CAUTION:

  Each installation must conform to all local, state and national codes. Refer to the national fuel gas code and local zoning and code authorities 

for details on installation requirements. The Mendota Inserts must be vented to the outside in accordance with the latest edition of the National Fuel Gas 
Code.  In the absence of local codes, the installation must conform with National Fuel Gas Code ANSI Z223.1 (NFPA 54), or Canadian Code CAN1-B149 
or most current edition, also known as NFPA 54.  Do not connect this Insert to a chimney flue serving a separate solid fuel or gas-burning appliance. 

1.  Remove glass doors, metal fire screens, etc. from existing fireplace.  Be sure there is 12" minimum 

distance from top of upper grill to bottom of mantel; see Specifications (Pg.4 & 5), and a 16" mini-

mum non-combustible hearth extension in front of the glass surface if a raised hearth is not sup-

plied.  (See pg. 10 for "Raised Hearth"). 

 

2.  Remove any additional framework or other obstructions in the existing fireplace opening and burn-

ing area.  Also remove any chimney cap from top of chimney so that vent liner can be installed 

freely. 

 

3.  Before Insert is installed, have gas supplier or contractor run gas line to the existing fireplace.  Be 

sure gas plumbing instructions [see Pg. 11 & 12

 

are carefully followed.  Gas supply may enter fire-

place on either side or back of fireplace, whichever is most convenient and accessible.  Electrical 

service (120 volt) should also be supplied [See electrical requirements on Pg. 3 and blower instruc-

tions on Pg

26]. 

 

4.  The entire chimney should be swept to remove creosote, soot and any obstructions (bird nests, 

etc.). 

 

5.  Open fireplace damper.  If damper opening is large enough to accept the 4" and 3" flue liners, 

permanently secure damper in "open" position.  

NOTE:  

Massachusetts requires that the flue dam-

per must be removed or permanently welded in the "open" position. 

 

6.  If damper opening is too small for the 4" & 3" flue liners, it will be necessary to remove the damper 

handle and the damper plate.  Some damper plates are held in place by a pinned hinge that can be 

released easily by tapping out the pin with a hammer and punch.  Others may be held in place by a 
screw or bolt, or pivots may be cast into the damper housing.  The latter types may be harder to 

get out and may require sawing or breaking out.  [NOTE:  if flue size is 6" (127 mm) or less, or if 

severe offsets occur, or a significant mortar slop is evident between the liners, try to snake liner 

down the chimney to the top of the damper housing before breaking out damper plate and hous-

ing.] 

 

 

CAUTION:  If the 4" & 3" flue liners cannot be installed in an extremely tight chimney DO NOT pro-

ceed with installation. 

7.  If damper opening is narrower than 4-1/2" to 5" (114 mm to 127 mm) and if local code authorities 

allow, loosen and remove mortar behind back side of damper housing in the center of the opening 

enough to get the gripping teeth of a pipe wrench over the flange of the damper housing (for cast 

iron housings).  Tighten the wrench snugly, and kick down on the wrench handle to break out a 
half moon shaped piece of the damper housing, enough to easily fit the flex liner through it.  If the 

opening is wide enough, the break out is not necessary. 

8.

 

Install Insert only in chimney heights of 12' (minimum) to 35' (maximum) -- as meas-

ured in step  9  below.  

9.

 

Measure the chimney height from the top of the chimney (or the existing flue liner) to a point 24" 

(610 mm) above the floor of the fireplace hearth.  It may be necessary to drop a rope and measure 

the rope itself.  Be sure to allow for all offsets in existing chimney.  Cut the 4" and 3”diameter flex 

liner (s) to this measured length. 

 

 

Содержание FV44i

Страница 1: ...vir des t l phones se trouvant dans le batiment o vous vous trouvez Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournis seur Si vous ne pouvez rejoindre...

