DER1 digital regulator instruction manual - rev. 03 - pag. 35 

3.  Description of Function 

 
The  DSR  Terminal  user  Interface  is  presented  as  shown  in  figure  15  and  permits  programming  and 
monitoring  from  1  to  32  slave  units  connected  through  serial  RS485  or  a  single  unit  connected  through 
RS232. The functions available are shown in table 20. 
The DSR Terminal user interface is divided into 6 areas with different functions. 
 

Transmit : 

Handles data transmitted towards slave units (DSR/DER1) 

Receive : 

Displays a single datum requested from slave units (DSR/DER1) 

Cyclic  Read  : 

Displays,  almost  in  real  time,  four  pieces  of  information  memorised  on  consecutive 

locations in the slave unit (DSR/DER1) 

STATUS  : 

Displays registries from 36 to 39 (measured voltage, measured frequency, active alarm flags 

and configurations) 

ALARMS : 

Displays active alarms (alarms and individual word alarm flags are shown in table 13). 

COMMUNICATION :

 Displays the status of communication 

 

The 

Configuration 

Menu

 

 

The 

Configuration 

Menu  is  indicated  in  figure  16;  it  permits  setting  of  configuration  flags  of  the  DSR/

DER1 regulator (parameter P[10]).  
 

File 

Menu

 

 
The 

File 

Menu presents the single option of Exit, to close the DSR/DER1 Terminal user interface. 

 

Up/Dw 

Menu

 

 
The 

Up/Dw 

Menu  is  used  to  load  and  unload  settings  files  to  and  from  the  regulator  (which  have  the 

extension .dat). The list of parameters is shown in table 6. 
There are three possible options: 

1.  Upload Data

 The “Upload” window opens

 

• 

The key 

Open 

allows selection of files with the .dat or .set extension, which must be loaded. 

• 

The 

Upload 

key unloads the parameters of settings files into the DSR/DER1 regulator; if the file has 

been opened with the .dat extension, all of the parameters are updated, if the file has been opened 
with  the  .set  extension,  only  the  parameters  from  10  to  30  are  updated,  leaving  those  from  0  to  9 
unaltered. 

• 

The key 

Done 

closes the Upload window 

2.  Download Data: 

The “DownLoad” window opens

 

• 

The 

DownLoad 

key transfers the settings files to the personal computer. 

• 

The  key 

SaveAll 

permits  the  operator  to  save  the  entire  settings  file  (from  0  to  30)  with  the  .dat 

extension. 

• 

The key 

SaveSettings 

allows you to save the file with customised data (parameters from 10 to 30) 

with the .set extension. 

• 

The key 

Done

 closes the DownLoad window. 

3.  DownLoad Alarm: 

The “DownLoad Alarm” window opens

 

• 

The key 

DownLoad 

transfers the list of memorised alarms to the personal computer, as many times 

as the alarms intervened and, for each of them, the duration of the last event and the overall duration. 

• 

The key 

Save 

allows the operator to save the alarms file with the .alr extension. 

• 

The key 

Done

 closes the DownLoad Alarm window. 

 

The 

About 

Menu

 

 

The 

About 

Menu signals the current release of the DSR Terminal software. 

Содержание DER1

Страница 1: ...64 93 8552 20 53 41 831 429 08 12 3843 20 46 81 383 227 86 73 3812 21 46 40 4862 44 53 42 3532 37 68 04 8412 22 31 16 342 205 81 47 863 308 18 15 4912 46 61 64 846 206 03 16 812 309 46 40 845 249 38 7...

Страница 2: ...Status Word Location L 39 pag 18 SETTING OF VOLT STAB AMP and Hz PARAMETERS pag 19 1 Voltage pag 19 1 1 Setting voltage pag 19 1 2 Soft Start pag 19 1 3 Slow voltage variations pag 20 2 Stability pag...

Страница 3: ...gured to obtain the best performance most of the settings are stored in a non volatile integrated memory EEPROM The first time the regulator is turned on a default configuration will be present which...

Страница 4: ...ized conditions load temperature Transient voltage drop and overvoltage within 15 Voltage recovery time within 3 of the value set in less than 300 msec Programmable Soft start Parameters VOLT STAB AMP...

Страница 5: ...Range 2 TABLE 2 CONNECTOR CN3 23 Common Active protections output Current 100mA Voltage 30V Max length 30m 3 Both activating alarm and delay time are programmable 24 A P O 25 Common Jumper 50 60Hz Typ...

Страница 6: ...ation overcurrent protection TABELLA 3 TRIMMERS Fig 1 INSTALLATION Upon receipt of the digital regulator perform a visual inspection to ensure that no damage has been sustained during transportation a...

Страница 7: ...or connections depend on the application and excitation system Figure 1 shows the functional aspect of the connection points to the regulator An error in connection may have deadly consequences for th...

Страница 8: ...tes Series star H SCC0160 H SCC0158 F N A F N A 530 550 575 600 690 760 800 920 960 from 520 to 1000 F SCC0161 F SCC0159 1200 from 1100 to 2000 F SCC0202 2 channels in series Parallel star 190 200 208...

Страница 9: ...rom the Configuration Menu 4 The parameter present in parameter P 5 if three phase sensing or p 6 if single phase sensing has to be calibrated Calibration should be adjust in order to obtain 225V from...

Страница 10: ...DER1 digital regulator instruction manual rev 03 pag 10 SCC0158 Three phase sensing 75V 150V...

Страница 11: ...DER1 digital regulator instruction manual rev 03 pag 11 SCC0159 Three phase sensing 150V 300V...

Страница 12: ...DER1 digital regulator instruction manual rev 03 pag 12 SCC0160 Single phase sensing 75V 150V...

Страница 13: ...DER1 digital regulator instruction manual rev 03 pag 13 SCC0161 Single phase sensing 150V 300V...

Страница 14: ...DER1 digital regulator instruction manual rev 03 pag 14 SCC0202 Single phase sensing 300V 600V...

Страница 15: ...DER1 digital regulator instruction manual rev 03 pag 15 SCC0203 Single phase sensing 300V 600V generator in threephase ZIG ZAG connection...

Страница 16: ...voltage can be controlled by software as well with the P 19 The excursion range and gain of the remote control can be set independently by software despite the output voltage control device system us...

Страница 17: ...protection of up to 20 with respect to the nominal speed value set by the 50 60 jumper if activated or by the 50 50 box in the Configuration menu at 50 Hz the threshold can be calibrated from 40 Hz to...

Страница 18: ...6 126 126 18 Step limitation reference 20 20 0 8 19 Vout Reference 6 9 9 0 0 8 20 Stability 6 9 9 16384 16384 8 21 A D A 6 9 9 16384 16384 FG 8 22 4 6 9 9 16384 16384 8 23 2 6 9 9 9000 9000 2 24 2 6...

Страница 19: ...ltage reaches the limit foreseen for input to which it is applied see Para 8 Remote control of voltage If saturation is enabled in the event of removal of the Vext Pext connection due to accidental op...

Страница 20: ...ated voltage tenths of volts 37 Second status word 0 900 Read only Frequency tenths of Hz 38 Third status word 16bit Read only Active alarms 39 Fourth status word 16bit Read only Active configuration...

Страница 21: ...cale H on sensing inputs 4 5 9 10 11 12 14 17 and 19 22 between 150 300 Vac scale F There are two ways to set from minimum to maximum value 1 With the VOLT trimmer which must be enabled by the Configu...

Страница 22: ...to obtain the desired gain i e parameter P 11 4 coefficient 24 16 The regulator diagram is shown in figure 6 KP KI s Ref Feedback Error PIout figure 6 Regulator Diagram 3 EXCITATION OVERCURRENT 3 1 D...

Страница 23: ...nderspeed protection threshold rotating the Hz trimmer counter clockwise if it has been enabled from the Configuration Menu or by entering 0 at parameter P 21 2 Rotate the AMP trimmer completely in th...

Страница 24: ...proportionately reduced as indicated in figure 8 Parameter P 23 sets the slope of the voltage frequency curve the default value is 9000 An increase in the value of P 23 involves a greater reduction of...

Страница 25: ...ues between 65535 1 and 32768 32767 lower the threshold proportionately to 50 Hz and 60 Hz respectively values between 0 and 32767 raise the threshold proportionately respectively to 60 Hz and 72 Hz r...

Страница 26: ...ge a decrease in the value of P 24 will cause a lower reduction in voltage up to the limit of P 24 0 which means that no reduction in voltage will take place WARNING If the voltage is not lowered enou...

Страница 27: ...age 5 Excitation Overcurrent APO Reduction of excitation current 6 Underspeed APO V F Ramp 7 Overspeed APO TABLE 12 ALARMS LIST TABLE 13 ALARM FLAGS AT LOCATION L 38 6 5 J 9 6 6 9 J 6J J 5 5 J J 12 1...

Страница 28: ...ted short circuit time goes from 0 1 to 25 5 seconds programmable in 100 ms steps then the regulator is blocked after saving DD and TT and signals the STOP status With the time in short circuit set on...

Страница 29: ...for which the APO must be activated obtaining a number B Example since it is desired to activate the APO in the case of over voltage and overspeed the formula is B 2 64 66 b Multiply the delay it is...

Страница 30: ...serial interfaces available on the DI1 communications unit are RS232 without handshake 3 wires on CN3 connector _____ RS485 two wires half duplex on CN4 connector DTE 1 Tx RTSRx RTS The connection be...

Страница 31: ...ector CN1 terminals 1 and 4 1 through a dedicated source AC 40V 15Hz 270V 72Hz or DC 40V 380V 3 Alternatively on connector CN5 terminals 1 and 2 through a completely isolated source in DC 9 14V WARNIN...

Страница 32: ...ational parameters reading of stored alarms A standard serial cable may be used with 9 pins SUB D connectors TABLE 18 CONNECTOR CN4 Pin N Description Notes 1 485 A RS485 channel A Insulated 2 485 B RS...

Страница 33: ...regulator instruction manual rev 03 pag 33 Fig 12 RS232 connection between one DSR regulator and PC through DI1 digital interface Fig 13 R485 connection between DSR regulators and PC through DI1 digit...

Страница 34: ...tor 15 goes from red to green IMPORTANT The communication may take place only if all three of the indicators Connected 16 Com STAT 15 and Com ERROR 14 are green The ADDRESS window indicates the slave...

Страница 35: ...tings files to and from the regulator which have the extension dat The list of parameters is shown in table 6 There are three possible options 1 Upload Data The Upload window opens The key Open allows...

Страница 36: ...equency protection threshold equivalent to Hz 22 16384 Excitation overcurrent threshold equivalent to AMP 23 9000 V F slope 24 6000 V F slope at start up 25 20 Short circuit time in tenths of a second...

Страница 37: ...1 digital regulator instruction manual rev 03 pag 37 Fig 15 DSR Terminal User Interface Fig 16 Configuration Menu 1 3 2 4 6 5 9 8 7 12 14 16 17 15 11 10 13 31 18 19 20 21 22 23 32 33 24 25 26 27 28 29...

Страница 38: ...parameters requested from the regulator 9 Activation of updating almost in real time 10 Visualisation of the regulator status voltage frequency active alarms configuration 11 50 60Hz Jumper inserted...

Отзывы: