6 APPLICATION EXAMPLES
6
A
pplication examples
6.1 Safety
Important regarding all testing
Read and comply with the
safety instructions.
Always comply with local
safety regulations.
Important
Note
If you are measuring resistance in a circuit
breaker or disconnecting switch (isolator),
make sure that it is closed and grounded at
both sides before testing.
6.2 Measurement using
Kelvin probes
An example how to perform testing using the two
Kelvin probes. This example describes the perfor-
mance if you only want to know if the test object pass
a preset value and you do not need to store the test
results.
1]
Select
LOG
function "OFF", and set
P/F
value
(see section 4.6 and 4.7).
2]
Attach the test cables with Kelvin probes (2 x
1.3 m) one with a trigger, to MOM2.
3]
Turn the function selector to desired posi-
tion.
4]
Hook the instrument to your belt or use the
strap.
5]
Press and hold the two Kelvin probes to the
test object and pull the trigger.
If the value is outside the limits there is a
sound telling the result was fail.
The measurement value remains until an-
other measurement is performed or until the
instrument is switched off.
Measurement on a test object
Содержание MOM2
Страница 1: ...WWW MEGGER COM User s Manual MOM2 MOM2 Win Micro ohmmeter Art No ZP BD03E Doc BD0333FE V06a 2016...
Страница 2: ......
Страница 13: ...BD0333FE ZP BD03E MOM2 13 4 Functions and set up...
Страница 31: ...BD0333FE ZP BD03E MOM2 31 6 Application examples...
Страница 43: ...BD0333FE ZP BD03E MOM2 43...
Страница 46: ...46 MOM2 ZP BD03E BD0333FE Index...
Страница 47: ......