MPQ1000 Operation
MPQ1000-UG-EN Rev 6 April 2020
33
NOTE: If the active channel is grayed out then this means that channel is required for
power and energy calculations and cannot be disabled.
If using not self-identifying current clamps then the full scale range of these current
clamps can be set from this screen.
Current ratios and voltage ratios can also be set from this screen.
3.
Under the INTERVALS tab, use the arrow keys and ENTER
key to set
recording intervals for RMS intervals, demand (power and energy) interval as well as
the THD interval. The THD interval will also include the harmonics and inter-
harmonic interval.
The declared voltage can be set. When
Set to Auto
the unit will automatically measure
the value on the line and set the limits based on the measured value. When a declared
value is set then the limits will be configured based on the selected declared value.
The event limit percentage can be selected from this screen. This is the percentage of
the declared voltage that the analyzer will use when setting its limits.