4 FUNCTIONS AND SET UP
4.6 Data logger – LOG
The data memory can store totally 190 measurements
and this capacity is shared by the two log modes.
SET / LOG
Display abbreviations / description
SEL
Select
oFF
OFF
1A1
Label for Breaker, Phase, Interrupter
1234
Running numbers
LOG modes
OFF
When the log is OFF only the latest value is stored and only
until the performance of a following measurement, which
overwrites the previous one.
Circuit breaker testing mode,1A1
This mode is primarily designed for measurement on circuit
breakers. The three characters (1A1) are supposed to indi-
cate: Breaker, Phase, Interrupter.
Measurement is automatically stored, provided that
there are less than three measurements stored on the
selected object label. Each label can store three meas-
urements. See also section 5.6 Measurement using
the log function.
Running numbers mode, 1234
The measurements are numbered in numerical order (1 to
1999)
Measurement is automatically stored, provided that
the memory is not full.
Set-up
1]
Select
SET / LOG.
Present setting is displayed.
2]
Press and hold
OK
key until characters start
to blink under the "SEL" letters.
3]
Use the
▲ ▼
keys to select mode.
4]
Press
OK
key.
Содержание MOM2
Страница 1: ...WWW MEGGER COM User s Manual MOM2 MOM2 Win Micro ohmmeter Art No ZP BD03E Doc BD0333FE V06a 2016...
Страница 2: ......
Страница 13: ...BD0333FE ZP BD03E MOM2 13 4 Functions and set up...
Страница 31: ...BD0333FE ZP BD03E MOM2 31 6 Application examples...
Страница 43: ...BD0333FE ZP BD03E MOM2 43...
Страница 46: ...46 MOM2 ZP BD03E BD0333FE Index...
Страница 47: ......