Страница 2: ...EAR BURNER 39 NAT GAS 54 L P GAS FRONT BURNER 46 NAT 56 LP OVERALL EFFICIENCY EXCEEDS D O E EFFICIENCY REQUIREMENTS A F U E FLUE VENT LINER CO LINEAR 4 DIAMETER EXHAUST 3 DIAMETER INLET NET WEIGHT 195...

Страница 3: ...t be placed on or near the Insert Mendota Inserts are designed for installation only in vented non combustible fireplaces Any fireplace in which an Insert is to be installed MUST be vented to the outs...

Страница 4: ...endota FV 44i I Fireplace Insert is a true high efficiency gas heater The Mendota Insert will usually heat a large area of your home if situated to maximize heat circulation NOTE The Mendota Insert is...

Страница 5: ...ey cleanouts must fit properly The refractory glass doors screen and log grates can be removed from the solid fuel fireplace to accommo date the gas insert Smoke shelves shields and baffles can be rem...

Страница 6: ...e 4 and 3 flue liners permanently secure damper in open position NOTE Massachusetts requires that the flue dam per must be removed or permanently welded in the open position 6 If damper opening is too...

Страница 7: ...t be vented vertically to the outside and must use the Mendota Co Linear flexible ducting system NOTE THE INSERT IS DESIGNED TESTED AND LISTED FOR OPERATION ONLY WITH MENDOTA INSERT VENTING COMPONENTS...

Страница 8: ...ch a sheet metal strap loop to the flex end of the liner s and tie a rope to it Two instal lers should proceed to the roof and drop the rope with weight on the end to make sure it goes all the way dow...

Страница 9: ...e opening Note Plug in the blower to a 110 volt AC recep tacle inside the fireplace opening if so equipped Re engage Slide Adapter and re install keeper plate as shown c Remove self tapping hex head s...

Страница 10: ...eling the unit may need to be shimmed with washers under the bottom corners of insert 22 The proper Insert Faceplate can now be placed in position Assemble surround by follow ing instructions supplied...

Страница 11: ...ds less than 16 refer to the diagram above and the following pro cedure to see if additional floor protection is required Project a line using string or a tape measure from the lower edge of the glass...

Страница 12: ...The proper gas line diameter must be selected to run from the supply regulator to the Insert Refer to the following table for proper gas pipe diameters PIPE LENGTH FEET SCHEDULE 40 PIPE INSIDE DIA TUB...

Страница 13: ...re to 7 W C 1 8 KPA Nat Gas This inches to inches regulator is of adequate capacity to service the gas appliances such as dryer furnace etc If this regulator s capacity is not sufficient to add the Ga...

Страница 14: ...e local or national installation code s to assure that adequate combus tion and ventilation air is available HIGH ALTITUDE INSTALLATIONS For installations from 610 1370 meters 2000 4500 ft the orifice...

Страница 15: ...tions in this ap pliance including field installed supply line fittings and all factory installed gas train connections between the gas valve and the burner orifice s and pilot light must be leak test...

Страница 16: ...tate th e tool 3 S lo w ly release the ten sio n o n th e latch 4 R em o ve th e Tool R ep eat th is p ro cedure on the rem ain in g latch LOG SET COALS AND EMBERS INSTALLATION INSTRUCTIONS Remove the...

Страница 17: ...quarter size pieces and place loosely at the rear edge of the back burner and in the gap between the front and rear burner as shown Tear some additional fiber embers into dime to nickel size pieces an...

Страница 18: ...17 Scatter loosely some of the smaller grey and black coals on top and among the fiber embers Tear up additional fiber embers and loosely place one more layer of embers on both burners...

Страница 19: ...ls to hide the burners The remaining smaller grey and black coals may be used to fill in the floor in front and at both ends of burners Use the remaining fiber embers to scatter over edges of burner P...

Страница 20: ...19 2 Left Grate Tine Place log 2 with groove on left grate tine Slide rearward until nose rests against stop on 2nd tine Place Log 3 over pin on Log 2 in position as shown 2 Log Stop 2 3...

