Performing measurements
32
4.4
Standard measurement
Directly after selecting the operating mode, the measurement screen opens and the
device starts to record measured data. Measured data should be recorded for at least
10 seconds while the sensor being used is in contact, or aligned, with the measurement
object in the correct way (see section 3).
After doing so, the measured data can be saved using the
button, which appears on
all measurement screens (not, however, on the camera screen). Saving again over the
course of further measurements is also possible without problems. In this case, the data
are filed in the same measured data folder as an additional data set.
The
button can be used to switch between the different measurement screens
described in the following sections.
Once the measurement using the respective sensor has been completed on the
measurement object,
can be used to open the screen for selecting the operating
mode and another measurement with a different type of sensor can be started on the
same measurement object straight away. The measured data are saved in the same
measured data folder.
If, in contrast, the measurement is to be continued on another measurement object, a
new measured data folder must be created in advance (see page 25).
Basic procedure