Settings
50
5.4
PRPD diagram display settings
If necessary, the display settings for the PRPD diagram can be adjusted. To do so,
proceed as follows:
1. Tap the
button in the main menu and open the
PRPD
settings menu.
2. Adjust the parameters to your specifications.
Parameter
Description
Threshold
Lower threshold for the charge level shown in the diagram.
Max Quantity
This value defines the upper quantity threshold.
If this value was set at 50 as shown in the example below, a
total of 50 charge pulses with the exact same amplitude and
phasing must be measured before the right-hand end of the
colour scale is reached.
Every further pulse measured with these values no longer
causes a change of colour.
Max Level
This value defines the maximum value on the Y-axis and can
be set to between 40 and 100 dB.
When set to
Auto
, the measurement starts with an upper limit
of 40 dB and ist he automatically increased, if higher values are
measured.