Страница 21: ...20 Place Log 7 on right Grate Tine with log groove resting on the tine Place Log 6 over pin on Log 7 with left end of Log 6 against back edge of Log Stop 7 6 7 Log Stop...

Страница 22: ...21 Place Log 5 on Log 6 Log 1 in their notches Place Log 4 on top of Logs 1 Log 3 Place Log 8 in front of grate approximately as shown 6 5 1 4 3 1 8...

Страница 23: ...volt battery into the back side of remote control 7 Ignite pilot with remote control as follows Simultaneously press the OFF and UP ARROW buttons until an audible BEEP is heard This starts a timing se...

Страница 24: ...me nighttime setback and timer modes available The burner will actually turn down modulate as the room temperature nears the set temperature NOTE Refer to Page 24 for a remote programming example See...

Страница 25: ...24...

Страница 26: ...for service NOTE To clean glass remove glass and wipe glass with cloth or paper towel 2 A change in flame appearance or burn er operation A A change in gas pres sure B Carbon dirt or lint Have your g...

Страница 27: ...below Remove the brass cap from the regulator body with adjustable wrench or channel lock See the following page for details on converting this regulator 3 Re install the brass cap onto the regulator...

Страница 28: ...nnel lock pliars turn counter clockwise and observe the removable plastic stem 2 Snap out the plastic stem and rotate it to the LP Position 3 Reinstall regulator cap and stem Natural Gas Position as s...

Страница 29: ...Rear Orifices using the 1 2 deep well socket Reinstall the burners and venturi tubes into the air boxes Replace the 3 8 nuts and tighten completely Note Use these instructions to convert this unit to...

Страница 30: ...utilizing LP Gas will have a maximum input rate of 23 500 Btu Hr LEAK TESTING REQUIREMENTS Prior to completing the conversion process check for gas leaks with soap and water solution at all plumbing j...

Страница 31: ...l in all the information that is requested in these labels For LP installations from 610 1370 meters 2000 4500 ft the orifice sizes DMS for natural gas are 47 Front 39 rear and for propane gas are 57...

Страница 32: ...flow blowers are made of special alloy steel for constant high speed operation at high temperatures Blowers are equipped with long life maintenance free bearings that insure quiet operation and maximu...

Страница 33: ...natural and propane to make it smell can be harmful to glass and can leave a white film deposit on the glass This deposit can be removed with cleaners such as KEL KEM Polish Plus 65 06 00455 See your...

Страница 34: ...UTLET VENTS GAS FLAME ADJUSTMENT During the initial installation the air shutter opening should be checked to be certain that the shutter is set correctly at 1 8 to 1 4 open for natural gas and 1 2 mi...

Страница 35: ...ice person check the operation of the pilot and cycle the burner per LIGHTING INSTRUCTIONS see Pg 18 3 THE VIEWING GLASS SHOULD BE CLEANED PERIODICALLY Exterior glass may be cleaned with cleaner as de...

Страница 36: ...01 00113 Burner Tile HA 58 00029 Glass Frame Assembly 15 02 00088 Blower 35 01 00524 Log Set includes all logs 35 01 00495 Log 1 35 01 00496 Log 2 35 01 00497 Log 3 35 01 00498 Log 4 35 01 00499 Log...

Страница 37: ...36...

Страница 38: ...37 NOTES...

Страница 39: ...facturer s specifications CHECK FOR PROPER CLEARANCES TO COMBUSTIBLES Per pipe manufacturer s specifications INSTALL PROPER SIZE GAS LINES CHECK FOR GAS LEAKS Per Manual CHECK FOR CORRECT GAS PRESSURE...

Страница 40: ...39 TAPE SHUT JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 POSTAGE NEEDED...

Страница 41: ...m performance of any part of the limited warranty This warranty does not cover glass or log breakage Mendota has the right to investigate and inspect the exact original fireplace and materials in the...

Страница 42: ...Johnson Gas Appliance Company 520 E Avenue N W Cedar Rapids IA 52405 Website www johnsongas com or www mendotahearth com Part 85 03 00685...

Отзывы: