DER1 digital regulator instruction manual - rev. 03 - pag. 20
NOTE 1: depending on the sensing and nominal frequency
Tabella 8: Funzioni dei bit della Quarta Word di stato (Configurazione attiva)
TABLE 10 :STANDARD VALUES OF THE FOURTH STATUS WORD (LOCATION L[39])
Sensing
50Hz
60Hz
Single phase
7956
24340
Three phase
8016
24400
Rated frequency:
Bit
Function
Value
/
B0
Not used
1
0
B1
Bit activating a periodical variation of reference voltage
2
0
B2
Bit activating automatic compensation of the offset in voltage acquisition channels
4
0/1
B3
Not used
8
0
B4
Bit enabling reading of 50/60 Hz jumper hardware
16
1
B5
Free for future use
32
0
B6
Three phase sensing active
64
0
B7
Voltage remote control by RAM location L[49] or input saturation ( in case of overflow )
128
0
B8
Bit enabling reading of reference voltage by VOLT Trimmer
256
1
B9
Bit enabling reading of stability parameter by STAB Trimmer
512
1
B10 Bit enabling reading of underspeed protection threshold by Hz Trimmer
1024
1
B11 Bit enabling reading of excitation current threshold by AMP Trimmer
2048
1
B12 Bit enabling reading of external voltage input
4096
1
B13 Bit enabling DAC
8192
0
B14 60Hz active setting (jumper 60Hz closed and/or 60Hz active setting on configuration menu)
16384
0/1
B15 Reserved
32768
0
TABLE 11 : BIT FUNCTION OF THE FOURTH STATUS WORD L[39] ( ACTIVE CONFIGURATION )
4. Volatile memory addresses
--'
Add name
Range
Access
Description
32 VOLT Trimmer
0..32767 Read only
VOLT Trimmer Position
33 STAB Trimmer
0..32767 Read only
STAB Trimmer Position
34 Hz Trimmer
0..32767 Read only
Hz Trimmer Position
35 AMP Trimmer
0..32767 Read only
AMP Trimmer Position
36 First status word
0..3200
Read only
Regulated voltage [tenths of volts]
37 Second status word
0..900
Read only
Frequency [tenths of Hz]
38 Third status word
16bit
Read only
Active alarms
39 Fourth status word
16bit
Read only
Active configuration
40 Commands
16bit
Write
Reserved Word Commands – Do not use
41 Pext/Vext Inputs
0..32767 Read only
Analogical input or external potentiometer value
42 Setpoint
0..32767
Read only
Setpoint value
43 Setpoint
0..32767 Read only
!8# '
44 Measured Voltage
0..32767 Read only
Internal variable
45 Estimated temperture
0..32767 Read only
Estimates temperature of exciter windings
… …
…
49
!-
0..32767 Write
Used if Vext input is disabled and voltage remote
control by RAM location is enabled (P[10]-Bit B7=1)
50 Peak to peak voltage
0..32767 Read only
Internal variable
51
$ "
0..32767 Read only
Internal variable
52 Offset voltage
0..32767 Read only
Internal variable (active only in single phase sensing)
… …
0..32767
…
TABLE 9 : VOLATILE MEMORY ADDRESSES
5. Fourth Status Word (Location L[39])
Location L[39] indicates (almost in real time) the active configuration at any given time; it is not a simple
replication of the value recorded in parameter P[10], however, inasmuch as the bits B2, B6 and B14 adjust
their value only on the basis of the configuration set, but also of the effective operational status of the
DER1 at that time; for example, if the regulator is connected with three phase sensing, even if bit B6 of the
configuration word is set on 0 (automatic recognition of single phase – three phase activation), bit B6 of
location L[39] will have a value of 1; similarly, if the 60 Hz jumper is engaged and reading is enabled 8Bit
B4 of parameter P[10] set on 1), bit B14 of location L[39] will have a value of 1 even if the corresponding
bit B14 of the configuration word is set on 0.
The values of the fourth word of status (location L[39]) are shown in table 10, on the basis of the type of
sensing and nominal frequency.
Содержание DER1
Страница 10: ...DER1 digital regulator instruction manual rev 03 pag 10 SCC0158 Three phase sensing 75V 150V...
Страница 11: ...DER1 digital regulator instruction manual rev 03 pag 11 SCC0159 Three phase sensing 150V 300V...
Страница 12: ...DER1 digital regulator instruction manual rev 03 pag 12 SCC0160 Single phase sensing 75V 150V...
Страница 13: ...DER1 digital regulator instruction manual rev 03 pag 13 SCC0161 Single phase sensing 150V 300V...
Страница 14: ...DER1 digital regulator instruction manual rev 03 pag 14 SCC0202 Single phase sensing 300V 600V...