GENERAL FLUE VENTING INSTRUCTIONS 

The Mendota Fireplace must be vented using Amerivent, Duravent, Selkirk Metalbestos, Security Chimney or ICC Brand 
venting systems.  All warranties will be voided and serious fire, health or other safety hazards may result from any of the 
following actions:  Installation by unauthorized personnel; installation of any damaged component; unauthorized modifica-
tion of vent system; installation of any components not approved by Mendota; failure to meet all clearance requirements; 
failure to properly twist-lock and positively seal all components.  Consult local building codes before beginning the installa-
tion. 

WARNING 

Always maintain required clearances (air spaces) to combustibles to prevent a fire hazard.  Do not fill air spaces with insu-
lation.  Check installation instructions for minimum clearance requirements between the outer walls of the vent pipe and 
nearby combustible surfaces.  Be sure to check the vent termination clearance requirements from decks, windows, soffits, 
gas regulators, air supply inlets, and public walkways, as specified in these installation instructions and local building 
codes.  

SAFETY PRECAUTIONS FOR THE INSTALLER:

  1) Wear gloves and safety glasses for protection; 2) Exercise 

extreme caution when using ladders or on rooftops; and 3) be aware of electrical wiring locations in walls and ceilings. 

The gas appliance and vent system must be vented directly to the outside of the building, and never attached to a chimney 
serving another solid fuel or gas burning appliance.  Each direct vent gas appliance must have its own separate vent sys-
tem.  Common vent systems are prohibited. 

To assure proper venting performance of the high-performance Mendota Direct Vent Fireplace, it is critical that all brands 
of vent pipe sections are sealed tightly and leak-proof.  This means that all pipe sections must be carefully rotated into the 
fully "twist-locked" position.   

We Strongly Recommend That Fixed Length Pipe Sections Be Used In Place Of Telescoping Sections Whenever 
Possible. 

Note:  When using vent pipe and components that do not incorporate a fiberglass or graphite gasket at the joints, it is rec-
ommended that you use Milpak 1000F silicate stove sealant (#65-06-00909).  High temperature foil tape may be used on 
the outer (air intake) pipe joints. 

DO NOT SEPARATE ADJUSTABLE TELESCOPING SECTIONS.  THEY MUST BE USED AS COMPLETE 
ASSEMBLIES.

 

VENT COMPONENTS "TWIST-LOCK" CONNECTION PROCEDURE 

DuraVent and American Metals pipe and fittings are designed with special twist-lock connections.  Twist-lock 
procedure is as follows: four (4) indentations, located on the female ends of pipes and fittings are designed to 
slide straight in to the male ends of the adjacent pipes and fittings, by orient-
ing the four pipe identifications so that they match and slide into the four en-
try slots on the male ends (Figure 3). 
 
Push the pipe sections completely together then twist-lock one section 
clockwise, approximately ¼ turn until the two sections are fully locked.  The 
female locking lugs will not be visible from the outside on the black pipe or 
fittings.  They may be located by examining inside of the female ends

 

 

 

 

Figure 3:  Twist-Lock Piping

 

Содержание DT3-PF2-LX

Страница 1: ...s blessures ou la mort ATTENTION Garder l essence ou autres liquides produi sant des vapeurs inflammables loin del appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareil...

Страница 2: ...perate this appliance with the glass removed cracked or broken A licensed or qualified person should do replacement of glass This appliance must be installed in accordance with local codes if any if n...

Страница 3: ...IR SHUTTER SYSTEMS Externally controllable Rear Burner air shutter and Internal rotary Front Burner air shutter LOG SET 9 piece Premium Definition Log Set with Extreme glow and realism ember bed REFRA...

Страница 4: ...6 INSTALLATION CHECK OFF LIST 37 LIGHTING CHECK OFF LIST 37 BEFORE YOU BEGIN 38 REMOTE TRANSMITTER OPERATING INSTRUCTIONS 39 FIRST TIME PILOT LIGHTING INSTRUCTIONS 41 INITIALIZING THE REMOTE CONTROL S...

Страница 5: ...and certified by a nationally recognized testing and certification agency to American National Standards Institute ANSI Gas Appliance Safety Standards The Mendota Gas DXV Fireplace has been tested an...

Страница 6: ...5...

Страница 7: ...ding Code 3 A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a min imum height of eight 8 feet above grade directly in line with the exhaust vent...

Страница 8: ...rds of high surface temperature and should STAY AWAY to avoid burns or clothing ignition Young children should be CAREFULLY SUPERVISED when they are in the same room as the appliance These units MUST...

Страница 9: ...by a professional service person More frequent cleaning may be required due to excessive lint from carpeting bedding material carbon build up etc It is imperative that control compart ments burners a...

Страница 10: ...ower grills Always use Mendota grills and Mendota approved vent systems and vent caps A non combustible hearth protector is required and must extend a minimum of 12 in front of the fireplace If fire p...

Страница 11: ...4 x 6 5 8 Coaxial Vent Pipes AMERIVENT DURAVENT SELKIRK METALBESTOS SECURITY CHIMNEY and ICC brand pipes and venting compo nents may be used when venting off the top Venting off the top on the DXV 35...

Страница 12: ...hut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 PSIG 3 5 kPa A proper gas line diameter must be selected to run from the supply re...

Страница 13: ...ditional inches to inches regulator must be installed for the Fireplace EXCEPTION Some codes allow 2 PSI 1 4KPA supplies to enter the residence in which case pounds to inches regulators are used The f...

Страница 14: ...ve the terminal from the center line of the ter minal 12 inches 30 cm minimum Vinyl surfaces require 24 min K Clearance to a mechanical air supply inlet 6 feet 1 8 m minimum E Clearance to unventilate...

Страница 15: ...nother solid fuel or gas burning appliance Each direct vent gas appliance must have its own separate vent sys tem Common vent systems are prohibited To assure proper venting performance of the high pe...

Страница 16: ...ront surface but may not overlap the 2 black front surface Noncombustible material such as marble stones or brick can be installed over the 2 black surface only if you are certain that a Deerfield Fro...

Страница 17: ...21 32 GAS INLET DECREASED IN THE SAME MANNER BY 2 MANTEL MAY BE LOWERED MANTEL DEPTH INCREASE TRIANGULAR AREA FOR COMBUSTIBLE MANTEL 12 FOR EVERY 1 THE FIREPLACE IS RAISED OFF THE FLOOR HEARTH PROTEC...

Страница 18: ...7 PIPE 9 ATTIC INSULATION SHIELD 12 10 ROOF FLASHING 0 12 TO 6 12 10 ROOF FLASHING 7 12 TO 12 12 11 STORM COLLAR 12 VERTICAL VENT CAP 13 SUPPORT BAND 14 HORIZONTAL VENT CAP 15 FIRESTOP SPACER Figure 5...

Страница 19: ...NOTE FOR LPG AND HIGH ALTITUDE APPLICATIONS SEE PAGE 19 NOTE 12 MINIMUM VERTICAL PIPE CAN BE USED IF NO HORIZONTAL VENT SECTIONS GREATER THAN 6 or 7 ARE USED ALL OTHER INSTALLATIONS MUST FALL WITHIN...

Страница 20: ...requires 22 minimum height to center of vent cap CAUTION If 90 elbows must be used a 24 inch vertical starter section must be used off the top of the fireplace L P GAS OR HIGH ALTITUDE ABOVE 4 000 FT...

Страница 21: ...ngle opening in the wall The hole must be positioned so the vent system will run level or have a rise AND be perpendicular to the wall The height of the opening must be located to meet all lo cal and...

Страница 22: ...RT PLATE 45 01 00201 FLASHING 0 12 6 12 PITCH 45 01 00202 FLASHING 6 12 12 12 PITCH 45 01 00203 STORM COLLAR 45 01 00204 ATTIC INSULATION SHIELD 45 01 00206 CO LINEAR APPLIANCE ADAPTOR 45 01 00207 CO...

Страница 23: ...suring the total vent pipe run so you can more accu rately locate the point where the vent pipe will penetrate the outside wall See Figure 2 Exterior Vent Locations PG 13 Be sure all vent components a...

Страница 24: ...pening should be a sufficient size to meet all clearance requirements Continue to assemble lengths of pipe and elbows necessary to reach up through the roofline Galvanized pipe and elbows may be utili...

Страница 25: ...frame 2 Pull Glass Latch Tool outward about 3 8 3 Rotate Glass Latch Tool 90 degrees 4 Slowly Release Glass Latch Tool 5 Remove Glass Latch Tool To Latch Glass Frame Latches reverse steps 5 to 1 abov...

Страница 26: ...s Appliance Company Contact your dealer for more detailed ordering information GLASS FRAME ASSEMBLY REPLACEMENT PARTS LIST ITEM PART NUMBER DESCRIPTION 1 HA 30 00411 FRAME WELDMENT GLASS DXV35 DT 3 2...

Страница 27: ...logs Coals must not block pilot or burner flames Placement of coals has a big effect on front burner flame ap pearance and glow of coals More coals less yellow flame and more glow Fewer coals more yel...

Страница 28: ...LOG 1 REAR LOG ON REAR SHELF BEHIND REAR BURNER SLIDE LOG TO RIGHT UNTIL LOG TOUCHES RIGHT SIDE BRICK PANEL PUSH LOG BACK SO IT TOUCHES REAR BRICK PANEL THIS LOG IS RECOMMENDED TO BE PUSHED TO THE FAR...

Страница 29: ...F LOG 2 DOES NOT SIT BETWEEN REAR AND FRONT BURNER PLACE LOG 2 BETWEEN THE TWO BURNERS AND SLIDE TO THE RIGHT UNTIL THE CURVATURE IN THE FRONT BURNER CONTACTS THE CURVATURE ON THE RIGHT FRONT TIP OF L...

Страница 30: ...O THERE IS A NOTCH THAT MATES WITH THE LEFT MOST GRATE BAR SET LOG 3 ON THE GRATE BAR AND THE RECTANGLE SHAPED AIR SHUTTER BOX TOP SURFACE LOG 3 MUST LEAVE CLEARANCE FOR THE REAR BURNER PORTS SOME ROT...

Страница 31: ...ST GRATE BAR ON THE FAR RIGHT SIDE SOME ROTATIONAL FLEXIBILITY IS ALLOWED TO LOG 4 AROUND THE PIN AND HOLE HOWEVER DO NOT ROTATE REAR END OF LOG OUTWARD ROTATE INWARD ONLY IF DESIRED ROTATING OUTWARD...

Страница 32: ...LOG 5 HAS A HOLE THAT ALIGNS WITH THE LEFT SIDE PIN ON LOG 1 THE V NOTCH BETWEEN THE TWO BRANCHES MUST SIT DIRECTLY ON TOP OF THE REAR BURNER S LEFT SIDE PORTS AND MUST ALLOW THE FLAMES TO RISE INTO...

Страница 33: ...LOG 6 HAS A HOLE IN ITS BACK SIDE TO MATE WITH THIS PIN PLACE LOG 6 ON TOP OF LOG 1 S PIN THE OTHER END OF LOG 6 SITS ON TOP OF LOG 2 AS SHOWN BELOW SOME ROTATIONAL FLEXIBILITY IS ALLOWED FOR LOG 6 T...

Страница 34: ...TOP OF THE FRONT BURNER S REAR VISIBLE EDGE AND ON TOP OF LOG 4 THIS LOG IS DESIGNED TO HIDE THE PILOT LIGHT PLACE THIS LOG SO IT PROVIDES CLEARANCE TO ALL BURNER FLAMES AND PILOT FLAMES YET POSITIONE...

Страница 35: ...N THE POSTION SHOWN HERE LOG 8 SITS ON TOP OF LOG 2 AND RESTS AGAINST THE GRATE BAR 2 ND FROM LEFT ATTEMPT TO POSITION LOG 8 AS SHOWN HERE FOR THE BEST GLOW EFFECT AND REALISTIC LOOK DO NOT PINCH FRON...

Страница 36: ...OF THE FRONT BURNER PORTS AND DO NOT PLACE THIS LOG ON TOP OF LOG 2 SCATTER SMALL COALS ON THE FLOOR AND BETWEEN THE LOG GRATE S HORIZONTAL BAR AND THE FRONT BURNER A FEW COALS MAY SIT ON TOP OF THE F...

Страница 37: ...COMPLETED LOG SET ASSEMBLY...

Страница 38: ...rrect gas pressure proper size gas lines and for gas leaks q 120 V electrical service and gas supply must be installed in accordance with instructions and local and national codes LIGHTING CHECK OFF L...

Страница 39: ...will stay functioning until the room temperature in creases 1 o F above the Set Point Temperature To increase the Set Point Temperature Press the UP button until the desired temperature is displayed...

Страница 40: ...uish If in Standing Pilot Mode the pilot light will remain ON Note If in SMART model the flame height function is not available for manual adjustment In SMART mode the flame height regu lates automati...

Страница 41: ...bat teries are low a Battery Icon will appear on the LCD display of the Transmitter before all battery power is lost When the batteries are replaced this icon will disappear OPERATING DURING POWER OUT...

Страница 42: ...ghts and the pilot is burning steadily 7 Once the pilot flame is lit and well established close glass door WARNING NEVER IGNITE MAIN BURNERS WITH GLASS DOOR REMOVED OR OPEN Doing so will lead to damag...

Страница 43: ...ode turns the pilot light OFF when the fireplace is not functioning and only lights the pilot light automat ically when a call for heat is made by the remote control CPI Standing Pilot Mode If set to...

Страница 44: ...DURING POWER OUTAGES This electronic ignition system utilizes the supplied 120VAC power when it is available for all functions of this system If the AC power is interrupted during a power outage this...

Страница 45: ...inated Please allow adequate operational time a minimum of 2 weeks for the blowers to break in before you contact your dealer for service WARNING Label all wires prior to disconnection when servicing...

Страница 46: ...ner and logs are properly installed After logs have been properly installed and operated for one to one and a half hours small additional adjustments to the air shutter may be necessary for final flam...

Страница 47: ...Interior glass surface should be cleaned using only soap and water or KEL KEM Polish Plus or comparable product CAUTION Do not use oven cleaner to clean glass Never touch glass or attempt to clean wh...

Страница 48: ...ota service person contacted Be sure logs are re installed per instructions D Check condition of glass door gasket gasket must seal tightly over firebox replace if necessary E Periodically check to ve...

Страница 49: ...SCHEMATICS Note The DXV35 DT3 LX ignition system utilizes Transformed DC power for normal ignition functions In the event of a power outage the Battery Pack power is utilized IGNITION SYSTEM WIRING S...

Страница 50: ...it HA 30 00507 is Optional and must be purchased separately LP Conversion Kit HA 30 00507 contains the following parts One Motorized LP Pressure Regulator 907 012 and two Cap Orifices 65 14 00364 dril...

Страница 51: ...tightly loosen Pilot Light s hex shape base using a open end wrench Rotate counter clock wise turn to loosen 8 Pilot arrives from the factory set for NG Push NG LP Adjustment Clip inward all the way t...

Страница 52: ...burner is run ning parallel to front face of unit positioned properly so that the pilot light hood pointing to the left is pointed properly towards the burner s flame propagation ports 13 Make certain...

Страница 53: ...TRUCTIONS WILL RESULT IN A LEAK OR OVERFIRING OF THE APPLIANCE AND CAN LEAD TO AN EXPLOSION OR A FIRE HAZARD 1 Remove the Courtesy Access Panel mounted behind the lower grill and lay down gently witho...

Страница 54: ...olution at all plumbing joints prior to placing this appliance into operation It is recommended that all gas plumbing joints factory installed and field installed are checked for leaks PILOT FLAME AND...

Страница 55: ...ust for varying altitudes the information sticker must be filled out by the installer and adhered to the appliance at the time of conversion Cet appareil est equip pour des altitudes compries entre 0...

Страница 56: ...64 R H BLOWER WITH MOTOR HA 82 00408 FRONT BURNER TUBE WELDMENT 15 02 00065 L H BLOWER WITH MOTOR HA 30 00510 VALVE ASEMBLY DXV35 DT3 05 01 00157 SNAP DISC FAN TEMP SENSOR 10 01 00003 RHEOSTAT BLOWER...

Страница 57: ...in the diagram below Any material that protrudes into this area on the sides top or bottom edges can only be flush with the front surface of the fireplace faceplate If planning to install either the...

Страница 58: ...m The top and sides of these trim kits fit within the inner perimeter of the Fireplace s Face plate The bottom member of this trim however overlaps the bottom 2 black boarder of the fireplace front fa...

Страница 59: ...58 RATING LABEL REPRESENTATION DXV35 DT3...

Страница 60: ...59 THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 61: ...60 THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 62: ...m vertical horizontal and vent runs q CHECK FOR PROPER CLEARANCES TO COMBUSTIBLES VENT LOCATIONS Per Manual q INSTALL PROPER SIZE GAS LINES CHECK FOR GAS LEAKS Per Manual q CHECK FOR CORRECT GAS PRESS...

Страница 63: ...62 TAPE SHUT JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 POSTAGE NEEDED...

Страница 64: ...ses that have not received prior written approval from Mendota NOTE Minor warping of certain parts or discoloration is normal and is not a defect covered by this warranty Major warping of parts can be...

Страница 65: ...Johnson Gas Appliance Company 520 E Avenue N W Cedar Rapids IA 52405 Mendota Hearth Division WEBPAGE www johnsongas com or www mendotahearth com Document 85 03 00906...

Отзывы: