirements Continue to assemble lengths of pipe and elbows necessary to reach the Ceiling Support...

Страница 15: ...tangular hole for the Support Box Cut the hole 1 8 larger than the Support Box outline Lower the Support Box through the hole in the roof until the bottom of the Support Box protrudes at least 2 inche...

Страница 16: ...through the center of the chimney system and center the Adapter on the top of the chimney pipe Drill 4 1 8 diameter holes through the Adapter and into the chimney top Insure that you are in fact drill...

Страница 17: ...2 1 3cm 5 8 1 6cm 1 2 1 3cm 40 100 1 2 1 3cm 1 2 1 3cm 3 4 2 0cm 1 2 1 3cm 100 150 3 4 2 0cm 1 2 1 3cm 7 8 2 3cm 5 8 1 6cm 150 200 3 4 2 0cm 1 2 1 3cm 7 8 2 3cm 3 4 2 0cm NOTE Some areas allow copper...

Страница 18: ...r s capacity is not sufficient to add the Gas Stove an additional inches to inches regulator must be installed for the Stove EXCEPTION Some codes allow 2 PSI 1 4KPA supplies to enter the residence in...

Страница 19: ...t be installed in accordance with instructions and local and national codes LIGHTING CHECK OFF LIST All items on Installation Check Off List see above must be completed If thermostat or remote control...

Страница 20: ...s in place cycle the burner again to make sure of prompt ignition of burner that flame runs smoothly around burner and does not lift off burner NOTE Flames may not come through coals until glass is in...

Страница 21: ...Log Fire View Figure 9 Log Module 2 0...

Страница 22: ...Carefully unpack one piece log assembly and center on log rest between Side Log Tabs Place log assembly over front locating pins 5 Place glowing embers wool sparsely on top coals in front of front lo...

Страница 23: ...ER DOES NOT COME ON IMMEDIATELY AFTER SECOND TRY RECHECK COMPLETE INSTALLATION OF LOGS PILOT ETC TO INSURE PROPER PILOT FLAME IMPINGEMENT ON THE THERMOPILE AND PROMPT BURNER IGNITION NEVER TURN BURNER...

Страница 24: ...in gas pressure B Carbon dirt or lint Have your gas supplier check for correct gas 7 W C Nat Gas 11 W C LP Gas If flame still needs adjustment see Flame Adjustment below Clean out carbon spider webs...

Страница 25: ...ves that are put in gas both natural and propane to make it smell can be harmful to glass and can leave a white film deposit on the glass This deposit can be removed with cleaners such as KEL KEM Poli...

Страница 26: ...side 7 18 50 01 00017 Pop Rivet 1 8 x 1 4 Aluminum WARNING Use only authorized parts and materials obtained from Johnson Gas Appliance when replacing defective or damaged glass DO NOT substitute other...

Страница 27: ...illivolt generation and assure trouble free burner operation Readings must be taken with a Pilot ONLY operating b Main Burner operating A PILOT ONLY OPERATING Thermostat OFF Minimum Millivolts 325 Usi...

Страница 28: ...e pg 20 for location Orifice is removed and installed with a deep well socket and ratchet 2 Install pilot orifice 05 04 00036 014 see pg 28 for location Remove and install pilot hood with 7 16 open en...

Страница 29: ...K 45 01 00101 908B STACK 6 RIGID VENT BLACK 45 01 00098 911B 11 14 ADJUSTABLE PIPE 45 01 00148 917B ADJUSTABLE PIPE 17 24 BLACK 45 01 00143 945BG ELBOW 45 DEG SWIVEL BLACK 45 01 00142 945G ELBOW 45 DE...

Страница 30: ...Piezo Igniter 65 14 00050 Main Orifice L P Gas 50 35 01 00239 Ember Wool 65 06 00435 Metallic Black Paint Spray Can 05 07 00061 Thermopile 50 06 00065 Door Latch 05 07 00067 Thermocouple 50 06 00064...

Страница 31: ...urer s specifications INSTALL PROPER SIZE GAS LINES CHECK FOR GAS LEAKS Per Manual CHECK FOR CORRECT GAS PRESSURE AT MANIFOLD Per Manual a 3 5 Inches Water Column Maximum Nat Gas b 10 5 Inches Water C...

Страница 32: ...TAPE SHUT POSTAGE NEEDED JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 3 1...

Страница 33: ...NOTES NOTES 3 2...

Страница 34: ...MENDOTA EXTENDED LIFETIME PROTECTION AND LIMITED WARRANTY MENDOTA MEDALLION SDV40 DIRECT VENT GAS STOVE 3 3...

Страница 35: ...warranted against burn out Mendota has the right to investigate and inspect the exact original stove and entire installation without any alterations or tampering in the event a claim is made to determ...

Страница 36: ...Johnson Gas Appliance Company 520 E Avenue N W Cedar Rapids IA 52405 WEBSITE www johnsongas com 0405 Part 85 03 00701...

Отзывы: