BL1448GE
ZP-BL16E
TM1700-sEriEs
73
6 APPLiCATiON EXAMPLEs
6.2 Example 2
3-phase circuit breaker with
two interrupters per phase and
separate operating mechanism
How to connect (per phase)
Test quantities
▪
Main contact timing measured by the Timing M/r section
▪
Auxiliary contact timing (one a & one b contact) measured
by the Control section
▪
Coil current & voltage measured by the Control section
Transducer in use
▪
n/a
Others
▪
No resistor contacts, no grading capacitors
Necessary settings in Breaker View
Breaker View
Number of phases
3
Operating mechanism
separate
Number of interrupters per phase
2
resistor contacts
None
Number of a-contacts
1
Number of b-contacts
1
Breaker View \
Pulse & Delay Times
These settings are depending on the circuit breaker
type. if you are uncertain please refer to the breaker
manufacturers data.
Breaker View \
Measurement Preferences
Coil current
On
Control voltage
On
static voltage
On
Breaker View \ Measurement Preferences \
Measurement Time & Sample Interval
The default settings should be sufficient in most of
the cases.
Breaker View \ Measurement Preferences \
Motion Measurement Preferences
Transducer type
Off
Содержание TM1700 Series
Страница 2: ......
Страница 15: ...BL1448GE ZP BL16E TM1700 series 15 3 System overview...
Страница 25: ...BL1448GE ZP BL16E TM1700 series 25 4 CABA Local...
Страница 61: ...BL1448GE ZP BL16E TM1700 series 61 5 Perform testing...
Страница 75: ...BL1448GE ZP BL16E TM1700 series 75 7 Specifications...
Страница 85: ...BL1448GE ZP BL16E TM1700 series 85 10 Quick Guide...