Figure 28 - Report Options Screen
The user can select to show or hide Comments and/or Deficiencies in the test report. The user may also
choose to delete the selected test section or close the test report.
Contact Resistance and/or Insulation Resistance test results can also be added to the Test results using
the Insulation/Contact Resistance button
. Press either Close Report to return to the test screen or
press Cancel to return to the report. To exit the report, press the Check
button in the top left corner
or select the Options button followe
d by the ‘Close Report’ button.
3.4.2
Testing Instantaneous Pickup
1) Select the appropriate output terminal (see section 3.2, Selection of Output Terminal) and connect
one end of a high-current lead to one side of thermal element or current coil on the overload relay or
breaker. Connect the other test lead to the COMMON terminal of the test set.
2) To monitor dry contacts, connect a pair of light leads (timer leads) from Normally Closed Contacts or
Normally Open Contacts of overload relay to binding posts of test set BINARY INPUT terminals.
3) Enter the desired starting current value (normally start at a value of 20% below the expected pickup)
by pressing the Requested Current window, and enter the amplitude using the numeric keypad.
4) Press the Mode button and set to the Momentary Mode.
5) Press the Blue Play button, and the Pulse Test Parameters screen will be displayed (Figure 28).